| 1 | Supply, installation, testing and commissioning of 11 KV Outdoor Package Sub-Station consisting of 11/0.433 KV 3 phase, 50Hz, (As per Complete Item No. 1 of the DNIT) |
| 2 | Supply, installation, testing & commissioning of 3 phase, 50Hz, 11KV VCB 800 Amp. (INCOMER) indoor type for Indoor sub Stations. The VCB should be floor mounted trolley type horizontal isolation, horizontal draw out, (As per Complete Item No. 2 of the DNIT) |
| 3 | DSR item No.5.4 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 4 | DSR item No.5.11 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 5 | DSR item No.5.6 Earthingwithcopperearthplate600mmX600mmX3mm thick including accessories, and providing masonry enclosurewithcoverplatehaving locking arrangement and watering pipe of2.7 metre long etc. withcharcoal/ cokeand salt asrequired. |
| 6 | DSR item No.5.14 Providingandfixing25mmX5mmcopperstriponsurfaceor inrecessforconnectionsetc.asrequired. |
| 7 | DSR item No.23.4.1 supplyingandmakingindoorcableendterminationwithheat shrinkablejointingkitcompletewithallaccessoriesincluding lugs suitable for following size of 3 core, XLPE aluminium conductorcable of11 KVgradeasrequired: |
| 8 | 50/70sq.mm |
| 9 | DSR item No.15.15.3 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 10 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 11 | DSR item No.15.16.3 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 12 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 13 | Labour charges for horizontal boring 1 Mtr. below ground level including cost of 2 Nos. pit digging and refilling complete in all respect to the entire satisfaction of EIC. |
| 14 | S/E of 4 Nos. sand buckets of 10 Ltr. Capacity each made out of 24 Gauge G.I sheet. The buckets with sand shall be hanged on Suitable size of angle iron stand fabricated out of 1 ¼ x 1 ¼ x1/8” angle iron having hooks for hanging the buckets in two rows. The job includes the cost of painting with two coats of red paint of superior quality after one coat of primer on buckets and stands to complete the job up to the entire satisfaction of the Engineer–in–charge. |
| 15 | S/E medium size first aid box made of 16 gauge MS sheet of size 14’’x7’’x5’’ with 6 wound dressing 3 burns dressing 13 gms absorbent cotton wool one dressing scissor one bottle of sprit of sal volatile 1 tube of burn ointment. |
| 16 | Supply and erection of shock treatment chart written in Hindi and English and local language duly framed in wood frame with glass complete as required as per India Electricity Act. (Safety rules) |
| 17 | Supply and Erection of rubber/ insulating mate approx. size 6’x3’x12 mm thick |
| 18 | Supply and Erection of M.S. sheet danger notice plate at least 2 mm thick. |
| 19 | Supply and Erection of Fire Extinguishers ISI marked duly erected/ hung on wall with hooks including the cost of hooks with all material & labour required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of work. |
| 20 | CO2 type of 9 Kg capacity fire extinguishers conforming to IS. |
| 21 | Supply and erection of 11 KV/110 Volt Trivector meter suitable to monitor the parameters of electricity consumption as per the specification of Chandigarh Electrical Department (CED) of approved make i.e. L&T/ Secure only. (As per Complete Item No. 17 of the DNIT) |
| 22 | Supply, fabrication and erection of cubical type dust and vermin proof metering panel outdoor type IP65, free standing floor mounting, made out of 14 Gauge M.S. sheet with channel for base frame to accommodate 30/5A ratio of CT & PT dry type unit and set of Trivector meter including fixing of MS angle /flat where ever required. |
| 23 | Supply and erection of HT XLPE insulated armoured power cable stranded aluminium conductor sheathed with extruded semi-conducting compound cross linked polyethylene insulated laid up inner sheathed of extruded PVC single layer of galvanized steel flat strip armoured and PVC sheathed over all suitable for 11 KV., (As per Complete Item No. 19 of the DNIT) |
| 24 | Size 50 sq. mm 3 Core HT XLPE cable. |
| 25 | Supply and erection of HT XLPE insulated armoured power cable stranded aluminium conductor sheathed with extruded semi-conducting compound cross linked polyethylene insulated laid up inner sheathed of extruded PVC single layer of galvanized steel flat strip armoured and PVC sheathed over all suitable for 11 KV (Earthed) cable to IS: 7098 (Part-ii) 1985 with up to date amendments and laying in the open duct/ existing cable tray. (As per Complete Item No. 20 of the DNIT) |
| 26 | Size 50 sq. mm 3 Core HT XLPE cable. |
| 27 | Supply and laying of XLPE insulated PVC sheathed Aluminum conductor cable of 1.1 KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid on existing cable tray/ open duct. The job include the cost of making connections with suitable size of Aluminium Lugs/ thimbles, testing, commissioning etc. as required to complete the job to the entire satisfaction of Engineer In Charge. (As per Complete Item No. 21 of the DNIT) |
| 28 | Size 300 sq. mm 3.5 Core HT XLPE cable. |
| 29 | DSR item no. 4.1 Supplying and installaton following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. |
| 30 | 150mmwidthX50mmdepthX1.6mmthickness |
| 31 | 300mmwidthX50mmdepthX1.6mmthickness |
| 32 | Placement of existing CSS on the top of building at a height of approx. 50 ft. with the help of Hydraulic crane. The job includes the cost of all the petty material and labour required to complete the job to the entire satisfaction of E.I.C. |
| 33 | Supply & Erection of 11 KV 400 Amp. Triple pole outdoor vertical mounted G.O. switch single vertical blade 3 insulator per pole tilting type based with copper flexible connecting links and arching horns etc. with GI operating pipe. (As per Complete Item No. 24 of the DNIT) |
| 34 | FOUNDATION FOR 1 NO. 315 KVA PACKAGE SUBSTAION[Note: - The foundation shall be 200mm below the ground level and 450mm above the ground level and having provision for cable trench, grouting of PSS etc and projected at least 500mm from the size of enclosure all around with provision of steps as required., (As per Complete Item No. 25 of the DNIT) |
| 35 | 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 36 | Thermo-Mechanically Treated bars of grade Fe-500D or more |
| 37 | DSR Item No. 10.2 (Civil) Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete., (As per Complete Item No. 25 of the DNIT) |
| 38 | Supply and erection of PCC H Pole Structure without disc 11.00 Mtr. long. The pole shall be erected 2 Mtr. below ground level after digging the hole of proper size. The job includes the cost of MS channel of size 100 mm x 50 mm x 6 mm 6’6” long for making PCC H Pole structure. (As per Complete Item No. 26 of the DNIT) Please Enable Macros to View BoQ information |