| Sl. No. | Item Description |
| 1 | SITC OF MAIN LT/CAPACITOR PANEL Design, manufacturing, testing at works, supply, delivery at site including supervision during installation of the following extensible cubicle type indoor mounting, dead front, fully compartmentalised with hinged lockable detachable front & back openable, dust and vermin proof, floor mounting sheet steel clad switchboard fabricated out of 2 mm thick CRCA powder coated sheet steel suitable for use at 415 volts 3 phase 4 wire 50 cycle system and to withstand a symmetrical fault level of 50 KA at 415 volts. Panels shall be fabricated in easily transportable sections, length, height, depth etc. to match with site condition. All incomer breaker and Bus Couplers shall be interlocked electrically as shown in SLD drawing no. EL/SLD/01.The following provisions shall be required to be made in the Main LT Panel as detailed below:The Switchboards shall have provision to accommodate all cables from the bottom /top as required.All live accessible parts shall be shrouded with 1mm thick polycarbonate/3 mm thick FRP sheet and all equipment shall be finger touch proof. The busbar insulation shall be with heat shrinkable sleeves according to the colour code. SMC shrouds and busbar supports shall be used. All MCCB door handle shall be interlocked and lockable in OFF position.Galvanised hardware with zinc passivation shall be used in fabrication of Switchboards. Suitable Aluminium earth bus to be provided throughout the length of Switchboards.All indication lamps / illuminated push buttons shall be LED type.All incomer meters of Main LT Panel shall be multifunction & should have all the electrical parameters like Ampere, KW, KVAR, KWH, PF, Frequency etc.Coil of all motor starters shall be fed from 440 V / 230 V Control Transformer. MIMIC diagram shall be for Main LT panel as per below: MIMIC shall be made of polycarbonate sheet of 5 mm thickness fixed on acylic sheet of 2mm thick.the size of panel shall be such that the diagram can be visualized from 5 to 6 meter distance. The panel shall display complete single line diagram of Main LT Panel. this line diagram shall be made from luminous non fading materials to glow in dark and each breaker legend shall be provided with bi-colour LED lights to show the ON/OFF status of the respective feeder (Incomers / Bus couplers) 1 Nos. 800 Amps, 50KA, 433 volt 4-P Electrically operated draw out ACB complete with micro processor based tripping mechanism, shunt release (24V DC), earth fault release and inbuilt O/C & SC releases (Microprocessor based) having variable range with time lag facility to acheive discrimination. Required Interlocking with other incomers & Bus Coupler to be provided as per Interlocking / operation scheme indicated in Drawing No.- EL/SLD/001. The ACB shall have suitable arrangement for termination by Al. Ar. XLPE Cables on incoming side for outgoing side termination by Bus Bar complete with following for each ACB: 1 Nos. 500 Amps, 50KA, 433 volt 4-P MCCB with micro processor based tripping mechanism, shunt release (24V DC), earth fault release and inbuilt O/C & SC releases (Microprocessor based) having variable range with time lag facility to acheive discrimination. Required Interlocking with other incomers & Bus Coupler to be provided as per Interlocking / operation scheme indicated in Drawing No.- EL/SLD/001. The ACB shall have suitable arrangement for termination by Al. Ar. XLPE Cables on incoming side for outgoing side termination by Bus Bar complete with following for each ACB: |
| 2 | DISTRIBUTION PANELS :- Design, manufacturing, testing at works, supply, delivery at site including supervision during installation of 2 mm thick MS sheet steel fabricated cubicle type Panel dust and vermin proof, fully compartmentalised complete with hinged and lockable doors . The Sheet Steel shall under go minimum eight tank treatment followed by finishing treatment of powder coating with 70 micron minimum thickness. All the panels shall be floor mounted and dead front construction complete with interconnections. Protection of Distribution Panel Shall be IP-42. Also refer SLD Drawing No. EL/SLD/02. All live accessible parts shall be shrouded with 1mm thick polycarbonate/3 mm thick FRP sheet and all equipment shall be finger touch proof. The busbar insulation shall be with heat shrinkable sleeves according to the colour code. SMC shrouds and busbar supports shall be used. All MCCB door handle shall be interlocked and lockable in OFF position.Digital Multifunction meter with RS-485 communication port for measurement of PF, V, A & Hz , equivalent to EM6459,with CT as required. (Bus Bars)Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 250 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.1 Nos. 63A TPN MCB 1 Nos. 100A TPN MCCB of 16 KA breaking capacity.of 10 KA breaking capacity. GROUND & FIRST FLOOR PANEL as described above .Electrolytic high conductivity aluminium three phase and neutral busbars rated at 1000 amps, 50 KA, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp. Neutral Bus Bar shall be 50% of Phase Bus Bar with providing Potential transformer for outgoing metering.All outgoing feeders shall be provided with RYB Phase Indication Lamp with MCB as backup protection & Dual Energy Meter with CT as required |
| 3 | SECOND FLOOR PANEL Incoming:1 Nos. of 160 Amp FP MCCB of 25 KA breaking capacity. Metering for incoming:Digital Multifunction meter with RS-485 communication port for measurement of PF, V, A & Hz , equivalent to EM6459,with CT as required.Phase indicating lamps RYB with 6 Amps SP MCB back up.ON/OFF/TRIP Indicating Lamp with 6 Amps SP MCB back up. Bus Bars: Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp. Outgoings 3 Nos. 63A TPN MCB of 10 KA breaking capacity. SPARES 1 Nos. 100A TPN MCCB of 16 KA breaking capacity. 3 Nos. 63A TPN MCB of 10 KA breaking capacity. |
| 4 | LIFT PANEL panel UPS INPUT PANELIncoming:1 Nos. of 100 Amp FP MCCB of 25 KA breaking capacity. Metering for incoming:Digital Multifunction meter with RS-485 communication port for measurement of PF, V, A & Hz , equivalent to EM6459,with CT as required.Phase indicating lamps RYB with 6 Amps SP MCB back up.ON/OFF/TRIP Indicating Lamp with 6 Amps SP MCB back up. Bus Bars:Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 125 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Outgoings 2 Nos. 63A TP, ELCB of 25 KA breaking capacity.2 Nos. 40A DP MCB of 10 KA breaking capacity.SPARES 1 Nos. 63A TP, ELCB of 25 KA breaking capacity.1 Nos. 40A DP MCB of 10 KA breaking capacity.LIFT PANEL as described above . |
| 5 | UPS INPUT PANEL .Incoming:1 Nos. of 160 Amp FP MCCB of 25 KA breaking capacity.Metering for incoming:Digital Multifunction meter with RS-485 communication port for measurement of PF, V, A & Hz , equivalent to EM6459,with CT as required.Phase indicating lamps RYB with 6 Amps SP MCB back up.ON/OFF/TRIP Indicating Lamp with 6 Amps SP MCB back up.Bus Bars:Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Outgoings01 Nos. 50 KVA, UPS (30 MINUTES BACKUP BATTERY BANK)01 Nos. 50 KVA, UPS (30 MINUTES BACKUP BATTERY BANK)UPS INPUT PANEL as described above . |
| 6 | UPS OUTPUT PANEL Incoming:1 Nos. of 100 Amp FP MCCB of 25 KA breaking capacity.1 Nos. of 32 Amp FP MCB of 10 KA breaking capacity.Metering for incoming:Digital Multifunction meter with RS-485 communication port for measurement of PF, V, A & Hz , equivalent to EM6459,with CT as required.Phase indicating lamps RYB with 6 Amps SP MCB back up,for all incomer ON/OFF/TRIP Indicating Lamp with 6 Amps SP MCB back up,for all incomer Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Electrolytic high conductivity Aluminium three phase and neutral busbars rated at 200 Amps, insulated with heat shrinkable coloured PVC sleeves & clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.Outgoings 4 Nos. 40A DP MCB of 10 KA breaking capacity.3 Nos. 16A DP MCB of 10 KA breaking capacity.SPARES 1 Nos. 16A DP MCB of 10 KA breaking capacity.UPS OUTPUT PANEL as described above |
| 7 | EXTERNAL LIGHTING Supplying & fixing of following accessories in the existing cubical panel board / feeder pillar including connection testing etc. as reqd.Supplying, fixing, connecting, testing and commissioning of Astronomical Timer along with power contactor 3 set of Double pole of 32 Amp. in the existing cubical panel board / feeder pillar (Timer shall be capable to operate 3 nos double pole Power contactor seprately to operate at different time schedule), complete in all respects. The above board shall be complete with 3 nos. phase indicating lights, flush mounted Ammeter, Voltmeter, CT's, PT's, selector switches, protective fuses etc. at Incomer with all interconnections by min. 2.5 sq.mm. Copper wires.Danger notice plateBUS BAR : 40 AMP, 500 Volts, 3 phase 50 HZ FP high conductivity electrolytic Aluminium bus bar. The current density of bus bar shall be minimum 1.00 sq mm / amp. OUT GOINGS : 15 nos. 6-32 AMP DP MCB (10 KA) OUT GOINGS : 15 nos. 6-32 AMP DP MCB (10 KA)OUT 3 Nos 40 AMP DP MCB (10KA) |
| 8 | ONLINE UPS & BATTERY BANK Supply, installation, testing and commissioning of 50 kVA UPS, 3 phase (415 V + 15%) Volts input & 3 phase output (440 V + 1%), 50 Hz, 100% IGBT inverter & converter, Input harmonic Current THD 3% typical at 100% load, 6% maximum at 50% load and 30 min battery backup for UPS along with battery cabinet complete in all respect including supporting steel structure for UPS and Battery as required. Quoted price shall be inclusive of approved rating single core copper conductor cable connecting UPS and batteries. (ALONG WITH BYPASS ARRANGEMENT) |
| 9 | Supply ,installation , testing and commissioning of 3 kVA Pure Sine Wave Inverter system for a constant secondary voltage of 220 volts at 50 Hz, single phase, batteries backup of minimum 90 Minutes back up duration including, batteries, battery chargers, rectifiers, transformers, controls, protection and instruments , trolley etc complete as required. (ALONG WITH BYPASS ARRANGEMENT) |
| 10 | SUPPLY OF HT / LT CABLES Supply,Receiving, laying, installation, testing and commissioning of following sizes of 11 KV (E) grade XLPE insulated, aluminium conductor, armoured power cables conforming to IS : 7098 (Part-I) laid in Existing Hume / DWC pipe in an approved manner complete as required and as per specifications including complete as required as per IS 1255 as required. (Necessary end sealing when cables laid in hume pipe shall be done by contractor) 3C X 240 sq. mm |
| 11 | Supply , Receiving, shifting, laying, testing and commissioning of following sizes of 1.1 KV grade XLPE insulated aluminium conductor armoured power cables conforming to IS : 7098 (Part-II) laid in existing cable tray in an approved manner complete as required and as per specifications and dressing of the cable in an approved manner complete as required as per IS1255 and as per drawing. 3.5 x 300 Sq.mm. |
| 12 | 3.5 x 95 Sq.mm. |
| 13 | 3.5 x 50 Sq.mm. |
| 14 | 4 x 25 Sq.mm. |
| 15 | COPPER CABLES (ARMOURED) SUBMAIN CABLE FROM PANEL TO DB 4 core 10 sq. mm. XLPE |
| 16 | 4 core 6 sq. mm. XLPE |
| 17 | 2 core 10 sq. mm. XLPE |
| 18 | 3 core 10 sq. mm. XLPE |
| 19 | 3 core 4 sq. mm. XLPE |
| 20 | Control Cables Supply Receiving, laying, testing and commissioning of following sizes of 1.1 KV PVC insulated, inner & outer PVC sheath extruded type ST-2, Copper conductor, armoured cables conforming to IS : 7098 (Part-II) and as per specification.(For HT Panel controls, Transformer Protection, PLC controls.) including cost of termation. 12 x 2.5 sq. mm. |
| 21 | 10 x 2.5 sq. mm. |
| 22 | 6 x 2.5 sq. mm. |
| 23 | 4 x 2.5 sq. mm. |
| 24 | 2 x 2.5 sq. mm. |
| 25 | 2 x 1.5 sq. mm. Cu. Shielded Cable |
| 26 | Supplying and making terminal joints for the following sizes of 11 KV (E) grade Aluminium conductor, XLPE, armoured, cable including terminal lugs, insulation tape, heat shrinkable kit complete as required. 3 C x 240 Sq. mm (Indoor/Outdoor Type). |
| 27 | Supply and making terminal joints for the following sizes of 1.1 KV XLPE insulated, Aluminium conductor armoured cable including providing terminal aluminium lugs, crimping the joints effecting terminal connections to the equipment complete as required double brass compression gland. 3.5 x 300 Sq.mm. |
| 28 | 3.5 x 95 Sq.mm. |
| 29 | 3.5 x 50 Sq.mm. |
| 30 | 4 x 25 Sq.mm. |
| 31 | COPPER CABLES (ARMOURED) SUBMAIN CABLE FROM PANEL TO DB 4 core 10 sq. mm. XLPE |
| 32 | 4 core 6 sq. mm. XLPE |
| 33 | 2 core 10 sq. mm. XLPE |
| 34 | 3 core 10 sq. mm. XLPE |
| 35 | 3 core 4 sq. mm. XLPE |
| 36 | Control Cable Termination Supply and making terminal joints for the following sizes of 1.1 KV PVC insulated Copper conductor cable including providing terminal copper lugs, crimping the joints effecting terminal connections to the equipment complete as required brass double compression gland. 12 x 2.5 sq. mm. |
| 37 | 10 x 2.5 sq. mm. |
| 38 | 6 x 2.5 sq. mm. |
| 39 | 4 x 2.5 sq. mm. |
| 40 | 2 x 2.5 sq. mm. |
| 41 | 2 x 1.5 sq. mm. Cu. Shielded Cable |
| 42 | EARTHING SYSTEM & CABLE TRAY Supply and installation of maintenance free Chemical Earthing using Electrode of size 23.2 mm dia, 03 meter long connected with 50X6 mm Copper internal strip complete with excavation, civil works, cast iron cover with back fill compound. The voltage between Neutral & Earth not to exceed 0 volts & IR value less than 1 ohm. The earth resistance shall be as per IS 3043 for Neutral earthing. |
| 43 | Supply and installation of maintenance free Chemical Earthing using Electrode of size 17.2 mm dia, 03 meter long connected with 25X5 mm Copper internal strip complete with excavation, civil works, cast iron cover with back fill compound. The voltage between Neutral & Earth not to exceed 0 volt & IR value less than 1 ohm. The earth resistance shall be as per IS 3043 for body earthing. |
| 44 | Supply and installation of maintenance free Chemical Earthing using Electrode of size 17.2 mm dia, 03 meter long connected with 50x6 mm GI internal strip complete with excavation civil works cast iron cover with back fill compound. The voltage between Neutral & Earth not to exceed 0 volts & IR value less than 1 ohm . The earth resistance shall be as per IS 3043 for earthing. |
| 45 | Supply and laying in position the following GI tape/wires including providing all fixing accessories and effecting proper connections including clamping to wall with suitable clamp / Saddle and fixing bolts / Soldering / rivetting in ground including the cost of digging & back filling as required & complete as required to comply with IS 3043. All joints shall be tinned. 25 x 5 mm GI tape |
| 46 | 50 x 6 mm GI tape |
| 47 | 50 x 6 mm CU tape |
| 48 | CABLE TRAY :- Supply and Fixing & installation of following sizes of MS Perporated type cable trays fabricated from 2 mm thick sheet steel with stove enamel paint of approved colour with necessary factory made bends, tees, reducer couplers, dashfastners,GI nuts bolts including cutting,bending, drilling, bolting etc.complete as per specifications and as approved by Project Manager, including providing required MS supports fabricated from steel flats, angles, bars, channels as required for fixing/hanging cable trays duly painted with one coat of primer and 2 coats of synthetic enamel paint of approved colour etc. complete as per specifications and as approved by Project Manager 900 mm wide, 100mm high perforated Type. |
| 49 | 400 mm wide, 100mm high Perforated Type. |
| 50 | 300 mm wide, 100mm high Perforated Type. |
| 51 | 150 mm wide, 100mm high Perforated Type. |
| 52 | SUBSTATION SAFETY EQUIPMENT :- Supply and fixing in position the approved \\"shock treatment charts\\" framed in teak wood frame and covered with glass in front as required in two languages (Hindi & English) |
| 53 | Supply & fixing of Mimic diagram for overall schematic of power distribution complete as required. |
| 54 | Supply and fixing in position the best quality \\"Danger Boards\\" of approved shape and size as specified by Local Electricity Authorities written in English and Local languages. 11 KV (250mm X 200mm) |
| 55 | 433V (150mm X 100mm) |
| 56 | Supply & Laying of non skid Electro mat 1 mtr wide and 3.0 mm thick 11 KV grade conforming to IS 15652 as required including cutting to required length complete as per requirement of local electricity authorities. |
| 57 | Supply of fire buckets 5 nos. 15 litre capacity duly filled with fine sand and fixed on an angle iron frame as per requirement of local authorities. The fire buckets shall be painted red from outside and white from inside, including lettered as FIRE with white colour with extra handle at bottom. |
| 58 | Supply & Laying of non skid Electro mat 1mtr wide and 2.0 mm thick 11 KV grade IS 15652 as required including cutting to required length complete as per requirement of local electricity authorities. |
| 59 | Supply of Rubber hand gloves 11 KV grade, as per IS 4770-1968. |
| 60 | Supply of standard first aid box as approved by Indian red cross society/ St.John Ambulance Brigade and conforming to IS 2217-1963. |
| 61 | Electrical Manhole Size- 600x600 mm as per standard drawings |
| 62 | Providing and laying of Double Walled Corrugated HDPE Pipe, conforming to IS:16098 SN4, having anti rodancy features complete with accessories including slip fit/push fit type couplers per 6 mtrs. of pipe length. (Excavation etc. will not be paid separately) |
| 63 | Design, manufacturing, testing at works, supply installation, testing and commissioning of 415 Volt DG Set of following rating for site conditions, complete with latest CPCB-IV complient Diesel Engine base frame, lube oil system, Radiator, required batteries, governor, instrumentation, day service fuel tank, exhaust silencers including Aluminium cladding, alarms, engine mounted control panel, utility piping, anti vibration pads, Alternator (Stamford / AVK SEGC) direct coupled to Engine along with static excitation system, AVR panel, inbuilt 990 Litre day oil tank and all required accessories complete as required and as per specifications.The scope of work does not include AMF panel, cabling and earthing. Cable Box to be provided for termination of required Al. Cable.The DG Set shall be provided with geneset controller as also mentioned above for AMF / Auto / Manual synchronising, Auto load sharing and having electrical and mechanical parameter monitoring, electrical protection (under and over frequency and voltage, over load (KW), over current, short circuit, reverse power, excitation failure, AMP sentry protection.1 No. 500 A FP, MCCB for 250 KVA DG Sets shall be installed in Control Panel for isolation purpose. The control panel shall be provision for incoming and outgoing cable connection.Design, manufacture, testing at works, supply installation,testing and commissioning of Acoustic Enclosure as per CPCB-IV, norms for the DG Set mentioned in the Item above including required ventilation system complete as required and as per specification. 250 KVA |
| 64 | EXHAUST SYSTEM :- Supply, laying and fixing of following sizes of MS B Class piping( Tatas, Jindal (Hissar), IST) with bends etc. for Exhaust of DG Sets including providing suitable self supporting arrangement etc. and supplying & fixing 75 mm thick mineral wool insulation of 150 Kg per cubic meter density on all sides of Exhaust pipe and silencer with chicken mesh wrapping and aluminium cladding with aluminium sheet of 26 SWG,suitable for outdoor installation complete as required and as per specification. (Refer Layout enclosed) The DG Exhaust shall be taken along the building supported from the wall however scope includes building required structure for crossing the ramp. 125 MM (NB) MS ERW pipe 4.85 mm thick.Note :- 1. The rates in 2.0 shall include guide support, expansion joints & wherever required.2. For Exhaust pipe size shall be as per back pressure calculation provided by DG Set vendor. |
| 65 | Supply & Fixing of miscellaneous Structural Support for horizontal/vertical exhaust Pipes. The Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. The contractor shall submit the structure strength calculation for approval before execution. |
| 66 | Supply 4 MP IP DOME UP TO 30 MTR CAMERA :- 1/2.8” Progressive Scan CMOSUp to 2 megapixel resolution ,Full HD1080p real-time video ,120dB Wide Dynamic Range 3D DNR ,EXIR high performance LEDs Up to 30/50 meters IR range 12V DC±25% & PoE(802.3af Class3) Support H.264+ IP67 CP PLUS/ HONEYWELL/ HIKVISION |
| 67 | SUPPLY OF 4 MP IP BULLET 30 MTR CAMERA :- 1/2.8” Progressive Scan CMOS Up to 2 megapixel resolution ,Full HD1080p real-time video ,120dB Wide Dynamic Range3D DNR ,EXIR high performance LEDs Up to 30/50 meters IR range 12V DC±25% & PoE(802.3af Class3) Support H.264+ IP67 (CP PLUS / HONEYWELL/ HIKSISION |
| 68 | Supply ,Installation, Testing , Commissioning, Integeration of 32-Channel 4K NVRs:- Third-party network cameras supported Up to 5 Megapixels resolution recording With 2 SATA Port up to 12 TB Supported Support 1-ch HDMI, 1-ch VGA, HMDI at up to 4K(3840x2160) resolution 4-ch network cameras can be connected with 40M/60M/80M incoming bandwidth Support dual-os to ensure high reliablility of system running Support various VCA detection alarm and VCA search Support H.265/H.264/MPEG4 video formats ( CP PLUS / HONEYWELL/ HIKSISION ) |
| 69 | Supply ,Installation, Testing , Commissioning, Integeration of SURVILLANCE HDD 4 TB ( WD / SEAGATE ) |
| 70 | Supply ,Installation, Testing , Commissioning, Integeration of 8 ports Giga uplink Port POE Switch 10/100/1000 MBPS (GIGABYTE) ( CP PLUS / HONEYWELL/ HIKSISION ) |
| 71 | Supply ,Installation, Testing , Commissioning, Integeration of 4 ports Giga uplink Port POE Switch 10/100/1000 MBPS (GIGABYTE) ( CP PLUS / HONEYWELL/ HIKSISION ) |
| 72 | P& F of RJ-45 Connectors ( D- Link Or equivalent) |
| 73 | Supplying & Laying of CAT 6 Cable should be unshielded twisted pair cabling system, TIA / EIA 568-C.2 Category 6 Cabling system.Network support should be ultra high speed data networks such as Gigabit Ethernet (1000 Base-T and 1000 Base-TX) and beyond.Cable should be ETL Verified, UL Listed and UL channel verified- all three certificates are mandatory. Conductors type should be 23 AWG solid bare copper.Frequency tested should be up to 600 MHz minimum.Impedance should be 100 ± 15 Ohms.Propagation delay should be 535ns/100m @250MHz.cable should be RoHS compliant.The LAN Structured cabling should be of CAT 6 U/FTP. All user nodes should be on 1G networks with 20 years warranty certificate. ( D- Link Or equivalent) |
| 74 | Supplying, Installation,Testing & Commissioning of 42 \\" LED Full HD TV Resolution 1920 x 1080 ,Contrast Ratio (Typical) 5000:1,Built-in Speaker (10W + 10W), Magic Clone (to USB), Auto Source Switching & Recovery, Lamp Error Detection, Super Clear Coating, Temperature Sensor, Plug and Play (DDC2B), Pivot Display, Clock Battery, PIP/PBP, Video Wall (10x10), Image Rotation, Button Lock, HDCP Support, Smart Scheduling, Smart F/W update, Built-In MagicInfo Premium-Swith Mounting Brackets as per Technical Specification complete in all respect. (LG/ SAMSUNG ) |
| 75 | Supply, installation, testing and commissioning of online 2 KVA UPS with 30 minutes back-up with inbuilt battery complete etc as required.( APC/ MICTOTEK /VGUARD ) |
| 76 | Supply, Installation, Testing & Commissioning of Fiber Cable (4 core, armoured, single mode)( D-LINK/ OR EQUIVALENT ) |
| 77 | Supplying and commissioning of 12 U rack with 1 no extra tray , Power Distribution Unit of 05Amps of 05 nos.Socket in a Single Pole / Screw,Mountable,etc as required.( WQ/VALRACK/D LINK) |
| 78 | Fire Alarm Control Panel:- The scope includes the supply, installation, testing, and commissioning of an approved make, microprocessor-based, multi-loop, networkable fire alarm control panel with a distributed loop architecture, supporting up to 1100 addressable points and expandable from 1 to 6 loops. Each loop shall accommodate a minimum of 125 detectors and 125 other devices (excluding 10% spare), with the capability to support all 1110 points as sensors. The panel shall feature a minimum 160-character LCD display, a 1000-event history log, and support peer-to-peer networking for up to 17 nodes with a total capacity of 18,870 addressable points. It shall include a 240V AC power supply, automatic battery charger, and 24V sealed lead-acid batteries rated for 24 hours of normal operation and 30 minutes in alarm mode, with a charging capacity of 55AH. The system must provide multiple outputs with a minimum 6 Amp current for third-party integration, at least 6 NAC circuits for notification/AUX outputs, and include all necessary licensed software and hardware for programming. The panel shall comply with UL 864 (10th Edition), UL 2572 (2nd Edition), and be FM Approved. |
| 79 | Field Devices :- Supplying, installing, testing and commissioning of fire alarm, public address and two way communication system field devices, control station, repeater panel, power supply, amplifier, cable, conduit etc. as below complete with junction box, connecting hardware accessory, cable tray, Fire survival cable, MS conduit, flexible conduits and other accessory to make fire alarm system operational as and when required. Supplying, installing, testing and commissioning approved make Addressable Multi-criteria Photo-Thermal Above False Ceiling Detector with sensitivity range of 0.5 to 4.0% obs/ft.The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. The detector sensitivity (day & night) shall be controlled from the panel to get accustomed to the local environment.The detector shall comply UL268 & UL521 , 7th Edition guidelines |
| 80 | Supplying, installing, testing and commissioning approved make Addressable Rate of Rise Heat Detector rated at 8.3 deg C/min. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Detector shall comply UL521 guideline. |
| 81 | Supplying, installing, testing and commissioning approved make Addressable Pull Type Station (Single Action). The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. The device shall comply UL approval. |
| 82 | UL listed Strobe with flash shall be supplied with 2 flash per second (2Hz) and shall not be less than 1flash per second, maximum pulse 0.2 second of maximum duty of 40%, flash light shall be clear nominal white 110cd, 95cd, 75cd and 15cd the device shall sit directly on addressable SLC (loop signalling circuit) of FACP (Fire alarm control panel) and powered through UL listed external 230vac input 24vdc output power supply supervised powered by FACP, candela shall not be mounted less than 80in (2.3m) and not greater than 96in (2.44m) from finishing floor, operating temperature range from 0°C to 45°C and a humidity tolerance of up to 93% RH, Non-Condensing with mounting backbox of 100x75x75x6mm with customizable of size as per site condition |
| 83 | Supplying, installing, testing and commissioning approved make Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. |
| 84 | UL listed 230VAC input 24VDC 5A output rated power supply for hooters and strobe not more than 10 devices as class B circuit supervised from main control panel. |
| 85 | Supplying, installing, testing and commissioning approved make Addressable Control Module for Sounders / Strobes / Sounder cum Strobes. The control module shall provide supervised NAC output rated at 24v DC, 2A. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. |
| 86 | Supply, installation, testing & commissioning of Addressable fire phone jack with plates complete with MS junction boxes as specified, Getty/fastener, GI screws as required to complete the job with mounting backbox of 100x75x75x6mm with customizable of size as per site condition |
| 87 | Supply, installation, testing & commissioning of Portable UL listed fire phone handsets with suitable enclosure and mounting accessories. |
| 88 | Public Address System: Supply, installation, testing & commissioning of 125/250/500W Class-D digital power amplifier with inbuilt fan for temperature control, line matching transformer 100V, 70V distortion typically < 0.01% @ 1 KHz, support for 2 Channel (125x4/250x4/500x2), amplifier with 100V, 70V, 4 Ohm & 8 Ohm output with selectors Dante network control with Suitable Matrix remote, pre-amplifier inbuilt DSP network interface primary & secondary Dante Network DSP - EQ, gain control, crossover, delay, limiter, high-pass filter & low-cut filter. Frequency Response - 40Hz-20KHz, Input Impedance - 10KΩ, THD - <0.1% @ 1KHz/-3dBv, S/N Ratio - > 80dB, Crosstalk - > 60dB, 1KHz, Max output. |
| 89 | Supply, installation, testing & commissioning of 6 watt ceiling mounted speakers with minimum of 5\\" speaker drive, complete ABS enclosure and metal grille in white, line matching transformer 100/70V line, three tap changing of 6 / 3 /1.5 W speaker shall be tap @ 3W changers including end terminators, with effective frequency range 100-15kHz, delivering SPL@1m/1W= minimum of 85dB, Complete with necessary mounting hardware, accessories, screws etc. for fixing on ceiling. |
| 90 | Cable & Conduit : Supply, Installation, Testing and commissioning of 600/1000V rated, stranded copper conductor armoured, Fire survival, 2C x 1.5 Sq.mm cable in compliance to BS 7846 latest edition for the requirement of construction & performance and as per detailed specification provided. The cable shall be class 2 annealed Cu conductor having mineral ceramic glass fibre barrier tape of 2 layer over conductor, covered by an extruded layer of cross linked LSZH insulation as per IE-5 of BS EN 50363 along with 1 layer of glass mica tape, AL tape screening and LSZH outer sheath as per BS 7629-1 and BS 5839-1 conductor should comply EN 60228 and Should retain circuit integrity as per BS 6387, 8434-2. cable should be LPCB and RTRC and NABL approved Cable shall be supplied with fixing accessories including glands/single compression glands end terminations, saddles, clamps with screws, cable tie etc. for fixing on wall/ceiling or on cable trays complete as required. Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail