| 1 | Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. 2 TR or 2.5 HP (or above) 4 - way Cassette Unit Make:- Daikin/Toshiba/Mitsubishi Electric |
| 2 | Supply, installation, testing and commissioning of following minimum capacity 4-way flow VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature 3 TR or 4.0 HP (or above) 4 - way Cassette Unit Make:- Daikin/Toshiba/Mitsubishi Electric |
| 3 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications 9.5 mm dia (3/8) (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation Make:- Rajco/Mandev/Maxflow |
| 4 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications12.7 mm dia (1/2) (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulationMake:- Rajco/Mandev/Maxflow |
| 5 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications15.86 mm dia (5/8) (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulationMake:- Rajco/Mandev/Maxflow |
| 6 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications19.1 mm dia (6/8) (OD) (hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Make:- Rajco/Mandev/Maxflow |
| 7 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications22.2 mm dia (OD) (7/8) (hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Make:- Rajco/Mandev/Maxflow |
| 8 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications28.58 mm dia (11/8) (OD) (hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation Make:-Rajco/Mandev/Maxflow |
| 9 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications34.9 mm dia (13/8) (OD) (hard drawn) with tube thickness 1.62 mm with 19 mm thick insulationMake:- Rajco/Mandev/Maxflow |
| 10 | Supply and Fixing of Interconnecting copper refrigerant pipe work with thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications41.3 mm dia (15/8) (OD) (hard drawn) with tube thickness 1.62 mm with 19 mm thick insulationMake:- Rajco/Mandev/Maxflow |
| 11 | Supply and Installation of Refrigerant R-410A to top up the system as per directions of OEM. |
| 12 | Supply, installation, testing and commissioning of refrigerant Copper Y-joints Make:- Daikin/Toshiba/Mitsubishi Electric |
| 13 | Supply, Installation, Testing and Commissioning of Master Remote Control panel including all necessary control wiring. Master Remote Control Panel shall be connected to all indoor/outdoor units and shall be of one touch screen type.Suitable for indoor units.Make:- Daikin/Toshiba/Mitsubishi Electric |
| 14 | CONTROL AND TRANSMISSION WIRING: Supply and Laying of 2 core x 1.5 sqmm PVC insulated copper conductor communication control cable in PVC Conduit. Make : Havells/ Polycab/ RR Kabel as per directions of Engineer In-Charge |
| 15 | POWER CABLE: Supply and Laying of 3 core x 2.5 sqmm PVC insulated copper conductor cable for indoor units. Make : Havells/ Polycab/ RR Kabel as per directions of Engineer In-Charge |
| 16 | Supply and Laying 4.0 core x 25 Sq.mm Alluminium conductor armoured cable. Make : Havells/ Polycab/ RR Kabel as per directions of Engineer In-Charge |
| 17 | Providing and fixing of MS Stand for Outdoor Units. |
| 18 | Supply, Installation, Testing and Commissioning of Modular Type outdoor units, equipped with Highly Efficient Scroll, all Inverter Compressor(s), special heat exchanger, Y- branch as required, outdoor unit support, auto check function for connection error, auto address setting,Refrigerant temperature control and capacity as mentioned below. VRV/VRF System shall be suitable for working on 50°C ambient temperature, Refrigerant R 410A. VRV/VRF System shall be suitable for working on 50°C Ambient Temperature, with Refrigerant R-410A. Unit price shall be inclusive of full charge of Refrigerant Gas and Oil, Freight, Insurance as applicable In INR. The COP of systems mentioned below shall be Minimum 7.1 at 50% load, at AHRI conditions in cooling conditions. The manufacturer of ODU and compressor shall be same. i.e the make of compressor shall be identical to the ODU. The ODU Shall have refrigerant cooled PCB chamber for better operation at high ambient temperature.The system shall deliver at least 87% of mentioned nominal capacity at 43 Deg C ambient temperature. The fan static pressure of ODU shall be minimum 75 Pa to avoid hot air accumulation40 HP (20 HP plus 20 HP ODU UNIT) Make:- Daikin/Toshiba/Mitsubishi Electric |
| 19 | Supply, installation, testing and commissioning of cubical type main MV panel board suitable for 3 Phase, 50 Hz and of 35 MVA rupturing capacity at 415 volts, fabricated from minimum 2mm thick CRCA sheet powder coated through seven tank process facility for prickling and degreasing complete with following mountings, interconnections etc. as required. (GA drawing of panel to be provided before fabrication). Panel shall be Floor mounted type with cable entry at the top and IP-65 Degree of protection. Panel shall be powder coated having colour shade RAL-7032. including the following switch gear and components: INCOMER: 400A FP MCCB 36KA TMR plus Spreader Links-01 NosOUTGOINGS: 125A FP MCCB 10KA (FOR VRF ODUs) - 7 Nos (as per site requirement) 10A TPN MCB 10KA(FOR VRF IDUs) - 82 Nos Make:- Havells/LandT/Siemens |
| 20 | [22.83]Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof. [Through Rate] |
| 21 | [22.87.3]Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings This includes jointing of pipes and fittings with one step CPVC solvent cement, trenching, refilling and testing of joints complete as per direction of Engineer in Charge. External work 3. 25 mm nominal outer dia Pipes [Through Rate] |
| 22 | [22.87.4]Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings This includes jointing of pipes and fittings with one step CPVC solvent cement, trenching, refilling and testing of joints complete as per direction of Engineer in Charge. External work 4. 32 mm nominal outer dia Pipes [Through Rate] |
| 23 | [22.87.5]Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings This includes jointing of pipes and fittings with one step CPVC solvent cement, trenching, refilling and testing of joints complete as per direction of Engineer in Charge. External work 5. 40 mm nominal outer dia Pipes [Through Rate] |
| 24 | [22.87.6]Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings This includes jointing of pipes and fittings with one step CPVC solvent cement, trenching, refilling and testing of joints complete as per direction of Engineer in Charge. External work 6. 50 mm nominal outer dia Pipes [Through Rate] |
| 25 | [23.23.6..2]MISCELLANEOUS 6..2. Supply and erection of MS cable tray , duly pained as required including erection of the same on wall or ceiling with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. MS perforated cable tray painted with powder coating 200 X 50 X 2 mm [Through Rate] |
| 26 | [23.23.6.1]MISCELLANEOUS 6.1. Supply and erection of MS cable tray , duly pained as required including erection of the same on wall or ceiling with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. MS perforated cable tray painted with powder coating 100 X 50 X 2 mm [Through Rate] |
| 27 | [23.23.7.1]MISCELLANEOUS 7.1. Supply and erection of cable tray cover made of 1.25 mm thick GI sheet as required including erection of the same on existing cable tray with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. GI cable tray Cover , suitable for cable tray of 100 X 50 X 2 mm [Through Rate] |
| 28 | [23.23.7.2]MISCELLANEOUS 7.2. Supply and erection of cable tray cover made of 1.25 mm thick GI sheet as required including erection of the same on existing cable tray with necessary fixture and other material required to complete the job in all respect up to the entire satisfaction of Engineer-in Charge of the work. GI cable tray Cover , suitable for cable tray of 200 X 50 X 2 mm [Through Rate] |
| 29 | [23.7.6.2]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.2. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia. [Through Rate] |
| 30 | [23.7.6.3]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.3. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 32 mm dia. [Through Rate] |
| 31 | [24.1.1]EARTHING AND LIGHTENING ARRESTOR 1. Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required. [Through Rate] |
| 32 | [24.1.2]EARTHING AND LIGHTENING ARRESTOR 2. Extra for using salt and char coal/coke for pipe earth electrode as required. [Through Rate] |
| 33 | [24.1.3]EARTHING AND LIGHTENING ARRESTOR 3. Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required. [Through Rate] |
| 34 | [24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode. [Through Rate] |
| 35 | [24.1.9]EARTHING AND LIGHTENING ARRESTOR 9. Providing and fixing 25 mm x5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required. [Through Rate] Please Enable Macros to View BoQ information |