| 1 | Wiring for light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface /recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc.as required.Group C |
| 2 | ..Do.. but for tube light point |
| 3 | ..Do.. but for Fan point |
| 4 | ..Do.. but for Street light point |
| 5 | ..Do.. but forTwin control point |
| 6 | S/F of 5/6 Amp Plug point on existing switch board |
| 7 | Supplying and fixing suitable size GI box with modular plateand cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modularswitch, connections etc. as required. Separate plug point |
| 8 | Supplying and fixing suitable size GI box with modular plateand cover in front on surface or in recess, including providingand fixing 6 pin 5/6 A & 15/16 A modular socket outlet and15/16 A modular switch, connections etc. as required. Power point |
| 9 | Supplying and fixing PVC batten/ angle holder includingconnections etc. as required. |
| 10 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junctionbox/ wooden block including connections etc. as required. |
| 11 | Wiring for group controlled (looped) light point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C |
| 12 | Supplying and fixing two module stepped type electronic fanregulator on the existing modular plate switch box includingconnections but excluding modular plate etc. as required. |
| 13 | Supplying and fixing following way, single pole and neutral, sheetsteel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,tin bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator) 6 way Double Door |
| 14 | Supplying and fixing following way, horizontal type three poleand neutral, sheet steel, MCB distribution board, 415 V, onsurface/ recess, complete with tinned copper bus bar, neutralbus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator). 4 way (4 + 12), Double door |
| 15 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C”curve, miniature circuit breaker suitable for inductive load offollowing poles in the existing MCB DB complete withconnections, testing and commissioning etc. as required. Single pole |
| 16 | Supplying and fixing following rating, four pole, 415 V, isolator inthe existing MCB DB complete with connections, testing andcommissioning etc. as required 40A |
| 17 | Supplying and fixing following rating, double pole, 240 V, isolatorin the existing MCB DB complete with connections, testing andcommissioning etc. as required 40A |
| 18 | Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, singlecore cable in surface/ recessed medium class PVC conduit asrequired. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 19 | …Do… But 2 X 2.5 sq. mm + 1 X 2.5 sq. mm |
| 20 | …Do… But 2 X 4 sq. mm + 1 X 4 sq. mm |
| 21 | Wiring for circuit/ submain wiring alongwith earth wire with thefollowing sizes of FRLS PVC insulated copper conductor, singlecore cable in surface/ recessed medium class PVC conduit asrequired. 4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 22 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thickincluding accessories, and providing masonry enclosure withcover plate having locking arrangement and watering pipe of2.7 meter long etc. with charcoal/ coke and salt as required. |
| 23 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or inrecess for connections etc. as required. |
| 24 | S/F of 10 Watt LED Lamp 2 Star Rating and 950 Lumen Output |
| 25 | S/F of 20 Watt LED Batten With Aluminium Housing and Integrated Electronic Driver |
| 26 | S/F of 45 Watt LED Street Light with Aluminium Housing and Lens Embedded PC Cover having bottom opening separate driver compartment with IP 66 protection and impact Resistance of IK08 |
| 27 | S/F of 36 Watt LED Panel mounting Luminaire with high brightness SMD LEDs as light source , sutaible for Armstrong /grid Ceiling |
| 28 | S/F of Ceiling Fan 1200mm Sweep Cover and Atleast 2 star Rating |
| 29 | S/F of Switch Disconnector 4 Pole 400 Amp( same Function as Isolator) |
| 30 | S/F of Switch Disconnector 4 Pole 250Amp( same Function as Isolator) |
| 31 | S/L of 3.5x 240 sq mm Al Armoured Cable in Existing Cable Tray / pipes as required |
| 32 | S/L of 3.5x 185 sq mm Al Armoured Cable in Existing Cable Tray / pipes as required |
| 33 | S/L of 4x6 sq mm Copper Armoured Cable in Existing Cable Tray / pipes as required |
| 34 | Main LT PanelSupply and Erection of factory fabricated dust and vermin proof floor mounting panel complete with following rating and breaking capacity MCCB with TMR and Terminal Spreader , Digital Ammeter, Digital Voltmeter , selector Switch and Suitable Size Al Busbar as per 8623 insulation with Heat shrink sleeving and Mounted on Non - Hygroscopic Support in Cubical Panel Board Including Drilling Holes, making connections, the switch board shall be fabricated with CRCA Sheet with Min.m Thickness of 1.6mm/2mm having cubical type switch Board.INCOMER1. MCCB 400A , FP, 36 KA THERMAL magnetic release 2.spreader terminal for 400 A FP MCCB 3. Extended rotary handle for 400A MCCB METERING AND PROTECTION 1. DIGITAL VOLTMETER 440V ACCLI 2. VOLT SELECTOR SWITCH 6A 3. DIGITAL AMPERE METER 440V ACCLI 4. AMP. SELECTOR SWITCH 6 A . 5. C.T. 400/5A , 10VA RESIN type 6. Phase indication lamp red , yellow blue... 7. neutral link 8. CONTROL MCB 6A SP10 KA \\"C\\" CURVEOUTGOING FEEDER SECTION 1.ON LOAD CHANGEOVER 400 A FPOUTGOING1. MCCB 250 A ,FP,25 KA , TMR :1no.2.MCCB 25A , FP ,25KA , TMR: 1 no.3. MCCB 16 A , FP , 18 KA,TMR : 5 no4. VACANT CHAMBER FOR MCCB : 1 no.. Please Enable Macros to View BoQ information |