| 1 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in deep and getting out in soft/loose soil for laying/taking out of underground cables and foundation of poles etc and getting out complete all as specified and directed. |
| 2 | Supply and laying dry river sand including spreading, levelling, punning for cushioning with a layer 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cable in trench/duct complete all as specified and as directed.Note : For measurement purpose only punned thickness (overall 18 cm) shall be considered for measurement and payment. |
| 3 | Returning, filling in trenches (soil), including spreading, levelling, watering and well ramming in not exceeding 25 cm thick complete all as specified and directed. |
| 4 | Removing of surplus excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed. |
| 5 | Supply and laying locally available, sub class 'B' Bricks (old size), laid flat and perpendicular to the direction of cable adjacent to each other, in trenches over the cable for protection complete all as specified and directed. |
| 6 | Taking out/down old existing LT cable 1100 Volts grade cables of size 35 to 300 Sqmm, 3.5 Core, XLPE, armoured, laid in trenches including bricks for protection and stacking, removal to store for reuse or credit complete all as specified and directed. |
| 7 | Supply and laying in trenches, LT underground cable, XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross sectional area 35 Sqmm, 3.5 core multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall complete all as specified and directed. |
| 8 | Supply and laying in trenches, LT underground cable, XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross sectional area 50 Sqmm, 3.5 core multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall complete all as specified and directed. |
| 9 | Supply and laying in trenches, LT underground cable, XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross sectional area 70 Sqmm, 3.5 core multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall complete all as specified and directed. |
| 10 | Supply and laying in trenches, LT underground cable, XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross sectional area 95 Sqmm, 3.5 core multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall complete all as specified and directed. |
| 11 | Supply and laying in trenches, LT underground cable, XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross sectional area 120 Sqmm, 3.5 core multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall complete all as specified and directed. |
| 12 | Supply and laying in trenches, LT underground cable, XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross sectional area 240 Sqmm, 3.5 core multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall complete all as specified and directed. |
| 13 | Supply and laying in trenches, LT underground cable, XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 Volts grade, cross sectional area 300 Sqmm, 3.5 core multistranded including cable connecting lugs, glands, jointing materials etc., laid in trenches, floors, roof, ducts and fixing using clamps, saddle for pole, wall complete all as specified and directed. |
| 14 | M & L for boring of holes under roof, pavement, hardstanding by trenchless technology and necessary machine with and including HDPE pipe of 75/100mm dia suitable for 0.4mpa working pressure complete all as specified and directed. |
| 15 | Supply and laying in repair GI tubing light grade 40 mm bore in trenches/fixing on pole/wall/crossing in drain etc. for protection of UG cable complete all as specified and directed. |
| 16 | Supply and laying in repair GI tubing light grade 50 mm bore in trenches/fixing on pole/wall/crossing in drain etc. for protection of UG cable complete all as specified and directed. |
| 17 | Supply and laying in repair GI tubing light grade 100 mm bore in trenches/fixing on pole/wall/crossing in drain etc. for protection of UG cable complete all as specified and directed. |
| 18 | Supply and fixing in repair MCCB 4 pole, 40 to 100 Amps 415 volts of breaking capacity 16 KA adjustable thermal and magnetic based type complete all as specified and directed. |
| 19 | Supply and fixing in repair MCCB 4 pole, 160 Amps 415 volts of breaking capacity 25 KA adjustable thermal and magnetic based type complete all as specified and directed. |
| 20 | Supply and fixing in repair MCCB 4 pole, 200 Amps 415 volts of breaking capacity 36 KA adjustable thermal and magnetic based type complete all as specified and directed. |
| 21 | Supply and fixing in repair MCCB 4 pole, 250 Amps 415 volts of breaking capacity 36 KA adjustable thermal and magnetic based type complete all as specified and directed. |
| 22 | Supply and fixing in repair MCCB 4 pole, 400 Amps 415 volts, 50 Hz of breaking capacity 36 KA adjustable thermal and magnetic based type complete all as specified and directed. |
| 23 | Supply and fixing in repair MCCB 4 pole, 630 Amps 415 volts, 50 Hz of breaking capacity 36 KA adjustable thermal and magnetic based type complete all as specified and directed. |
| 24 | M&L for Cable joining kit (straight through cold shrinkable) for 1100 V (Earthed) grade cable complete with jointing material and accessories suitable for XPLE armoured aluminium conductor cable of size 35 Sq. mm, 3.5 to 4 core including taking down unserviceable termination complete all as specified and directed. |
| 25 | M&L for Cable joining kit (straight through cold shrinkable) for 1100 V (Earthed) grade cable complete with jointing material and accessories suitable for XPLE armoured aluminium conductor cable of size 50-95 Sq. mm, 3.5 core including taking down unserviceable termination complete all as specified and directed. |
| 26 | M&L for Cable joining kit (straight through cold shrinkable) for 1100 V (Earthed) grade cable complete with jointing material and accessories suitable for XPLE armoured aluminium conductor cable of size 120-185 Sq. mm, 3.5 core including taking down unserviceable termination complete all as specified and directed. |
| 27 | M&L for Cable joining kit (straight through cold shrinkable) for 1100 V (Earthed) grade cable complete with jointing material and accessories suitable for XPLE armoured aluminium conductor cable of size 240-300 Sq. mm, 3.5 core including taking down unserviceable termination complete all as specified and directed. |
| 28 | Supply and installation steel tubular swaged pole complete with cast iron base plate find taper plunge bolt and nuts and screws all as specified type 410-SP-31, 9 mtr long complete with 2 coats of aluminium paint over a coats of red oxide primer including blue and white colour of alternatively of stripe upto 1.2 metre and writing pole No. complete all specified and directed. Please Enable Macros to View BoQ information |
| 29 | Supply and installation steel tubular swaged pole complete with cast iron base plate find taper plunge bolt and nuts and screws all as specified type 410-SP-31, 9 mtr long complete with 2 coats of aluminium paint over a coats of red oxide primer including blue and white colour of alternatively of stripe upto 1.2 metre and writing pole No. complete all specified and directed. Please Enable Macros to View BoQ information |