| 1 | SITC FOR STRENGHTNING / PERMANENT RESTORATION OF POWER INFRASTRUCTURE DAMAGED DUE TO FLOODS IN THE YEAR 2025 UNDER SASCI PART-I (DISASTAR) |
| 2 | SITC OF HT Line |
| 3 | S.T Pole 8 mtrs long (410-SP15) |
| 4 | Galvanisied V cross-arm with top bracket including clamp |
| 5 | Galvanisied Channel cross-arm including clamp and braces. |
| 6 | 30 mm2 ACSR Weasel Conductor |
| 7 | PG Clamps for 30mm sq ACSR Weasel Conductor |
| 8 | 50 mm2 ACSR Rabbit Conductor |
| 9 | 11 kv Pin insulators with pins (10KN) |
| 10 | 11 kv Disc insulators with fittings (45 KN) |
| 11 | Earthing Complete by G.I. Pipe 40mm or G.I. Rod 20mm 2.5mtr long through G.I. Strip |
| 12 | Cemment Bottoming 1:2:4 mix as per REC standard 0.5 cubic mtr per poles |
| 13 | Galvansied Stay set with 50x8mm stay clamp, guy insulator (02nos.) anchor plate (200x200x6mm) nut bolts, 2nos. Turn bukles, 1.8m long 16mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 14 | Almunium Jointing Sleeves |
| 15 | Al. Painting |
| 16 | Red Oxide |
| 17 | Anti Climbing Device with clamps |
| 18 | Danger Plates with clamps |
| 19 | Galvansied Nuts and Bolts of sorts |
| 20 | SUPPLY OF MATERIAL |
| 21 | 25KVA Transformer Level II , 11/0.433KV,3-Phase Distribution Transformer with Bimetallic Terminal Connectors Almunium Wound with LV Cable Box having detachable Aluminium Gland plate. |
| 22 | 63KVA Transformer Level II , 11/0.433KV,3-Phase Distribution Transformer with Bimetallic Terminal Connectors ,Almunium Wound and with LV Cable Box having detachable Aluminium Gland plate. |
| 23 | 100KVA Transformer Level II , 11/0.433KV,3-Phase Distribution Transformer with Bimetallic Terminal Connectors ,Almunium Wound and with LV Cable Box having detachable Aluminium Gland plate. |
| 24 | 250KVA Transformer Level II , 11/0.433KV,3-Phase Distribution Transformer with Bimetallic Terminal Connectors ,Copper Wound and with LV Cable Box having detachable Aluminium Gland plate. |
| 25 | PVC insulated stranded conductor FRLS type 1.1kv Grade Cable 185 mm sq with Thimbles |
| 26 | 30 mm2 ACSR Weasel Conductor |
| 27 | S.T Pole 8 mtrs long (410-SP15) |
| 28 | PCC Pole 8 mtrs long (WL-200KG) |
| 29 | 11 kv Pin insulators with pins (10KN) |
| 30 | Galvansied Nuts and Bolts of sorts |
| 31 | SITC OF EARTHING FOR DISTURBUTION TRANSFORMERS |
| 32 | Earthing of Sub-station ,excavation of earth pit of dia 650mm and depth 3000mm,installation of earthing pipe of 40mm nominal bore and 4mm wall thickness and length 2.5 mtr.long as per IS 1239.GI strip for neutrl earthing of size 25 mm*3 mm for connection of transformer body ,G.O set and lightening arrestor as per IS 2629/85,GI nuts and bolts ,refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.(Specification as per cost data) |
| 33 | SITC OF LT Line |
| 34 | S.T Pole 8 mtrs long (410-SP15) |
| 35 | 30 mm2 ACSR Weasel Conductor |
| 36 | 50 mm2 ACSR Rabbit Conductor |
| 37 | Shakle Insulator (16KN) |
| 38 | Mukky Clamps |
| 39 | Cemment Bottoming 1:2:4 mix as per REC standard 0.45 cubic mtr per poles |
| 40 | Galvansied Stay set with 50x8mm stay clamp, guy insulator (02nos.) anchor plate (200x200x6mm) nut bolts, 2nos. Turn bukles, 1.80m long 16mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 41 | Anti Climbing Device with clamps |
| 42 | Red Oxide |
| 43 | Al. Painting |
| 44 | LT line spacer |
| 45 | Danger Plate |
| 46 | Nuts and Bolts of sorts Please Enable Macros to View BoQ information |