| 1 | Item Rate BoQ BoQ_Ver4.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER,CHENNAI SER. PAGE NO: Name of Work: SPECIAL REPAIR / REPLACEMNT OF OLD 02 / 04 POLE STRUCTURES TO VCB'S AT MD ACCN AT ARMY AREA UNDER GE AVADI Contract No: CWE/AVD/ OF 2026-2027 Name of the Bidder/ Bidding Firm / Company : SCHEDULE 'A'(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of items Item Code / Make Quantity Unit Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT With Taxes TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | Earthwork excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth and getting out in soft / loose soil for laying cables / pipes / erection of poles etc complete all as specified |
| 3 | Removing excavated material (soil) to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified |
| 4 | Returning filling in soil including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified |
| 5 | M&L for fine seived excavated dry soil laid to the required width of trench at bottom and top of cable as cushioning to cable complete all as specified. Note :- Thickness shall be measured after punning |
| 6 | Supply and laying reinforced precast concrete cable cover, class HV, type 1, flat of size 300 mm x 180 mm x 40 mm complete all as specified |
| 7 | Supply and laying HT UG XLPE insulated with multistranded aluminium conductor armoured with galvanised steel wire / taps 11000 volts grade cable of size 3 core, 95 Sqmm conforming to IS laid in trenches/poles/wall etc complete all as specified and as directed. |
| 8 | S & F outdoor termination heat shrink type joint for 11 KV (Earthed) grade underground HT XLPE / armoured heavy duty cable with aluminium conductor of size 3 core, 95 Sqmm including jointing materials and accessories including labour complete as specified and as directed. |
| 9 | S & F straight through cold shrink type joint for 11 KV(Earthed) grade underground .HT XLPE / armoured heavy duty cable with aluminium conductor of size 3 core, 95 Sqmm including jointing materials and accessories including labour complete as specified and as directed. |
| 10 | Supply, Install, testing and commissioning of RMU panel Outdoor type (01 No Incoming LBS & 02 Nos out going VCB)11KV, 630A, 26.3kA load break switch -01 No, 11KV 1250A 26.3kA drawout type Vaccum Circuit breaker with 230AC Motor & 110V dc closing/ opening shunt, aux contact- 6NO + 6NC - 02 Nos Ring Main unit Motorised operated RMU with PT Chamber, Auxillary transformer, battery & battery charger complete all as specified and directe with following accessories:- Make :ABB/ Schneider/ Siemns (a) Potential Transformer Fixed type of Epoxy resin cast 3PH of Ratio 11KV//110V Core 15VA CL0.2 accy - 2 Nos (b) Current Transformer Epoxy resin cast, Ratio 100-50/5-5A, Core1: 0.2S/5VA per phase for Metering, Core2: 5P20/15VA for protection - 06 Nos (c) Relays: 3-OC, 1- EF relay - 2 Nos, Master tripping Relay -02 Nos (d) Meters- Ammeter with selector switch -02 Nos, Voltmeter with selector switch -02 Nos, Provision of TOD Meter -02 Nos, (e) Indications/ Switches/ Annunciator: R/Y/B/ ON/ OFF/ TRIP/ Trip ckt healthy/ Spring Charged Indication Lamp - 14Nos, TNC Switch - 02 Nos, Space heater/ Illumination lamp- 03 Nos, Test Terminal block - 02 Nos |
| 11 | (f) Copper Bus bars 50x10mm mounted on epoxy resin cast insulators - 03 Nos, Door switch actuated CFL for panel illumination- 03 Nos, LV control fuses/ Power & control terminals as required- 03 Nos (g) Tripping Coil for tripping the circuit breaker in fault condition, Local 'PUSH TO TRIP' mechanism for emergency trip, Right Angle boots (Non touch proof type) (h) The combined unit shall consist of standard mechanical interlocks to avoid unsafe operation, Mimic diagram on front panel, complete with status indicators (ON-OFF-EARTH), provision for padlocking for Open, Close, Earth position in correct sequence,The earth bus bar shall boot of copper flat and provided inside the cable chamber throughout the switch gear including necessary PCC foundation as recommended by OEM, Cable doors shall be Arc proof and interlocked with respective switches, door with locking arrangement to prevent unauthorized access complete all as specified and directed. |
| 12 | Supply, Install, testing and commissioning of VCB panel outdoor type 11KV 1250A 26.3kA drawout type Vaccum Circuit breaker with 230AC Motor & 110V DC closing/ opening shunt, aux contact- 6NO + 6NC - 01 Nos with PT Chamber, Auxillary transformer, battery & battery charger complete all as specified and directed with following accessories:- Make :ABB/Schneider/Siemns (a) Current Transformer Epoxy resin cast, MAKE: AMITY, Ratio 100-50/5-5A, Core1: 1/15VA per phase for Metering, Core2: 5P10/15VA for protection - 03 Nos (b) Potential Transformer of Epoxy resin cast 3PH, Ratio 11KV//110V, 100VA CL 1 accy - 01 Nos (c) Relays: 3-OC, 1- EF relay with high set - 01 Nos (d) Master tripping Relay - 01 Nos, Antipumping relay-01Nos (e) Multifunction meter -01 Nos (f) Indications/ Switches/ Annunciator: R/Y/B/ ON/ OFF/ TRIP/ Trip ckt healthy/ Spring Charged Indication Lamp - 10Nos, TNC Switch - 01Nos, Thermostat controlled by Anti condensation Space Heater with switch, 01 Nos, Door switch actuated CFL for panel illumination -01Nos, MCB for AC/DC control circuits -02 Nos, Disconnecting/ Non disconnecting type control terminals - 01Nos, Powerpack- 01 Nos (g) Aluminium bus bar type (h) Tripping Coil for tripping the circuit breaker in fault condition, Local 'PUSH TO TRIP' mechanism for emergency trip, Right Angle boots (Non touch proof type) (j) The earth bus bar shall boot of aluminium flat and provided inside the cable chamber throughout the switch gear including necessary PCC foundation as recommended by OEM, Cable doors shall be Arc proof and interlocked with respective switches, door with locking arrangement to prevent unauthorized access complete all as specified and directed. |
| 13 | M&L for drilling/ making bore hole under the road in any type of soil through trenchless technology by HDD (horizontal direction drilling method) including necessary machinery as required,perparing and settin up the plant and equipment , perparing new pipe/cable laying work like excavation shoring/ strutting etc drilling, stringing reaming pulling back the new work on the path alignment proper disposal of drilling fluid and the ground penetrating radar survey to protec existing utilities at the pipe/cable installation location restoration of site agter completion all inclusive as per and STT IS No 2.3 2.2 2.2 second edition 2008 code of practice of trenchless technology suitting indian condition for making horizontal bore size of 75mm dia suitable for HDPE pipe insertion under the road crossing hard standing including HDPE pipe of size 75 mm nominal dia with suitable minimum wall thickness to any depth complete all as specified and directed. Note : (a) Necessary infrastructure such as tools, plants,machinery ,equipments etc as required for boring shall be arranged by the Contractor and quoted rate shall deemed to be included for the same.(b) HDPE pipe 75mm dia shall be measured and paid separately under relevant items . |
| 14 | M&L for 75 mm dia HDPE pipe PN-10 with fittings laid in trenches / wall for protection of underground cable at road crossing complete all as specified and directed. |
| 15 | M&L for earthling complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground earth pit not less than 2.25 m deep below normal ground level with the top edge of earth plate at a depth of not less than 1.5 m below normal ground level connected to GI earth strip 32x6 mm dia by means of bolts, nuts, check nuts and washers made out of GI and GI earth strip protected by 40 mm bore light grade GI pipe,watering arrangement by provision of 20mm dia GI pipe medium grade with cast iron funnel,provision of test point and connected to main control board all as shown in electrical plate No 3 of SSR Part I including necessary earth work and excavation in any type of soil and PCC 1 : 2 : 4 type B - 1 in chamber and 40 mm thick RCC 1:2:4 type B - 1 cover slab with 6 mm dia mild steel bars at 100 mm centre to centre both ways with 6 mm dia M S hooks complete all as specified and as directed. |
| 16 | Dismantling old unserviceable cross arms of mild steel channel or angle sections etc from poles and taken on credit complete all as specified and as directed. |
| 17 | Dismantling old unserviceable electrical poles of any type /size/ height including demolition of PCC foundation of any description and removing from site complete all as specified and as directed. |
| 18 | Dismantling old unserviceable GOD device complete with all aaccessories complete all as specified and as directed. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |