| 1 | Providing and making steel pole collar with cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) of specified size and shape including form work, plastering if required, curing etc. as required. (Volume of pipe/pole not to be deducted)(Electrical DSR-18/Ite. No. 11.5 pg.37) |
| 2 | Supply and making straight through joint with cast resin compound including ferrules and other joints material for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade as required |
| 3 | a) 3.5x70 sq. mm ((Electrical DSR-18/Ite. No. 9.3.20 pg.35) |
| 4 | a) 2x25 sq. mm ((Electrical DSR-18/Item. No. 9.3.2 pg.34) |
| 5 | a) 2x16 sq. mm ((Electrical DSR-18/Item. No. 9.3.1 pg.34) |
| 6 | Dismantling of pole/Street Light standard /strut embedded in cement concrete foundation etc. as required (Electrical DSR-2018/item no. 12.42 P-46) |
| 7 | Supply of Steel Tubular Pole 11 M long designated 410-SP-56 . complete in all respects as per direction of E/I. .(UPERC P-30) |
| 8 | Errection of metallic pole of following length in cement concrete 1:3:6 ( 1cement:3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required above 10.0 mtr and upto 12 mtr (Electrical DSR 2018 I. n. 11.3.4 ) |
| 9 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30cm in depth. 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth, lead upto 50m and lift upto 1.5m. The contractor has detect different utilities like sewer line, water supply line, electric cable, Telephone cable, Gas pipe line etc. using utility detecting machine before start of excavatiob and shall start excavation only after permission of Engineer in charge. All kind of soil. (AOR) |
| 10 | Filling available excavated earth( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth consolidating each deposited layer by ramming & watering, lead upto 50 m and lift upto 1.5 m. (AOR) |
| 11 | Supplying and laying of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 Volts grade at a depth of 750 mm. below ground level over a cushion of 75 mm. thick sand alround and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. Clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respects. the armouring of the cable shall be properly connected with the earth conductor by clamps etc. (Polycab, KEI, Grandlay, Gloster, Havell's, make) |
| 12 | (a) 16 Sq.mm. x 2 Core (PS No. 501) |
| 13 | (b) 16 Sq.mm. x 4 Core (PS No. 501) |
| 14 | (C) 25 Sq.mm. x 2 Core (AOR) |
| 15 | (D ) 50 Sq.mm. x 3.5 Core (PS No. 501) |
| 16 | (E ) 70 Sq.mm. x 3.5 Core (PS No. 501) |
| 17 | S/F of Palm or Pin type copper tin plated cable socket (lugs) to the cable lead insulation with tape and making connections complete as per direction of E/I. P.S. No. 504 |
| 18 | a)- 16 sq. mm |
| 19 | b)- 25 sq. mm |
| 20 | c)- 35 sq. mm |
| 21 | d)- 50 sq. mm |
| 22 | e)- 70 sq. mm |
| 23 | S/E of overhead line with ACSR conductor on steel tubular poles incl. compression joint, laying stringing and binding etc. as PS No. 627 |
| 24 | Supply and buring of safe earthing electrode T-19 (Hot dip galvanized), length up to 3000mm outer type 50mm, inner pipe, 25mm terminal dia 12mm, outer GI pipe of 16 SWG and inner GI pipe of 12 SWG with Hot Dip galvanization up to 100 micron filled with crystalline conductive mixture(CCM) having anti corrosive & conductive property with 50 Kgs activated soil (BFC) capable of reducing the soil resistivity with good micture of retaining capicity along with 30cm square C.I. frame with hinged cover & masonry husing (from electrode terminal to switch board, cost of 25x3 G.I. strip will be extra as per PS No. 725B |
| 25 | S/Laying of 51 mm dia (OD 63 mm & ID 51 mm nominal) size of (DWC) HDPE Pipes ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part-II complete with filling and cutting, jointing etc. direct in ground ( 75 cm below ground level) including excavation and refilling the trench pat excluding sand cushioning and protective covering etc. Complete in all respects. Rex/Duraline/ Time/CPE make. as per DSR 2018 item no. 14.16.2 page no. 49 |
| 26 | S/Laying of 90 mm dia (OD 90 mm & ID 76 mm nominal) size of (DWC) HDPE Pipes ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part-II complete with filling and cutting, jointing etc. direct in ground ( 75 cm below ground level) including excavation and refilling the trench pat excluding sand cushioning and protective covering etc. Complete in all respects. Rex/Duraline/ Time/CPE make. as per DSR 2018 item no. 14.16.2 page no. 49 |
| 27 | Supply and making Straight Through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required. (Electrial DSR-2018, Item No. 10.6) |
| 28 | (a) 120 Sqmm ( Item No. 10.6.2 P-38) |
| 29 | (b) 240 Sqmm ( Item No. 10.6.3 P-38) |
| 30 | Supply and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11KV grade as required. (Electrial DSR-2018, Item No. 10.5) |
| 31 | (a) 120 Sqmm ( Item No. 10.5.2 P-37) |
| 32 | (b) 240 Sqmm ( Item No. 10.5.3 P-37) |
| 33 | S/F of jointing of following sizes outdoor/indoor type 11 KV jointing kit heat Shrinkable type for 11 KV Cable including cost of all material, labour, T&P etc. for proper completion of the E/I. (Raychem/Denson Make) uperc Pg-29 |
| 34 | 185 Sq.mm. |
| 35 | Supply of following type high conductivity aluminium strand compacted circular conductor XLPE armoured 11 KV Cable neutral earthed system confirming to IS 7098-Part-II (1985) with latest amendment at a depth of 900 mm. below ground level over a cushion of 100 mm. thick sand around and protect with brick on sides and top of cable shall be properly connecting with the earth conductor by clamps etc. with the cost of all material, labour, T&P etc. required for proper completion of the work. (CCI/ Gloster/ ICL/ Grandley/Havells/Diacab/KEI make)(Approved by CEO) |
| 36 | i) 185 Sq.mm. 3 Core E-48 |
| 37 | Laying of One number PVC insulated and PVC sheathed/ XLPE power cable of 11KV grade of following size in the existing RCC/ HUME/ METAL/HDPE pipe as required.(DSR elect 2018 Item.N. 8.3.2/P31) Above 120 Sqmm and upto 400 Sqmm |
| 38 | S/F of sintex type junction box model no. IIGSJB 2817 of size 280x170x115mm with hinges and locking arrangment & MS clamp of 50x6mm flat, complete in all respects including 2 no. G.I pipe 1.5\\" dia having 1.0 meter length each and chuck nut for cable connection etc. as per direction of E/I. (AOR) |
| 39 | Supply and fixing Pole bus bar support connector 4 way with backsheet i/c connection of cable complete in all respect. |
| 40 | S/F of 11 KV TPMO Relco/Rama/Azad make 9 Nos. insulator of Jai shree/BHEL/ Rama/ Rastriya make complete in all respects as per direction of E/I.(UPERC cost data book 2019/P-48) |
| 41 | S/F of out door type 11KV fuse set Relco/Rama/Rastriya make with insulator Jai shree/BHEL make complete in all respects as per direction of E/I..(AOR) |
| 42 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (DSR-2018/Item No. 1.17.2) (1.5S Q. MM 2 CORE) |
| 43 | Supply and laying of 25mm x 3mm G.I. strip from earth electrode directly in the ground as required complete in all respect.(PS no 716/ P-138) |
| 44 | Electrician Per day as applicable in authority labour supply. ( 1 Nos. Electrician) |
| 45 | Helper Per day as applicable in authority labour supply. (1 Nos. Helper) |
| 46 | Demolishing cement concrete manually/ by mechanical means including disposal of material with in 50 Mtr. Lead as per direction of E/I. Nominal concrete 1:3:6 or richer mix(i/c equivalent design mix) (AOR) |
| 47 | Providing and laying in position cement concrete 1:3:6 (1 cement : 2 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc including form work etc as required. (DSR Elect. 2018/14.9/48) |
| 48 | Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. (DSR 2018 item no. 12.34 page no. 42) |
| 49 | Location and pin pointing of LT cable fault exposling the same in the underground LT cable including digging of trench upto the depth of the cable. Cutting the faulty cable and sealing of the faulty cable, by making experts technical staff. Complete in all respects as per direction of Engineer in charge (AOR) |
| 50 | Location and pin pointing of 11 KV HT cable fault exposling the same in the underground 11KV HT cable including digging of trench upto the depth of the cable. Cutting the faulty cable and sealing of the faulty cable by providing fault location machine with operator (Cable fault locator) Complete in all respects as per direction of Engineer in charge (AOR) |
| 51 | Supply and fixing of SS Rope Wire 16Mtr/30 Mtr High mast. Complete in all respects as per directiion of E/I. (AOR) |
| 52 | Supply and fixing of Winch Machine assembly suitable for 30 Mtr High mast. Complete in all respects as per directiion of E/I. |
| 53 | Dismantling of 30 Mtr Height High Mast with the help of Crane/Hydra and required labour T&P etc. Complete in all respect . As per direction of E/I. |
| 54 | Fixing of 30 Mtr Height High Mast with the help of Crane/Hydra and required labour T&P etc. Complete in all respect on existing foundation. Complete in all respects As per direction of E/I. |
| 55 | Repair of 63 KVA Transformer incl. changing of HV & LV Coil, Bushing, Gasket &fresh Transformer oil without returning of old & unsearciable material. Complete in all respects as per direction of E/I (AOR) |
| 56 | Dis/Re-Fixing of 63/100 KVA Transformer |
| 57 | Supplying and erection of 11kV pin insulator complete with large steel head G.I. Pin, nuts & washer etc. as required (DSR-2018 item no. 13.10 pg.46) |
| 58 | Supplying and erection of 11kV Disc insulator for 11kV overhead line with galvanised inculator fitting, ball and socket type and complete with galvanised strain clamp, bolts, nuts & washer etc. as required (DSR-2018 item no. 13.11 pg.45) |
| 59 | Dismantling of 16 Mtr Height High Mast with the help of Crane/Hydra and required labour T&P etc. Complete in all respect . As per direction of E/I. |
| 60 | Fixing of 16 Mtr Height High Mast with the help of Crane/Hydra and required labour T&P etc. Complete in all respect on existing foundation. Complete in all respects As per direction of E/I. |
| 61 | Repairing of 11KV fuse wire/Jumper i/c supply and fixing of required size conductor, fuse wire of 11KV Line/DP structure of Transformer by takinng shutdown from UPPCL Department with all safety instruments like-safety belt, Gloves, shoes and other necessary items complete including all taxes. Please Enable Macros to View BoQ information |