| 1 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik)having 3mm thikness with single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect. as per direction of E/I(PS No. 647) (Make - Bajaj/Transrail/Volmont) |
| 2 | S/Fixing of LED Street Light fitting having die cast Aluminium body and difuser with driver set suitable for 52 to 72 watt. Confirming to IP-66 and above protection. Complete in all respects. (PS No. 1422) Cat-AAA (Make -LT/Bajaj/Havells/ Crompton/Philips/Wipro) |
| 3 | Supply , Installation , testing and commissioning of standard 4.0 Mtr. High (above ground) hot dip galvanized (grading of galvenisation average 70 micron or better as per IS 2629 or equivalent) Octagonal pole, with stiffener, chain, allen bolt, foundation, single arm bracket, template, nut and bolts galvanized, factory finish base plate of size 200x200x12mm etc complete as required. The pole shall be made of 3mm thickness sheet with tolerance of +/- 5%. The column shall also be provided with flush door at the bottom with proper strengthening to the cutout of the door opening, a junction/loop box with heavy duty 3 phase , 32 Amp. connector with 16A DP MCB including all accessories complete as required derected by E/I.(Make - Bajaj/Transrail/Volmont) |
| 4 | Supply & fixing of 10 mtr GI Octagonal Pole of approved make (top dia 100 mm, Bottom dia 200 mm and base plate 16mm thick) having 3 mm thikness with Double arm bracket 1 Mtr length in 1:2:4 RCC foundation bolt including the cost of foundation, excavation & back filling and Required T&P completee in all respect.(PS No. 650) (Make - Bajaj/Transrail/Volmont) |
| 5 | Dismantling of pole/Street Light standard /strut embedded in cement concrete foundation etc. as required (DSR-2018/item no. 12.42 P-46) |
| 6 | S/Fixing of LED Street Light fitting having die cast Aluminium body and difuser with driver set suitable for 75 to 90 watt. Confirming to IP-66 and above protection. Complete in all respects. (PS No. 1423) Cat-AAA (LT/Bajaj/Havells/ Crompton/Philips/Wipro) |
| 7 | Supply and burring of Safe Earthing Electrode T-19 (Hot Dip Galvanized), Length up to 2000 mm, Outer pipe 50mm, inner pipe 25, terminal Dia 12mm, outer GI pipe of 16 swg and inner GI pipe of 12swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive and conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with food mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25x3 G.I. strip will be extra.) ps 725(A) |
| 8 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.(DSR-2018/item no. 5.18. P-27) |
| 9 | Supply and burrying of 75 mm Dia 3 Mtrs. Long Electrode casted with maintenance free, conductive concrete, non corrosive mixture ( Ultra low Resistive carbon 0.001 ohm/Mtr) in the ratio of 3:1:1 (marconite : cement : water) on M.S. Rod with hole (16 mm diameter X3 Mtrs ) will be vertically installed for earthing with 1Mtr G.I strip (25 mm X 2.5mm) connected with SS nut bolt. The earth electrode will be installed into the 100 mm pit up to 3000 mm depth. noraml soil will be used as backfill material. Make : As approved in U.P.P.W.D & C.P.R.I. Certified. (PS no 729(c) |
| 10 | laying of 90mm dia DWC(Double wall corrugated) pipe across the road by Trenchless method(Manual).AOR |
| 11 | Supplying and Laying of 6 sq. mm 2 core PVC Insulated Al. moued cable for street Light pole (as per RESPO-2018) annexure -3 pg. 17. |
| 12 | Taking out existing CC interlocking paver blocks from footpath/ central verge, including removal of rubbish etc., disposal of unserviceable material to the dumping ground, for which payment shall be made separately and stacking of serviceable material within 50 metre lead as per direction of Engineer-in-Charge.(AOR) |
| 13 | Laying old cement cocrete interlocking paver blocks of any design/ shape laid in required line, level, curvature, colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineerin-charge. (Old CC paver blocks shall be supplied by the department free of cost).(AOR) |
| 14 | Numbering of Pole/GI post / feeder pillar with combination of yellow and black colour paint etc. complte in all respects as per direction of E/I. (AOR) |
| 15 | Supplying and laying of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 Volts grade at a depth of 750 mm. below ground level over a cushion of 75 mm. thick sand alround and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. Clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respects. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. (KEI/ Havells/ Polycab make) (PS No 501) |
| 16 | (1) 16 Sq.mm. x 4 Core (PS No. 501) |
| 17 | 3) 70 sq mm 3.5 core (PS No 501) |
| 18 | S/F of Plain of pin type copper tin plated cable socket(lug) to the cable leads, insulating with tape and making connection etc. Complete in all respects as per direction for E/I (PS No. 504) |
| 19 | 4) 16 sq. mm |
| 20 | 3) 70 Sq.mm. |
| 21 | S/Laying of 90 mm dia (OD 90 mm & ID 76 mm nominal) size of (DWC) HDPE Pipes ISI marked along wigh all accessories like socket, bend, couplers etc. conforming to IS 14930, Part-II complete with filling and cutting, jointing etc. direct in ground ( 75 cm below ground level) including excavation and refilling the trench pat excluding sand cushioning and protective covering etc. Complete in all respects. Rex/Duraline/Time/CPE make. as per DSR 2018 item no. 14.16.2 page no. 49 |
| 22 | Supply and fixing of 40 Amp TPN capacity of automatic street light cubical control panel painted with anti corrosive alkali and acid proof paint crossing of time switch TSO 100 series with contractors, HRC fuse, isolating swtich metering instrument & instrument box with CTs etc. in case of TPN, Complete in all respects. as per PS No. 807D |
| 23 | Errection of metallic pole of following length in cement concrete 1:3:6 ( 1cement:3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required above 6.5 mtr Above and upto 8 mtr (DSR 2018 I. n. 11.3.1) |
| 24 | Demolishing cement concrete manually/ by mechanical means including disposal of material with in 50 Mtr. Lead as per direction of E/I. Nominal concrete 1:3:6 or richer mix(i/c equivalent design mix) (AOR) |
| 25 | Filling available excavated earth( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth consolidating each deposited layer by ramming & watering, lead upto 50 m and lift upto 1.5 m. (AOR). P- |
| 26 | Cutting road and making good the same including supply of extra quantities of materials i.e. aggregate, moorum screening, red bajri and labour required (AOR) |
| 27 | a) Bituminous Portion (AOR) (2265.0+18% gst) |
| 28 | b) Water Bound Macadam (AOR) (1400.0+18% gst) |
| 29 | Earth work in Excavation in by mechanical means (Hydraulic excavator) manual means over areas excaading 30 mtr in depth,1.50 mtr width as well as 10sqm on plan)including out and desposal of excavated earth ,load upto 50m and lift upto 1.5 m as directed by the Engineer incharge (AOR). |
| 30 | S/F of out door type 11KV fuse set Relco/Rama/Rastriya make with insulator Jai shree/BHEL make complete in all respects as per direction of E/I.(AOR) |
| 31 | Supply of Steel Tubular Pole 11 M long designated 410-SP-56 . complete in all respects as per direction of E/I. .(UPERC P-30) |
| 32 | Errection of metallic pole of following length in cement concrete 1:3:6 ( 1cement:3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required above 10.0 mtr and upto 12 mtr (DSR 2018 I. n. 11.3.4) |
| 33 | Supply and erection of overhead line with ACSR Conductor (Dog & Raccoon) poles / service bracket including binding etc. complete in all respects. P.S. No. 627 |
| 34 | Painting of the electric pole with 2 Coats of aluminium paint over red oxide primer complete in all respects. P.S. No. 634 |
| 35 | Supplying of channel iron 75mmx40mmx6mm(7.14 Kg Per mtr) pole top bracket/cross arm for single 11 kV overhead line conductor complete with 50mmx6mm flat iron clamp, bolts, nuts and washer including drilling holes for insulator pins bolts and nuts etc, and painting with primer and finish paint as required (DSR-2018 item no. 13.2 pg.44) |
| 36 | S/E of straight MS Channel 50x100 mm. (9.2 Kg/M) 2.60 M long as per design with required clamps made of M.S. flat of size 50x6 mm. with nut & bolts etc. as per direction of E/I. .((UPERC P-30) |
| 37 | Supplying and erection of 11kV pin insulator complete with large steel head G.I. Pin, nuts & washer etc. as required (DSR-2018 item no. 13.10 pg.46) |
| 38 | Supplying and erection of 11kV Disc insulator for 11kV overhead line with galvanised inculator fitting, ball and socket type and complete with galvanised strain clamp, bolts, nuts & washer etc. as required (DSR-2018 item no. 13.11 pg.45) |
| 39 | S/F of 11 KV TPMO Relco/Rama/Azad make 9 Nos. insulator of Jai shree/BHEL/ Rama/ Rastriya make complete in all respects as per direction of E/I.(UPERC page no. 58) |
| 40 | S/E Testing & Commissioning of 63 KVA Al. wound outdoor type Transformer as per ISS. Complete in all respects Make : AZAD/P.M./Kanohar/LD Power/Paramix as per direction of E/I..(RESPO page no. 51) Please Enable Macros to View BoQ information |