| 1 | Deploying the following staff for repair, maintenance and upkeep of all internal electrical installation & fans, Compound light, Submersible P/sets and DG Sets of CE (East Zone), CE (South Zone), SCC-3, QAC Lab, I.E.I. work of 14 Nos. Staff Qtr. at AGVC, 16 Nos. Staff flats at Chirag Enclave & Saket and Street lighting & parking lighting in front of BHEL parking, Siri fort sport Complex parking area etc. as required at site. a) Wireman Gr II - 2 Nos. |
| 2 | b) Khallasi - 2 Nos. |
| 3 | Deploying the following staff for servicing, repairing and maintenance of Window, Split air conditioners, Water coolers in the various offices of DDA at Shahpurjat and AGVC office complex. (Note:- The following staff will be deployed as per requirement at site or as per directions of Engineer-in-charge) a) Wireman cum AC mechanic Grade I -1 No. (in general shift) |
| 4 | b) Khallasi -1 No. |
| 5 | Supplying & replacement of 18”/20” desert cooler body of size H-86, W-65 & D-65 cm (+/-3%) made out of 18 SWG G.I. sheet (Top Tank, Legs) & 22 SWG, G.I. Grill front & side louvers with distributer PVC pipe 1/2 “ dia wood wool pads, control plate with 2 Nos. 5 Amp. Switch etc. as required. |
| 6 | Servicing & replacement of desert coolers wood pads (3 Nos.) set suitable for 18”/20” size desert coolers i/c removing of old pads, cleaning of dust, greasing, oiling, testing of fan motor, water pump, connection etc. complete as required. |
| 7 | Supplying & fixing electric power driven cooler pump (submersible type) 1400 rpm (appox.) having 1 meter head, discharge 5.5 Ltrs/min (appox.) with nut bolts of suitable size for 18”/20” cooler connection, testing etc. complete as required. |
| 8 | Servicing & cleaning/ polishing of steel surface of Four Nos. drinking water coolers quarterly i/c dismantling of fan motor, cleaning of condenser, water tank, oiling, checking & repairing of water connection for leakage of drain pipe, over flow pipe, float valve etc. as required. |
| 9 | Rewinding of exhaust fan / ceiling fan i/c cutting the old winding wire, rewinding the same with suitable size of enameled copper wire, varnishing, backing, greasing, oiling, testing etc. as required, i/c credit for old winding wires. |
| 10 | Supplying & replacement of desert cooler connection cord 23/76 three core & flexible copper wire with 15 Amp Top, connection, testing etc. complete as reqd. |
| 11 | Supplying & fixing of single phase cooler motor suitable for operation of 220 Volt, 50 Hz 450, 1370 rpm (appox.) with copper winding complete mounting accessories suitable for 18”/20” desert cooler, providing & fixing GI nut, bolt of suitable size, legs, connections, testing etc. complete as required. |
| 12 | Supply and fixing the desert cooler fan blade of suitable size including connection etc. as required. |
| 13 | Supplying and fixing following rating capacitors in the desrt coolers and Window/ Split Air conditioners etc as required.a) 5 mfd for desert cooler |
| 14 | b) 45 mfd for AC |
| 15 | Painting, cleaning of 18”/20” desert cooler outer body after removing the existing paint/rust and repairing of all parts of desert cooler ( except water pump and front portion Grill) etc. complete as required. |
| 16 | Servicing of window/split Air Conditioners of 1.5 Ton/ 2.0 Ton capacity i/c cleaning of condenser coil, cooling kit with water soap solution, lubrication fan motor, cleaning & rectifying defects in electrical wiring numbering etc. as required. a)Window type AC 1.5 Ton/ 2.0 Ton. |
| 17 | b) Split type AC 1.5 Ton/ 2.0 Ton. |
| 18 | Supply and fixing of Copper tubes of dia. ½” & 3/8”, along with 3 core 70/76 wire, drain pipe, clamps, insulation i/c testing, commissioning etc. as required. |
| 19 | Supplying & charging of refrigerant in the following air conditioners/ water coolers of different make including detection of minor puncture & repairing the same capillary replacement including testing as required. a) Window type AC 1.5/2.0 T capacity. |
| 20 | b)Split type AC 1.5/2.0 T capacity. |
| 21 | c) Water coolers 120/150 ltrs. Capacity. |
| 22 | Supplying & replacement of burnt/defective compressor manufacture re-operated compressor of same capacity suitable for 1.5/2.0 Ton window or split AC including gas charging, nut, bolts, washers, rubber bushes including brazing, welding etc. as required. |
| 23 | Supplying and replacement of outdoor colour coated copper condenser coil for 1.5/2.0 Ton capacity split AC including connection, brazing, welding etc. as required. |
| 24 | Supply, Installation, Testing and Commissioning of suitable wattage ceiling fan having 1200 mm sweep size, BEE 5 star rated, suitable for 230 V, 50 Hz, single phase AC supply, earthing etc. complete as required. |
| 25 | Supply of 18-22 watt surface and wall mounted LED batten having lumen efficacy > = 105( lm/watt) with powder coated die cast /extruded aluminium housing and integrated electronic driver as complete as required. |
| 26 | Supply and fixing of 2x2 ft. 36 Watt LED panel light with powder coated die cast /extruded aluminium body having driver efficiency > 85% suitable for operation at 140-270 Volt, 50 Hz, single phase AC supply fitting commissioning, testing complete as required. |
| 27 | Lifting of submersible pump out of the existing bore well including dismantling of GI pipe complete as required. |
| 28 | Lowering of submersible pump in the existing bore well including re-assembling the GI pipe complete as required. |
| 29 | Supplying and fixing 5A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single pole |
| 30 | b) Double pole |
| 31 | c) Triple pole and neutral |
| 32 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. a) 20 mm |
| 33 | b) 25 mm |
| 34 | Supply and fixing of Call bell/ buzzer suitable for single phase 230 V complete as reqd. |
| 35 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. a) 3 x 1.5 sq. mm |
| 36 | b) 3 x 2.5 sq. mm |
| 37 | c) 3 x 4.0 sq. mm |
| 38 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 5/6 A switch |
| 39 | b) 15/16 A switch |
| 40 | c) 3 pin 5/6 A socket outlet |
| 41 | d) 6 pin 15/16 A socket outlet |
| 42 | Bell push |
| 43 | Servicing of following KVA DG Sets including changing of oil filter, air filter (both inner and outer), coolant as per capacity, lubricant oil, cleaning of fuel injection parts, gasket with complete overhaulling of other part of engine i/c labour charges etc as required.a) 30 KVA |
| 44 | b) 40 KVA |
| 45 | Servicing and Repairing of alternator of DG set after dismantling it from engine and reassembling it with engine i/c thorough cleaning of each parts, replacement of worn out/ defected parts, changing of alternator copper winding oiling, greasing i/c to and fro & labour charges etc. as required. |
| 46 | Supply and fixing of battery charger suitable for DG set of minimum capacity of 40 KVA including cleaning of thimbles, connection, testing etc. as required. |
| 47 | Supply and installation of 12 Volt 100 AH heavy duty battery suitable for operation of minimum 40 KVA DG set i/c connection, testing etc as required. Please Enable Macros to View BoQ information |