| 1 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 2 | 12 way (4 + 36), Double door |
| 3 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 4 | 8 way (4 + 24), Double door |
| 5 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 6 | 125 A,36KA, FP MCCB |
| 7 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 8 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 9 | Single pole |
| 10 | Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 11 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 12 | 4X4 sq.mm + 2X4 sq. mm earth wire |
| 13 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 14 | 3x4 sq.mm |
| 15 | Supplying and fixing suitable size G.I. box with modular plate and cover in front on surface or in recess including providing and fixing 25A modular socket outlet and 25A modular SP MCB \\"C\\" curve including connections, painting etc. as required. |
| 16 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
| 17 | Upto 35 sq. mm |
| 18 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 19 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 20 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 21 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 22 | Supplying and fixing of following sizes of heavy class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 23 | 25 mm |
| 24 | Supplying and installing following size of perforated Hot Dipped Galvanised with Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 25 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 26 | Supplying and installing following size of perforated Hot Dipped Galvanised with Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. |
| 27 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 28 | Providing and fixing of 25 mm PVC drain pipe exposed on wall with necessary clamps, and fittings etc. duly insulated with 19 mm thick closed cell elastometric nitrile rubber of minimum 45 Kg/cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer in Charge. |
| 29 | Supplying, Installation, Testing and Commissioning of Air Cooled Cassette type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), R-32/R410A/R-407 Green Refrigerant, wireless Remote, inbuilt drain pump, suitable for 400/230V, 50 Hz ,1 /3 phase AC supply, including surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 5.5 Mtr (IDU to ODU), copper power and control cable upto 5.5 Mtr (IDU to ODU) including drain pipe, the system shall be capable of performing cooling, dehumidification, Air circulation, filteration & ventilation offollowing capacity with Scroll/rotary compressor with min 5 year Original Equipment Manufacturer (OEM) warranty covering all parts of the air conditioning unit, as specified. The system shall be able to deliver 100% of the rated capacity as per relevant IS Code. The lab testingreports as per IS: 1391 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per International Electrotechnical Commission (IEC) 17025 standards/Central Power Research Institute (CPRI)/ Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification and as per IS: 1391 as required. |
| 30 | 1.5 TR with 3 Star BEE Rating Heating & Cooling |
| 31 | 2.0 TR with 3 Star BEE Rating Heating & Cooling |
| 32 | 4.0 TR with 5 Star BEE Rating |
| 33 | Supplying of one number PVC insulated and PVC sheathed / XLPE aluminium conductor armoured power cable of 1.1 KV grade of size 3.5C x 25 sqmm etc as required. |
| 34 | Supplying of one number PVC insulated and PVC sheathed / XLPE aluminium conductor armoured power cable of 1.1 KV grade of size 4C x 16 sqmm etc as required. Please Enable Macros to View BoQ information |