| 1 | Supplying, erecting, testing and commissioning of diesel generating set with alternator of 25 kVA output continuous rating, 3 phase, 415 V, 50 Hz, 0.8 p.f.,A.C. supply, a totally enclosed air cooled / liquid cooled multi-cylinder dieselengine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12hours, along with standard accessories, self-excited, self-regulated, screenprotected alternator with static excitation system running at 1500 RPM as per IS4722-2001 with voltage regulation +/- 5 %, with performance class G2/G3 andmaximum fuel consumption 5.0 ltr/hr @75% loading. Both the engine andalternator direct coupled on a common fabricated steel base frame and mountedon anti-vibrating pads, with standard control panel comprising meters,switchgears, indicators connected with suitable wires/cables, the complete setenclosed in composite acoustic enclosure as fully assembled integral unit made of16 SWG CRCA sheet, sound absorbing material to restrict sound level up to 75dB at 1.0 m, provided with first filling of oil, diesel not less than 65 ltr etc., onprovided M20 grade CC foundation as per specification no. GEN-DG |
| 2 | Supplying, erecting, testing and commissioning of microprocessor based AMF panel suitable for diesel generating set of above 20 kVA upto 25 kVA capacity 3 phase, 415 V, 50 Hz, A.C. supply with all standard features, safeties etc as perspecification no. GEN-AMF. |
| 3 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 70 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL(7-1-33) |
| 4 | Providing & erecting epoxy straight through joint outdoor/indoor for LTXLPE armoured cable 25 to 50 sq mm., with necessary material as perspecification No. CB-JT/LT(7-4-2) |
| 5 | Supplying and laying (including excavation of suitable width & depth up to 90cm) 90 mm outside dia. double wall corrugated pipes (DWC) of HDPEfor enclosing cable below ground/road surface, complete. |
| 6 | Supplying & erecting single compression type brass cable glands for 4 core35 Sq.mm./3 core 50 Sq.mm. cable as per specification no. CB-GL |
| 7 | Supplying & erecting crimping type copper lugs for cable 35 sq mm completeas per specification No. CB-CL/CU |
| 8 | Making trench in Hard murum/Tar road having 0.75m depth and minimum0.3m width for laying provided cables up to voltage level 1.1kV cable complete asper specification no. CW-EXN-CTR |
| 9 | Making cement concrete foundation in 1:3:6 cement concrete, (20 to 25) mm.stone metal duly plastered with necessary curing for complete. (pole muffing orany other purpose). |
| 10 | Supplying and erecting iron work, sheet metal work consisting of MS sheets,various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc.for panel board or any other purpose with bending, cutting, drilling and weldingcomplete erected at the position with necessary materials duly painted withone coat of red oxide and two coats of enamel paint to match the switchgears oras per directions by the site engineer. |
| 11 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG GI sheet of 150 mm width & 100 mm height withrequired standard accessories.(7-11-1) |
| 12 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recordingthe results as per specification no. EA-EP(9-1-4) |
| 13 | Providing & erecting 3 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB should have phase barriers both sides, with insulation withstand capacity 800V,no line-load bias in provided enclosure/panel as per specification no. SW-MCCB(5-5-4) |
| 14 | Supplying, erecting, testing & commisioning metal work in CRCA sheetincluding Iron work for supports with fabrication of boxes, panel boards, etc.including cutting, bending, drilling, welding, riveting, treated with anti-rusttreatment and painted with one coat of red lead paint and 2 coats of enamel paint or powder coating complete as per specification no. CP/SH/CR(6-1-1) |
| 15 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel wirearmoured (round) cable 1100 V, 3 core 4 sq. mm. copper conductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU(7-2-15) |
| 16 | Supplying & erecting ON LOAD change over switch 4 Pole, 415V, 200A, openexecution having staggered termination, phase barrier, shroud termination and terminal cover along with auxiliary contacts and ready to upgrade with fuse protection kit, operational current category AC23A complying to IS/IEC 60947-3 Part-1/3 as per specification no. SW-SWR/COS.(5-1-6) |