| 1 | Supply, installation, testing and commissioning of silent diesel Engine driven generating set 415 volts, 3 phase 4 wire engine of capacity 40 KVA as per IS: 10001/10002 and Alternator as per IS: 13364 complete with standard control panel, meter and sound proof canopy as per CPCB Norms-IV and foundation for DG Set and AMF Panel etc relay panel and switch gears for automatic starting on main failure of 40 KVA made out of 3.15 mm thick CRCA sheet outdoor type with vermin proof powder coated painting all as specified and directed by Engr-in-Charge. NOTE FOR DG :A). DIESEL ENGINE :Diesel Engine rated 1500 rpm. Radiator Cooled Engine with CRDi System four stroke and three cylinder conforming to BS 5514/ ISO 3046.(i) Electrical starter motor 12V DC(ii) Battery charging alternator(iii) Electronic Governor(iv) Spin-on fuel filter(v) Spin-on full flow lube oil filter(vi) Residential Silencer(vii) Air Cleaner (paper element type)(viii) Recovery bottle(ix) Safety for LLOP/ HWT(x) Flywheel & Flywheel housing(xi) First Fill to lube oil and coolant |
| 2 | B). ALTERNATOR :Synchronous Alternator of 40 KVA of 'H' class insulation suitable for continuous operation at 1500 rpm 230/ 415 Volts 0.8 to 1 pf (lag), 50Hz 3 phase 4 wire system conforming to BS 5000/ IS 4722, Brushless type screen protected revolving field, self excited, self regulated, (+-) 1.0 % Voltage Regulation (Max) in static conditions, Permissible overload 10% for one hour in 12 hrs operations.C). CONTROLLER :The genset control panel is manufactured with 3.15mm CRCA sheet and powder coated for a weather proof, long last finish. Control panel consist of following parts:-(i) Microprocessor based Engine Instrumentation.(ii) Graphical LCD display(iii) Individual phase current (Amps)(iv) Phase voltage (V)(v) Frequency (Hz)(vi) Lube oil pressure (kPa)(vii) Working hours(viii) MCB of suitable rating(ix) LED indication for main failure(x) Suitable current transformers(xi) Integrable with AMFD). Lube oil change period 500 hrsE). Sound proof canopy as per CPCB Norms-IV with inbuilt silencerF). Base Frame in MS iron material |
| 3 | G). AUTO MAIN FAILURE PANEL :(i) Line Volage Monitoring - 01 No(ii) 100 Amps ATS Switch - 01 No(iii) 240V AC Control Contactor - 02 No(iv) 12V Battery Charger - 01 No(v) Auto/ Manual Switch - 01 No(vi) 12V Relay - 02 No(vii) 220V AC Indicating Lamp - 02 No(viii) 6 Amps IP MCB for DC Control - 01 No(ix) 25 Sqmm Power wire - 01 No(x) 100Amps 4 way terminal - 03 NoH). Drawing for foundation as recommended by manufacturer of DG Set and Panel to be produced to Engr-in-charge |
| 4 | Supply and laying 70 SQMM 3.5 Core LT UG cable, 1100 volts grade, XLPE insulated and sheathed, armoured, multistranded, heavy duty electric cable with aluminium conductor laid in trenches, ducts, on poles, walls, through pipes etc including identification tags over on cable complete including cable glands on both side terminations where necessary complete all as specified and directed by Engr-in-Charge. |
| 5 | Excavation in trenches not exc. 1.5 m wide and not exc.1.5 m deep for laying of cable, pipe and for erecting of steel tubular swaged pole etc, and getting out in hard/dense soil complete all as directed by Engg-in-charge. |
| 6 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as directed by Engg-in-charge. |
| 7 | Removing excavated material not exc 50 meters and depositing where directed at a level not exceeding 1.5 mtr above the starting points in soil all as directed by Engineer-in-Charge. |
| 8 | Supply and Laying of HDPE DWC Pipe medium grade of size 90mm outer Dia for protection of XLPE UG cable complete all as directed by Engg-in-charge. |
| 9 | Earthing with galvanised steel earth plate electrode 60cmX60cmX6mm thick, buried directly in Ground vertically at a depth not less than 2.25 METRE below Ground Level with the Top Edge of Earth Plate at a depth not less than 1.50 METRE below Ground Level connected to galvanised iron strip of size 32x6mm as Earthing Lead by means of Bolts, Nuts, Check Nuts and Washers of galvanised iron , Earth Plate Electrode surrounded by a packed thickness of Charcoal or Coke Dust mixed with Common Salt in alternate layers of not exc. 150mm thick, GI Strip protected with and including 40mm bore GI Light Grade Pipe up to 1.0 METRE above the Floor Level of the Building where Main Switch/DB situated including PCC Pit in Cement Concrete (1:3:6) type C1 (20mm Graded Stone Aggregate) and RCC Cover of size 450X450X50mm in RCC (1:2:4) type B1 (20mm Graded Stone Aggregate) reinforced with and including 8.0mm Dia TMT Bars @ 100mm centre to centre both ways, GI Wire Mesh, Funnel, 20mm bore Medium Grade GI Watering Pipe, necessary Excavation in Soft/Loose Soil, returning, filling in and removal of surplus Spoil up to a distance of 50.00 metre and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on completion as specified and directed by the Engineer-in-Charge. |
| 10 | Removing/ shifting and refixing the main supply cable from existing LT feeder/ transformer to proposed AMF panel for unaltered power supply complete all as specified. Note : Rate quoted is inclusive of tools, plants/ machinery used for the work. |
| 11 | Dismantling /taking out the existing Pump & Motor of capacity up to 20HP including breaking the existing foundation of pump & motor from the site/pump house/borewell/Open well and depositing the same to the MES Store Yard of GE Tirunelveli Complete all as directed by Engg-in-Charge. |
| 12 | Supply & Fixing Monoblock pump set suitable for 230 V Single phase system having capacity 3 HP Size 50MM x 40MM including PCC foundation Base of suitable size, anchor Nut & Bolt, electrical connection with pump starter/starter panel, necessary modification for fixing and connecting the inlet & outlet pipe complete all as directed by Engg-in-charge Make- Kirloskar ( Model- KDS-355++) or Equivalent model of Crompton/Havells |
| 13 | Supply & Fixing Sewage Dewatering Pump self-priming 5 HP 3 phase 415 Volt size 80mm x 80mm including PCC foundation Base of suitable size, anchor Nut & Bolt, electrical connection with pump starter/starter panel, necessary modification for fixing and connecting the inlet & outlet pipe complete all as directed by Engg-in-charge. Make- Kirloskar (Model-SP3L++CS) or Equivalent model of Crompton/Havells |
| 14 | Supply & Fixing Open well submersible pump 7.5 HP three phase 380 Volt size 65mmx50mm including PCC foundation Base of suitable size, anchor Nut & Bolt, electrical connection with pump starter/starter panel, necessary modification for fixing and connecting the inlet & outlet pipe complete all as directed by Engg-in-charge. Make-Kirloskar (Model-JOS-846)or Equivalent model of Crompton/Havells |
| 15 | Supply & Fixing monoblock Pump set suitable for 415 V three phase system having capacity 20 HP. Size 100mmx80mm including PCC foundation Base of suitable size, anchor Nut & Bolt, electrical connection with pump starter/starter panel, necessary modification for fixing and connecting the inlet & outlet pipe complete all as directed by Engg-in-charge. Make- Kirloskar, (Model- KDS 2050+) or Equivalent model of Crompton/Havells |
| 16 | Supply & Fixing Monoblock Pump set Single Phase 5 HP size 80mmx80mm including PCC foundation Base of suitable size, anchor Nut & Bolt, electrical connection with pump starter/starter panel, necessary modification for fixing and connecting the inlet & outlet pipe complete all as directed by Engg-in-charge. Make-Kirloskar (Model-KDS520+) or Equivalent model of Crompton/Havells |
| 17 | Supply & Fixing Dewatering Pump Self Priming 3HP Three Phase 415 Volt of size 50MMx50MM including PCC foundation Base of suitable size, anchor Nut & Bolt, electrical connection with pump starter/starter panel, necessary modification for fixing and connecting the inlet & outlet pipe complete all as directed by Engg-in-charge. Make- Kirloskar( Model-SP-2HCS) or Equivalent model of Crompton/Havells |
| 18 | Supply & Fixing Monoblock Pump 1.5 HP single Phase 230 Volt size 50Mmx40 mm including PCC foundation Base of suitable size, anchor Nut & Bolt, electrical connection with pump starter/starter panel, necessary modification for fixing and connecting the inlet & outlet pipe complete all as directed by Engg-in-charge. Make- Kirloskar (Model-KDS-1.522++) or Equivalent model of Crompton/Havells |
| 19 | Supply & Fixing Open well vertical Submersible Pump set 15 HP 3 Phase 415 Volt size 80mm including PCC foundation Base of suitable size, anchor Nut & Bolt, electrical connection with pump starter/starter panel, necessary modification for fixing and connecting the inlet & outlet pipe complete all as directed by Engg-in-charge. Make-Kirloskar (Model-JVSA-1506) or Equivalent model of Crompton/Havells |
| 20 | Supply and laying in trenches steel water tubing 100 MM galvanised medium grade and connection including fitting like Tee, Bend, Socket, Elbow, Short pieces connectors, plugs, and unions etc, cutting thread including taking down old existing complete all as directed by Engg-in-Charge. |
| 21 | Supply and laying in trenches steel water tubing 80 MM galvanised medium grade and connection including fitting like Tee, Bend, Socket, Elbow, Short pieces connectors, plugs, and unions etc, cutting thread including taking down old existing complete all as directed by Engg-in-Charge. |
| 22 | Supply and laying in trenches steel water tubing 50 MM galvanised medium grade and connection including fitting like Tee, Bend, Socket, Elbow, Short pieces connectors, plugs, and unions etc, cutting thread including taking down old existing complete all as directed by Engg-in-Charge. |
| 23 | Supply and laying in trenches steel water tubing 40 MM galvanised medium grade and connection including fitting like Tee, Bend, Socket, Elbow, Short pieces connectors, plugs, and unions etc, cutting thread including taking down old one Complete all as directed by Engg-in-Charge. |
| 24 | Supply and fix NON RETURN VALVE cast Iron double flange as per IS/5312 PN 1.6 rating complete with Bronze body & wedge Stainless Steel spindle, Gland packing, Rubber gasket Valve, reflux, with by-pass Arrangement, 40/50 mm Dia including taking down old one complete all as directed by Engg-in-charge. |
| 25 | Supply and fix NON RETURN VALVE cast Iron double flange as per IS/5312 PN 1.6 rating complete with Bronze body & wedge Stainless Steel spindle, Gland packing, Rubber gasket Valve, reflux, with by-pass Arrangement,80 mm Dia including taking down old one complete all as directed by Engg-in-charge. |
| 26 | Taking down old defective foot valve and supply and fix new CI foot valve 50 MM heavy duty with confirming IS-4038 complete all as specified and directed |
| 27 | Taking down old defective foot valve and supply and fix new CI foot valve 80 MM heavy duty with confirming IS-4038 complete all as specified and directed |
| 28 | Supply and fix water proof submersible flexible flat copper cable, 4 Sqmm 3 core, 1100 Volts complete all as specified and directed. Note : Rate quoted shall be deemed to be inclusive of the cost of under water fixing arrangements complete |
| 29 | Supply and fix water proof submersible flexible flat copper cable, 6 Sqmm 3 core, 1100 Volts complete all as specified and directed. Note : Rate quoted shall be deemed to be inclusive of the cost of under water fixing arrangements complete |
| 30 | Supply and fix water proof submersible flexible flat copper cable, 10 Sqmm 3 core, 1100 Volts complete all as specified and directed. Note : Rate quoted shall be deemed to be inclusive of the cost of under water fixing arrangements complete |
| 31 | Supply and fix Liquid chlorine dosing system having Dosing Pump 01 Nos, 0-6 LPH Capacity for dosing liquid chlorine to achieve residual dosing in the range of 0.2 to 0.5 PPM with a dosing tank of 100 litre and operating panel -01 No capacity including necessary foundation/stand support, electrical work (including wiring), pipeline lines work complete all as directed by Engg-in-charge. |
| 32 | Taking down unserviceable Split/Window Type Air Conditioner of capacity 1.5 TR to 2.0 TR from its existing location and depositing to MES store yard of AGE E/M Tirunelveli complete all as specified and directed. |
| 33 | Supply, installation, commissioning and testing of Split type Air Conditioner of 1.5 TR (4500 Kcal/Hr) capacity, Digital inverter type, complete with cordless remote control unit with LCD/LED display, 5 star rating and EER of 3.3 and above. Indoor unit Hi wall mounted type suitable for 230 volts, 50 Hz, single phase AC supply and capable of performing the function as cooling , heating, air circulating and filtering. Outdoor unit of the air conditioner shall be fitted with discharge cool type rotary/ scroll compressor operating on non-CFC refrigerants (like R410 A or equivalent) with over load protection and mounted on resistant mountings for quite operation. The filters packs provided shall be washable. Remote cordless control shall be provided with ON/OFF timer, fan speed selector (min 3 speed), mode selector (cooling/fan) and setting -up of temperature. Display of temperature and mode shall be provided on indoor unit and on handset. Overall power factor of the unit shall not be less than 0.85 at operating conditions. Note :- The installation shall include Laying refrigerant piping, extension of drain pipe up to 3 mtr length and connecting both units after drilling holes, putting PVC sleeve, sealing and fishing the same duly matched with adjoining surface. Refrigerant pipe shall be insulated with expanded polyethylene foam not less than 5mm thick. Leak testing of the entire system after installation to be carried out. Rate quoted will include Charging refrigerant gas in the unit, suitable electric connection between indoor and outdoor unit.Note:- (1) Refrigerant Pipe including insulation, Electric connection between indoor and outdoor unit by 2.5 Sqmm 4 core and electric connection from plug socket by 2.5 Sqmm 3 core beyond the length as supplied by the OEM if required shall be measured and paid separately |
| 34 | Supply & Fixing heavy duty air conditioner Outdoor unit mounting bracket made up of heavy duty powder coated mild steel sheet suitable to carry load of capacity 2.0TR outdoor unit and all as directed by engg-in-charge. |
| 35 | Supply & Fixing Plug Top 3 pin 16 Amp complete all as directed by Engg-in-Charge. Make- Anchor/Havells/Legrand |
| 36 | Supply and laying of copper refrigerant pipe 1/4\\" Dia with PUF insulation as per required length at site complete with brazing and flaring nuts of suitable size (brass) all as specified and as directed by the Engr-in-Charge. |
| 37 | Supply and lay of copper refrigerant pipe 1/2\\" Dia with PUF insulation as per required length at site complete with brazing and flaring nuts of suitable size (brass) all as specified and as directed by the Engr-in-Charge. |
| 38 | Supply & Fixing PVC insulated 3 Core 2.5 Sqmm copper FRLSH round wire for connection of Split AC to socket point as and where required complete all as directed by Engg-in-Charge. |
| 39 | Supply & Fixing PVC insulated 4 Core 2.5 Sqmm copper FRLSH round wire for connection of Split AC outdoor and indoor as and where required complete all as directed by Engg-in-Charge. Please Enable Macros to View BoQ information |