| 1 | Providing & erecting 8 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 135 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL |
| 2 | Making M-20 grade reinforced cement concrete foundation by consideringthe safe soil bearing capacity at site as 10 T/sq.m at 1.5m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help oftemplate, duly plastered as per design complete (for 6m to 8m highoctagonal/conical GI pole). |
| 3 | Providing and erecting galvanised 1000mm single arm sword type bracket withFRP dome and ball as per specification no. OH-PL/BKT |
| 4 | Supplying and erecting integrated LED street light fitting 60W IP65 & IK08class having single piece pressure die-cast aluminium housing, having systemlumens output of Min. 6600 Lumens, min. efficacy of 110 lumen/W, CRI>70,CCT upto 6500K, THD<10%, p.f. >0.95, operating range of 140-270V, inbuiltsurge protection of 10 kV, Life class of 50,000 Hrs at L70B50 including drivercomplete with minimum 2 Years warranty as per specification No. FG-ODF/SL. |
| 5 | Supplying & erecting FRP box of size 300mm x 200mm x 125 mm, 2.7 mmthick complete on pole/wall as per specification No. CB-SB |
| 6 | Supplying, erecting & terminating FR XLPE insulated, galvanised steelformed wire armoured (strip) cable, 1100 V 4 core 25 sq. mm. aluminiumconductor complete erected with glands & lugs on wall/ trusses/pole or laid inprovided trench/ pipe as per specification no. CB-LT/AL |
| 7 | Supplying, erecting & terminating FR XLPE insulated, galvanised steelformed wire armoured (strip) cable, 1100 V 4 core 16 sq. mm. aluminiumconductor complete erected with glands & lugs on wall/ trusses/pole or laid inprovided trench/ pipe as per specification no. CB-LT/AL |
| 8 | Supplying and erecting 12.5 m (clear height) motorized high-mast (Top -150mm,Bottom- 360mm) hot dipped galvanized material with average minimum thickness 65 micron, made from high tensile structure grade steel as per BSEN - 10025 S 355/E350 & 3mm thickness, with base plate 25 mm thick x OD 520 mm grade as per IS-2062, pole made in single section & submerge arc welded, with lowering & raising motorized unit, wire rope stainless steel 316 grade 2 nos., 7x19 construction 5mm, SG-DG U clamps, double drum with assembly 250 kg, 5x2.5 Sq.mm.flexible copper cable with lantern carriage assembly suitable for max. 12 nos.luminaries and its control gear box, lightning arrestor, arrangement for fixing aviation light, night glow reflector on pole at suitable height, high-mast with serial number, factory inspection report/test report of high-mast should be provided as per specifications on provided foundation J type stud/bolts with double check nuts & necessary accessories complete. specification no. OHPL/HM |
| 9 | Supplying and erecting outdoor stand mounted feeder pillar for high-mast ofthe same manufacturer with 63A TPN MCB incomer, 24hr astronomical timeswitch with minimum 5 Years battery backup, 45 A TP contactor for automaticswitching of luminaries, 2 no 9A contactors and raise/lower push button, and provision for termination of adequate size of incoming and outgoing cablescomplete erected in min. 14 SWG CRCA sheet box powder coated with supporting angles, self lock, gasket and slanting top erected on CC foundation complete. |
| 10 | Supplying and erecting integrated LED flood light fitting Max. 155W IP65 &IK07 class having pressure die-cast aluminium housing, having system lumensoutput of Min. 18600 Lumens, min. efficacy of 120 lumen/W, CRI>70, CCTupto 6500K, THD<10%, p.f. >0.90, operating range of 140-270V, inbuilt surgeprotection of 4 kV, Life class of 50,000 Hrs at L70B50 including driver with Ushaped bracket with minimum 2 Years warranty as per specification No. FGODF/FL. |
| 11 | Supplying & erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulatedwire laid in provided conduit/trunking/inside pole/bus bars or any other placesas per specification no. WG-MA/BW |
| 12 | Providing & erecting epoxy straight through joint outdoor/indoor for LTXLPE armoured cable 25 to 50 sq mm., with necessary material as perspecification No. CB-JT/LT |
| 13 | Supplying & erecting G.I. pipe ‘A’ class 25 mm dia. for enclosing XLPEarmoured cable on wall/pole as per specification no. CB-CE |
| 14 | Supplying and laying (including excavation of suitable width & depth up to 90 cm)75 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. |
| 15 | Supplying & erecting cast iron cable indicator plate buried along with route ofcable for PVC / XLPE armoured cable as per specification No. CB-CIP |
| 16 | Supplying & erecting crimping type copper lugs for cable 35 sq mm completeas per specification No. CB-CL/CU |
| 17 | Making M-20 cement concrete foundation by considering the safe soil bearingcapacity at site as 10 T/sq.m at 2m depth including excavation and fixing providednut bolts with the help of template, duly plastered as per design complete (for12.5m raising lowering high mast). |
| 18 | Supplying, installing and testing earthing with galvanised iron earth plate size60 x 60 x 0.6 cm complete with all accessories of GI materials & recording theresults as per specification No. EA-EP |
| 19 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or20 mm dia. G.I. Rod complete with all accessories of GI materials & recordingthe results as per specification no. EA-EP |
| 20 | Supplying and erecting regular/ standard model ceiling fan of 1400mm. sweepcomplete erected in position as per specification no. FG-FN/CF. |
| 21 | Supplying and erecting exhaust fan heavy duty 230 V A.C. 50 cycles 450 mm.1400 RPM complete erected in position as per specification no. FG-FN/EXF |
| 22 | Supplying and erecting electronic type step regulator for ceiling fan 600/ 900/1200/ 1400 mm. sweep, complete erected on provided switch board. |
| 23 | Supplying & erecting ready to use Retrofit T8 LED, 18 / 20 watt tube lightwith polycarbonate body, heat sink, integrated HF electronic driver complete &compatible to T8 / T12 LED luminaire by disconnecting starter & ballast ifnecessary as per specification No. FG-LP/RET. |
| 24 | Supplying, erecting & marking DP MCB 6 A to 32 A, B-series with rated short -circuit breaking capacity (Icn) 10kA in provided distribution board as perspecification no. SW-MCB |
| 25 | Supplying, erecting & marking SP MCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no.SW-MCB |
| 26 | Supplying & erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulatedwire laid in provided conduit/trunking/inside pole/bus bars or any other places.as per specification no. WG-MA/BW |
| 27 | Supplying and erecting modular type switch 16A on provided plate and boxwith wiring connections complete. |
| 28 | Supplying and erecting modular type 3 pin 6/16A multi socket with safety shutter on provided plate and box with wiring connections complete. |
| 29 | Supplying and erecting module type switch 6A/10A on provided plate and box with wiring connections complete. |
| 30 | Supplying and erecting modular type 3 pin 6A multi socket with safety shutter on provided plate and box with wiring connections complete. |
| 31 | Supplying and erecting PVC Surface modular switch box with double mounting & front plate for 8 module complete duly connected. |
| 32 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module complete. |
| 33 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 4 module complete. |
| 34 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 6 module complete. |
| 35 | Supplying, erecting, testing & commisioning GI sheet 1.6 mm (16 SWG) having zinc coating of 350 microns with galvanization process compliance to IS2629:1985 to be used for fabrication of boxes panel boards etc. includingcutting, bending, drilling, welding, riveting etc. and painting with one coat of redlead paint and 2 coats of enamel paint as per specification no. CP/SH/CR |
| 36 | Supplying & erecting triple pole and neutral distribution board (TPNDB), SP/TPMCBs total 8 ways/24 poles, with door, 1.2mm thickness surface/flush mounted, IP43 Protection on provided iron/GI frame (vertical busbar type) as per specification no.SW-MCBDB. |
| 37 | Point wiring in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E)FRLSH grade copper wire, flush type switch,earthing and required accessories as per specification no. WG-PW/SW |
| 38 | Supplying & erecting 10-12W, 230V integral type LED Lamp suitable for B-22/E-27 base as per specification no. FG-LP. |
| 39 | Supplying and erecting mains with WP 2 x 6 sq. mm. 1.1kV. grade aluminiumPVC insulated and PVC sheathed wires on G.I. bearer wire no. 8 SWGcomplete erected with required size of porcelain reel insulators and 16 SWGG.I. binding wire. |
| 40 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel wirearmoured (round) cable, 1100 V 3 core 10 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in providedtrench/ pipe as per specification no. CB-LT/AL |
| 41 | Supplying, installing, testing & commissioning split type variable speed inverter technology with minimum 3 to 1 convertible mode for compressor. room airconditioning unit 1.7TR to 2.0TR capacity having ISEER minimum 5.0suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unithi-wall/floor mounting type complete with refrigerant R32 having coppercondenser, minimum 2.5PM filter, self diagnosis feature, stabilizer free operation& temperature display on indoor unit, noise level maximum 50dBA at position inprovided recess with wooden frame complete specification no. AP-AC/SAC |
| 42 | Supplying & erecting seamless outside & inside, smooth, dry and clean copper pipe with ROHS compliant suitable for refrigerant having 22SWG thickness and inner dia/size 16mm complete as per specification no. AP/AC-CP |
| 43 | Supplying, erecting, testing and commissioning self contained watercooler 230/250 V 50 cycles nominal cooling capacity of 80 litres per hour andstorage capacity 120 litres with partially stainless steel body as per specification no. AP-WCR/WC |
| 44 | Supplying and erecting ultra violet storage type water purifier ( RO+UV+UF) with softener for safe drinking water consisting of UV germicidal tube of 8W capacity choke made of copper wire and two indicator lamps with output of purified water minimum 0.33 litre/min with activated carbon filter and softener operating on 230 V single phase A.C. supply with UV fail & filter change indication system .(for TDS more than 200) |
| 45 | Supplying and erecting iron work, sheet metal work consisting of MS sheets,various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc.for panel board or any other purpose with bending, cutting, drilling and weldingcomplete erected at the position with necessary materials duly painted withone coat of red oxide and two coats of enamel paint to match the switchgears oras per directions by the site engineer. |
| 46 | Add GST Charges 18% |
| 47 | Add 1% Insurance Please Enable Macros to View BoQ information |