| 1 | Disconnection of existing APFC Panel of any capacity/rating, from all incoming and outgoing electrical connections, checking serviceability of each components viz. capacitors, contactors, relays, MCB's, MCCB's, indicator lights, display meters, PF controller etc., replacement of burnt out internal wirings with suitable size FRLSH PVC insulated multistranded copper conductor wires,replacement of defective lugs,thimbles etc.,replacement of defective parts,through cleaning of panel both internally and externally, re interconnection of parts including reconnection of all incoming and outgoing electrical connections after repairs, testing and commissioning, complete all as specified and as directed. Notes:- (i) The work shall be carried out through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by the Engineer in Charge. (ii) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after. |
| 2 | Supply Only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In,operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours,rating 5 kVAr, 440 V, complete all as specified and as directed. |
| 3 | Supply Only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In,operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours,rating 7.5 kVAr, 440 V, complete all as specified and as directed. |
| 4 | Supply Only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In,operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours,rating 10 kVAr, 440 V, complete all as specified and as directed. |
| 5 | Supply Only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In,operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours,rating 12.5 kVAr, 440 V, complete all as specified and as directed. |
| 6 | Supply Only power factor correction capacitors, box type, heavy duty, with over current withstand capability 1.8 x In,operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours,rating 15 kVAr, 440 V, complete all as specified and as directed. |
| 7 | Supply Only power factor correction capacitors,box type, heavy duty, with over current withstand capability 1.8 x In,operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours,rating 20 kVAr, 440 V, complete all as specified and as directed. |
| 8 | Supply Only power factor correction capacitors,box type, heavy duty, with over current withstand capability 1.8 x In,operating losses 0.35 W/kVAr, peak inrush current withstand capability 300 x In, maximum ambient temperature 55º C, minimum operating life 150000 hours,rating 25 kVAr, 440 V, complete all as specified and as directed. |
| 9 | Supply Only capacitor duty contactors, type MO C5, built in auxillary contacts 1NO, rating 5 kVAr, 440 V, 3 phase, 50 Hz , complete all as specified and as directed. |
| 10 | Supply Only capacitor duty contactors, type MO C8.5, built in auxillary contacts 1NO, rating 8.5 kVAr, 440 V, 3 phase, 50 Hz , complete all as specified and as directed. |
| 11 | Supply Only capacitor duty contactors, type MO C10, built in auxillary contacts 1NO, rating 10 kVAr, 440 V, 3 phase, 50 Hz , complete all as specified and as directed. |
| 12 | Supply Only capacitor duty contactors, type MO C12.5, built in auxillary contacts 1NO, rating 12.5 kVAr, 440 V, 3 phase, 50 Hz , complete all as specified and as directed. |
| 13 | Supply Only capacitor duty contactors, type MO C15, built in auxillary contacts 1NO, rating 15 kVAr, 440 V, 3 phase, 50 Hz , complete all as specified and as directed. |
| 14 | Supply Only capacitor duty contactors, type MO C20, built in auxillary contacts 1NO, rating 20 kVAr, 440 V, 3 phase, 50 Hz , complete all as specified and as directed. |
| 15 | Supply Only capacitor duty contactors, type MO C25, built in auxillary contacts 1NO, rating 25 kVAr, 440 V, 3 phase, 50 Hz , complete all as specified and as directed. |
| 16 | Supply Only LED Indicator 16 mm with power consumption < 0.6W, LVGP & surge protection, 64/110 Volts AC/DC / 240 Volts AC, colour Red/Green/ Yellow/Blue , complete all as specified and as directed. |
| 17 | Supply Only APFC controller for contactor switching with 1 CT input 1/ 5 Amp, 415 V, 8 steps (For Contactor Switching) , complete all as specified and as directed. |
| 18 | Supply Only 3 Phase LED Voltmeter, Accuracy Class 1.0, Input voltage measurement range 50-550 VAC (P-P), Aux supply 80-300 VAC, CT secondary site selectable 1A / 5A, flush mounting 96 x 96 mm, with inbuilt selector switch , complete all as specified and as directed. |
| 19 | Supply Only 3 Phase LED Ammeter, Accuracy Class 1.0, Aux supply 80-300 VAC, CT secondary site selectable 1A / 5A, flush mounting 96 x 96 mm, with inbuilt selector switch , complete all as specified and as directed. |
| 20 | Supply Only miniature circuit breaker (MCBs) three pole and neutral, 240 Volts, 10KA, 40 to 63 Amps, complete all as specified and as directed. |
| 21 | Disconnection of existing Air Circuit Breakers (ACBs), 3 Pole/4 Pole,manually/electrically operated, fixed/draw-out type, AC 440 Volts,breaking capacity 50-100 kA, rated current 800-2000 Amps, form all incoming and outgoing electrical connections,checking serviceability of each components viz. ON/OFF button,CTs, tripping coil, shunt trip device,auxillary switches,locking arrangement,safety shutter,arc shield etc., replacement of defective lugs,thimbles etc.,replacement of defective parts, through cleaning of ACB both internally and externally, reassembling of parts including reconnection of all incoming and outgoing electrical connections after repairs, testing and commissioning,complete all as specified and as directed. OEM :- L&T, ABB, C&S and Schneider. Notes:- (i) The work shall be carried out through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by the Engineer in Charge. (ii) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after. |
| 22 | Supply Only CT of capacity 400-800 Amps Fix and Draw-out type ACB complete all as per OEM's specifications and as directed. |
| 23 | Supply Only Locable Trip Push Button (LTPB), complete all as per OEM's specifications and as directed. |
| 24 | Supply Only Locable Trip Push Button Kit (3IC & 2 BC), complete all as per OEM's specifications and as directed. |
| 25 | Supply Only Locking of ACB in Isolated Position (LIP) type C,complete all as per OEM's specifications and as directed. |
| 26 | Supply Only Locking of ACB in any Position (LAP) type C,complete all as per OEM's specifications and as directed. |
| 27 | Supply Only Racking interlock type CC, complete all as per OEM's specifications and as directed. |
| 28 | Supply Only Racking Padlock Assembly, complete all as per OEM's specifications and as directed. |
| 29 | Supply Only Door Interlock, complete all as per OEM's specifications and as directed. |
| 30 | Supply Only Mechanical operation counter, complete all as per OEM's specifications and as directed. |
| 31 | Supply Only Mounting Kit for Front mounted counter, complete all as per OEM's specifications and as directed. |
| 32 | Supply Only Shunt release, complete all as per OEM's specifications and as directed. |
| 33 | Supply Only under voltage release, complete all as per OEM's specifications and as directed. |
| 34 | Supply Only Earth fault Release, complete all as per OEM's specifications and as directed. |
| 35 | Supply Only vertical terminal adaptors for draw out ACB, complete all as per OEM's specifications and as directed. |
| 36 | Supply Only electronic timer adjustable type from 3 to 30 sec, complete all as per OEM's specifications and as directed. |
| 37 | Supply Only spring charging motor 110V/220VV AC/DC,Power rating 100-200watt speed 1400RPM for ACB , complete all as per OEM's specifications and as directed. |
| 38 | Disconnecting incoming and outgoing connections of existing LT Feeder Pillar Box, AC 415 V, 50 Hz, 3 Phase,checking serviceability of each components viz. MCB's, MCCB's, indicator lights, display meters, etc.,replacement of burnt out internal wirings with suitable size FRLSH PVC insulated multistranded copper conductor wires,replacement of defective lugs,thimbles etc., replacement of non hygroscopic fibres and brass screws for mounting of busbars,repairs/replacement of damaged frame, canopy, compartments,shutters,back covers,legs etc., repairs/ easining the locking arrangements along with door hinges, through cleaning of feeder pillar box both internally and externally, providing PCC (1:2:4) Type B1 foundation block in legs of feeder pillar box after demolition of existing damaged PCC foundation block, painting old painted steel surfaces both internally and externally by applying two coats of synthetic enamel paint (ordinary tint) by spray painting process after preparation of surface, re-interconnection of parts,including reconnection of all incoming and outgoing electrical connections after repairs,testing and commissioning, complete all as specified and as directed. Notes:- (i) Structural steel required for replacement of defective members of the structure/cubicle will be measured and paid seperately under relevant items here in after in this BOQ. (ii) New steel surfaces shall be applied a coat of red oxide primer. and two coats of paint of existing shade. |
| 39 | Supply Only 500 mm long LT power cable with stranded copper conductor, 50 Sqmm, single core, XLPE insulated,PVC innersheathed,unarmoured, extruded PVC Type ST2 outer sheathed,1100 V Grade conforming to IS 7098 (Part 1) 1988,both ends fixed with suitable size copper lugs with and including copper nut,bolt and washers, as in cable connectors, complete all as specified and as directed. |
| 40 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, Three pole 400 Amp 50 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 41 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, Four pole 400 Amp 50 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 42 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, Three pole 250 Amp 50 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 43 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, Four pole 250 Amp 50 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 44 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, three pole 200 Amp 50 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 45 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, four pole 200 Amp 50 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 46 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, four pole 160 Amp 36 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 47 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, four pole 125 Amp 25 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 48 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, three pole 125 Amp 25 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 49 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, four pole 100 Amp 25 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 50 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, three pole 100 Amp 25 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 51 | Supply fix in repair's MCCB confirming to IEC 60947-2, AC 415 Volt, four pole 63 Amp 16 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln, complete all as specified and as directed. |
| 52 | Supply and fix in repair's On Load Change Over Switch in sheet steel enclosure, Four Pole, Current Rating 400 Amps, conforming to IS 13947 (Part 3)-1993; IEC: 60947-3, complete all as specified and as directed. |
| 53 | Supply and fix in repair's switch disconnector fuse unit complete with HRC fuse of capacity 250 Amp, 415 Volt, 3 pole, 50 Hz in open execution type with fuse, complete all as specified and as directed. |
| 54 | S&F in repair's switch disconnector fuse unit complete with HRC fuse of capacity 200 Amp, 415 Volt, 3pole and neutral , 50 Hz in open execution type with fuse, complete all as specified and as directed. |
| 55 | S&F in repair's switch disconnector fuse unit complete with HRC fuse of capacity 125 Amp, 415 Volt, 3 pole and neutral , 50 Hz in open execution type with fuse, complete all as specified and as directed. |
| 56 | Supply and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m, complete all as specified and as directed. |
| 57 | Supply and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m, complete all as specified and as directed. |
| 58 | Supply and laying synthetic Rubber insulated mats 3.0 mm thick for voltage upto 33 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m, complete all as specified and as directed. |
| 59 | S&F Mild Steel Chequered Plates confirming to Gde Fe 410 - O or Fe 310 - O (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment, square cut to required size for Cable Duct Cover, complete all as specified and as directed. |
| 60 | S&F Structural steel work of angle, confirming to Gde Fe 410 - O or Fe 310 - O fixed independently as in fencing, brackets, for duct etc., complete all as specified and as directed. |
| 61 | Disconnection of existing AMF Panel of DG Sets of any capacity/rating (63-750KVA), from all incoming and outgoing electrical connections,checking serviceability of each components viz. capacitors, contactors,relays,timers, MCB's, MCCB's, indicator lights,display meters,controller etc.,replacement of burnt out internal wirings with with suitable size FRLSH PVC insulated multistranded copper conductor wires,replacement of defective lugs,thimbles etc.,replacement of defective parts,through cleaning of panel both internally and externally, re interconnection of parts including reconnection of all incoming and outgoing electrical connections after repairs,testing and commissioning,complete all as specified and as directed. Notes:- (i) The work shall be carried out through Authorised Original Equipment Manufacturer's Service Centre Engineers or through OEM Certified Agencies as approved by the Engineer in Charge. (ii) Spare Parts for replacement will be measured and paid seperately under respective items of this BOQ here in after. |
| 62 | Supply Only 4 pole power contactors conforming to IS / IEC 60947-4-1 & IEC 60947-4-1, Type MCX 32, AC-1 rating 160 Amps, complete all as specified and as directed. |
| 63 | Supply Only 4 pole power contactors conforming to IS / IEC 60947-4-1 & IEC 60947-4-1, Type MCX 33, AC-1 rating 200Amps, complete all as specified and as directed. |
| 64 | Supply Only 4 pole power contactors conforming to IS / IEC 60947-4-1 & IEC 60947-4-1, Type MCX 34 , AC-1 rating 255 Amps, complete all as specified and as directed. |
| 65 | Supply Only 4 pole power contactors conforming to IS / IEC 60947-4-1 & IEC 60947-4-1, Type MCX 43, AC-1 rating 400 Amps, complete all as specified and as directed. |
| 66 | Supply and connect lead acid batteries of 12 Volts, 180 AH, 25 plates including acesories like terminal clamps, copper cable of required sioze and length, petroleum jelly and baterry initial charging, complete all as specified and as directed. Make Exide/Amron. |
| 67 | Supply and connect lead acid batteries of 12 Volts, 150 AH, 25 plates including acesories like terminal clamps, copper cable of required sioze and length, petroleum jelly and baterry initial charging , complete all as specified and as directed. |
| 68 | S&F in repair's AMF Panel Battery charger of capacity 10 A, 12 Volt DC, as per existing make, Complete all as specified and as directed. |
| 69 | S&F in repair's AMF Panel Battery charger of cap 10 A, 24 Volt DC, as per existing make, Complete all as specified and as directed. |
| 70 | Supply and laying PVC insulated and FR PVC sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, conforming to IS 694 electric control cable with copper conductor, 1100 volts grade, cross sectional area 2.50 sqmm 8 core including taking down old U/S cable, complete all as specified and as directed. |
| 71 | Materials and Labour for pasting on existing display boards, letters or figures (Block,Roman, Italic or Indian) exc. 5 cm but n exc.10 cm high and symbols (stops,commas,short lines,dashes,hyphens, brackets, etc.) made out of high intensity grade retroreflective encapsulated lens type vinyle sheet, complete all as specified and as directed. |
| 72 | Site Clearance in soft/loose soil,complete all as specified and as directed. |
| 73 | S&F Air Circuit Breaker MDO (Mechanically Drop Out) type, 800A, 4P, 50kA breaking capacity Icu=Ics=Icw(1s)=50 kA with electronic protection unit, Ir=0.4 to 1 In, Isd= 1.5 to 10 lr, li= 2 to 15 In and shall be install on the existing panel board by extending the existing size bus bar and modification of existing panel (if reqd), reconnection & testing, checking etc. complete all as specified and as directed. |
| 74 | Supply, Installation, testing & Commissioning of Automatic Main Failure control unit with AMF Panel outdoor type suitable for 82.5 KVA DG Set fabricated with 3.15 mm thick CRCA sheet factory made floor mounted, dust and vermin proof in sheet steel construction, the panel should have doors at front and rear side for easy asessibility with suitable rated bus bar internal wiring and with provision for connecting incomming/outgoing leads with the folowing accessories :-a) Microprocessor based control unit with Control cabling from AMF Panel to diesel engine and elsewhere if required, all complete and inter locking, connecting the existing power cables.b) Relays, Timers, set of CTs for metering and protection.c) Energy analyzer to indicate currents, phase and line voltages, frequency, Power factor, KWH, KVARH,KVAH.d) Provision for Overload, short circuit, earth fault, under frequency.e) 3 pole power contactors conforming to IS / IEC 60947-4-1 & IEC 60947-4-1, Type MNX 110, AC-3 rating 110 Amps and AC-1 rating 160 Amps- 2No.f) MCCB confirming to IEC 60947-2, AC 415 Volt, four pole 125 Amp 25 KA with adjustable overload setting: 0.8 -1.0 x in and adjustable short circuit setting: 6-10 x ln - 02 No.g) Two set of indicator lamps 6 Nos LED Type for main and DG indication h) Master switch for auto/manual/test/offj)One set of lamps for indicating \\"load on set\\" \\"load on mains\\"set fails to start\\" low oil pressure\\" high cylinder tamp\\" \\" battery low\\"k) Alarm/Hooter Continue to 74.10... |
| 75 | Item No 74 Continued….l) Bettery charger connected to main supply side to charge bty comprising the following :-m) Charge rate selection for tricle or high chargen) Indicator lamp for betteryq) Set for easily accessible control fuseso) Set for relays to auto-start the engine on main failure and low voltage.p) Emergency trip |
| 76 | M&L for Earthing complete with GI earth plate electrode of size 600x600x6 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to GI earth strip of size 32 x 6 mm earth lead by means of nuts, bolts, check nuts, washers of galvanised iron as steel, protected by galvanized iron pipe 40mm bore (Medium grade) all as directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42 x 42 x10cm thick reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion, complete all as specified and as directed after taking down old unserviceabile earthing.Note: GI strip upto 7.5m including testing consider in this item. |
| 77 | Excavation in trenches not. exc. 1.5m wide and not exc. 1.5 deep and getting out in soft/loose soil, complete all as specified and as directed. |
| 78 | Removing excavated material (soil) not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and as directed. |
| 79 | Returning filling in including spreading leveling watering and well ramming in layers n.exc 25cm thick in soft/loose soil , complete all as specified and as directed. |
| 80 | Horizontal Boring for passing GI protection pipe up to 100 mm bore (dia), under road / foot path, not exc. 15.00 metre in a single length, complete all as specified and as directed. |
| 81 | M&L for Sand Cushioning (dry) in Trenches for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 230mm Spread thick -ness and consolidated (punned) upto 180mm thickness, complete all as specified and as directed. NOTE : For the purpose of Payment, Punned thick-ness of Sand Cushioning only shall be Measured and Paid. |
| 82 | S&F Sub-Class B brick, well burnt, laid breadth-wise along the axis of Cable laid in Trenches over Sand Cushion laid for UG Cable Protection, complete all as specified and as directed. |
| 83 | Supply Laying or Fixing or Passing through Pipe, XLPE insulated, Armoured, Electric Power UG Cable (Heavy Duty) with Aluminium Conductor, 1100 Volt Grade, Nominal Cross-Sectional Area 120 sqmm 3.5 core and Testing, including Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and as directed. |
| 84 | S&F Galvanised Iron Pipe 50mm Bore (dia) ‘Light Grade’ for protection of UG Cable, laid in Floors/ Road Crossing, fixing to Pole with Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and as directed. |
| 85 | Material and labour for painting with two coats of synthetic enamel paint over a coat of red oxide metal primer after preparation of external surface of panels & feeder pillar, complete all as specified and as directed. . Materials and Labour for rendering 8 mm thick, cement plaster, in cement mortar (1:4) mixed with water proofing compound as per manufactures instructions over and including 12 mm thick backing coat in cement mortar (1:4) on fair faces of brick work or concrete surface in walls, complete all as specified and directed.Note: - (Water proofing compound will be measured and paid separately) Please Enable Macros to View BoQ information |