| 1 | Wiring for lighting points/fan points/ exhaust fan points/call bell points with 1.5 sq mm FRLS PVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit, with 240V 6A modular switch , modular plate and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable, etc. as required. (Havells/ Polycab/ Anchor/ Finolex/KEI/RR or equivalent make ) incl. cost of conduit. SAmple to be approved by EIC. |
| 2 | Wiring for light/power plug points (15/16A heating points) with 2x4 sq mm FRLS PVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit along with 1x4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing, etc. as required. (Maximum two points shall be connected on one circuit).(Havells/ Polycab/ Anchor/ Finolex/KEI/RR or equivalent ) incl. cost of conduit |
| 3 | Supplying and fixing of suitable size GI box with modular plate and modular cover in front on surface or in recess, including providing and fixing of 6 pin 15/16 A modular socket outlet and 15/16A modular switch, connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or equivalent) SAmple to be approved by EIC. |
| 4 | Supplying and fixing of suitable size GI box with modular plate and modular cover in front on surface or in recess, including providing and fixing of 2 no. 3 pin 5/6 A modular socket outlet and 2 no. 5/6A modular switch, connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or eq.) SAmple to be approved by EIC. |
| 5 | Supplying and fixing of modular sockets/ indicators/switches on existing modular plate and switch box , incl. connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or equivalent) |
| 6 | i.3 pin 5A - 10A socket. |
| 7 | ii. indicator. |
| 8 | Point wiring for 5A -10A socket out lets (computer points) with 2x2.5 sq mm (P+N)FRLS PVC insulated 660/1100volt grade flexible stranded copper conductor wires in recessed or surface conduiting system and earthing the point with 1 x 2.5 sq. mm single core copper wire (loop earthing),(Maximum two points shall be connected on one circuit).(Havells/ Polycab/ Anchor/Finolex/KEI/RR or equivalent) incl. cost of conduit |
| 9 | Supply, installation, testing and commissioning of 12 - 15 Watt LED recessed/ mounted (round or square) Down lighters having aluminum body, minimum 100lm/w, average life 50000 hours, LM79 & LM80 test report should be from Govt. Approved NABL lab / Govt. Of India , Operating temperature -10`C to +45`C. The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date ofsuccessful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/ Jaguar/Wipro). Commercial series. |
| 10 | Supply, installation, testing and commissioning of 3 star 1200 mm sweep ceiling fans of Havells / Crompton Greaves/Bajaj/ Usha (Sample to be got approved), incl. cost of extension of GI rod (if required) and making ofnecessary connections. |
| 11 | Supply and fixing of two module stepped electronic fan regulator on the existing modular plate switch box, incl. connections but excluding modularplate etc. as reqd. |
| 12 | Supply, installation, testing and commissioning of 200-250 mm sweep shutter type exhaust fans, incl. cost of ceiling rose and making of space in walls/windows as per site and necessary connections. (Havells/ Philips/ Crompton). |
| 13 | Supply, installation, testing and commissioning of 100Watt LED Flood lighting luminaries having aluminum body, minimum 100lm/w, the luminary housing should be aluminum and the luminary optics shall have a high efficiency with transmittance, average life 50000 hours, Operating temperature -10`C to +45`C. LM79 & LM80 test report should be from Govt. Approved NABL lab / Govt. Of India. The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/ Jaguar/Wipro). SAmple to be approved by EIC. |
| 14 | Supplying and fixing of modular blanking plates on existing modular plate and switch box ,excluding modular plate as required. |
| 15 | Wiring for sub mains along with earth wire in FRLS PVC insulated 660/1100 volt grade flexible stranded copper conductor wires in recessed or surface conduiting system, incl. cost of conduits(Havells/ Polycab/ Finolex/ Anchor/KEI/RR or equivalent). |
| 16 | 2 x 2.5 sq.mm + 1x 2.5 sq. mm earth wire |
| 17 | 2 x 4 sq.mm + 1x 4 sq. mm earth wire |
| 18 | 2 x 10 sq.mm + 1x 6 sq. mm earth wire |
| 19 | Supply and fixing of 16 way Double door surface/ recess mounting , Vertical/ Horizontal type, 240 V, SP&N MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs, excluding cost of MCBsand Incomer. . |
| 20 | Supply, installation, testing and commissioning of 5-32A single pole rating 240/415V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T suitable for inductive load in the MCB distribution board complete with necessaryconnections. |
| 21 | Supply, installation, testing and commissioning of 32 A DP rating 240V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T suitable for inductive load in the MCBdistribution board complete with necessary connections. |
| 22 | Supply, installation, testing and commissioning of 63 A DP rating 240V, 10 KA “C” curve MCB of Legrand/ Havells/ L&T suitable for inductive load in the MCB distribution board complete with necessary connections. |
| 23 | Supply, installation, testing and commissioning of wall/floor mounted compartmentalized , main distribution panels, fabricated out of 16 gauge sheet steel, dust protected, painted, incl. earth terminal with all necessary accessories with internal wiring as required. The panel is to be provided with the following adjustable type controlling/ protection switch gear devices:1.NORMAL INCOMING125A DP MCB 10KA 01 no.200A SP&N bus bar AL. Strips 01 set Digital meter and phase indicators 01 set.2. Generator INCOMER63A change over switch 01 no. 100A SP&N bus bar AL. Strips 01 setDigital meter and phase indicators 01 set.3.INVERTER/ SOLAR INCOMER40A DP MCB 10KA 01 no.100A SP&N bus bar AL. Strips 01 set Digital meter and phase indicators 01 set. OUTGOING63A DP MCB 10KA 02 no.40A DP MCB 10KA 02 noThe contractor has to submit the test certificate of main switch gear. |
| 24 | Providing of chemical earthing as per IS standards by way of digging 8 feet pit then embedding 3 mtr. Long GI earthing electrode, 80 mm dia. Connecting the plate with main control board by 10 SWG Copper wire with 1/2” dia. Full thread brass nut and bolts and washers, refilling the pit with chemicalcompound. |
| 25 | Supply, installation, testing and commissioning of 1625VA Power Inverter (Pure Sine Wave type) having generator compatible & provided and fitted with 2 no. 12V, 200 Ah, tall tubular batteries of Exide make and PVC trolley for resting/ housing of batteries. The job also includes terminal connections of batteries, input/ output leads of required size and length, carriage andapplicable taxes. |
| 26 | Supply, laying, connecting and commissioning of 50 sq. mm 2 core PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade Aluminum LTcable , incl. cost of required al. thimbles duly crimped. (Over head). |
| 27 | Supply and fixing of fan deep made of heavy gauge sheet in RCC slabs. |
| 28 | Supply and fixing of 4”/ 5” deep Junction boxes in RCC slabs. Please Enable Macros to View BoQ information |