| 1 | Supply of the following materials :- |
| 2 | 09 mtr long PCC pole |
| 3 | ACSR Rabbit (6/1/3.35mm) |
| 4 | PVC Cable 120 sq.mm |
| 5 | XLPE Cable (HT) 3Cx50 sq.mm |
| 6 | Porcelain Cut out 200 Amp |
| 7 | 11KV Polymer Pin Insulator |
| 8 | GI Stay Set HT |
| 9 | Stranded stay wire 7-4 mm |
| 10 | MS Channel (75x40x40x6 mm ) |
| 11 | MS Channel (100x50x50x6 mm) |
| 12 | GI Bracket clamp 50 x6 mm |
| 13 | GI Stay clamp 50x50x6mm |
| 14 | 11 KV GOS (3-Phase) (Porcelin type) |
| 15 | 11 KV Drop out Switch (Porcelin) |
| 16 | Aluminium Lugs 120mm sq |
| 17 | 1/2 dia PVC pipe for earthing |
| 18 | HDPE Pipe Pe-100 Grade PN 8 (SDR 17) 110 mm dia, Wall thickness: minimum- 6.5mm, maximum-7.3mm |
| 19 | 9 KV, 5 KA Lightening Arrestor. |
| 20 | 11 KV HT 4 way outdoor type feeder pillar- Kiosk with necessary fittings and structures complete as per requirement |
| 21 | 16 Sq.mm PVC Cable |
| 22 | Aluminium Lugs 70mm sq |
| 23 | 8 SWG GI Wire |
| 24 | Erection of the following Materials:- |
| 25 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Trench Size:Width-350mm, Hieght- 1200mm/Sand(couhioning) :Hieght- 250mm, Width- 350mm/Protection: Double layer BricksUpto 120 sq. mm |
| 26 | Manually digging /driIIing horizontally or diagonali direction for road crossing / Water supply line/ Telcomunication line/Gas Pipe line etc.in/c Laying of 64 to 200mm dia GI pipe direct into the earth at a depth of minimum 1100mm below the ground surface with out effecting the existing road including excavation earth for entry pit as per site condition and direction of Engineering In Charge. |
| 27 | Erection of Stay set direct in earth complete with 19mm x 1800 mm long stay rod, anchor plate of size 300 x 300 x 8 mm, thimble, turn buckle, 7/3.15 mm dia G.I Standed stay wire and stain insulator etc. with Supply of M.S.Clamp,Nuts & Bolts etc. as required. and making complete in all respect |
| 28 | Erection of M.S.Angle Cross-Arm,2.8 Mtr.Long 65 x65 x 6 mm ( Excluding the cost of BackClamp, Nuts & Bolts) |
| 29 | Erection of M.S.Channel Cross-Arm,1.3 to 2.8 Mtr. Long75 x40 x 40 x 6 mm ( Excluding the cost of Back Clamp, Nuts & Bolts) |
| 30 | Erection of M.S.Channel Cross-Arm,0.6 to 2.8 Mtr. Long100 x50 x 50 x 6 mm ( Excluding the cost of Back Clamp, Nuts & Bolts) |
| 31 | Erection of 11KV Pin insulator along with Pin. |
| 32 | Earthing with G.I pipe 2.5mtr. Long and 40mm dia, in/c excavation, refilling with alternate layer of salt & Charcoal as per drawing (excluding supply of G.I Pipe, Salt & Charcoal, Gi wire, nuts&boIts etc. as reqd) |
| 33 | Laying of 8 SWG GI wire at 300mm below the ground level for earthing of Sub-Station equipments from the earth electrode |
| 34 | Erection of DANGER PLATE on OH lines (11KV/415VoIts) |
| 35 | Laying & Stringing of 1KM (Single Conductor) ACSR 6/1/3.35 mm dia RABBIT including hoisting & KM binding etc. Complete as required. |
| 36 | Erection of 9KV,5KA single pole metal oxide gapless type LA, including necessary connection complete as per technical specification |
| 37 | Erection of 11KV DOF unit set of three Nos including necessary connection complete as per technical specification. (Excluding the cost of back clamp, Nuts & Bolts) |
| 38 | Erection of 11KV 200 Amp. GOS unit set of three Nos including necessary connection complete as per technical specification.(Excluding the cost of back cIamp,Nuts & Bolts) |
| 39 | Installation/Positioning of 11/0.430KV,3-Phase 63 KVA of Distribution Transformer on Pole with necessary connections & fitting fixing of all allied accessories components as required for making complete in all respect for energizing |
| 40 | Erection of 9.0 mtrs long PCC Pole at any kind of soil, including excavation of earth, refilling the pit with soil upto the ground level, ramming and making complete in all respect. |
| 41 | Erection of 4 Way 630 A HT Kiosk/ 11 KV outdoor Type Feeder pillar made of MS Sheet complete with Aluminium Insulator etc as required system and painting MS Angle(50x50x6 10 SWG Busbar HT provided with locking to be filled in structure off and concreting mach leg of kosk in the 1:24 cement 2 er sand 4 hama Bricks 42 mm) & MS fat/40x6 mm) tem code 40 apgregate with 20 mm nominal se, ncludag certering shadering & Disposal of excess excavated soil |
| 42 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/HDPE/ HUME/ METAL pipe as required Upto 120 sq. mm |
| 43 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of all size in the GI Pipe/HDPE for riser including tieup of Pipe with pole by the help MS Flat Clamp (excluding cost of Clamp and Nut & Bolts) as required Up to 400 sq. mm |
| 44 | Supplying and Making Indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as requiredUp to 150sqmm |
| 45 | Supplying and Making Outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as requiredUp to 150sqmm |
| 46 | Fixing of cut out(Set of 3nos)on wooden plank (preferably korai wood) |
| 47 | Supply of M.S.Nuts & Bolt i/c Washer of assorted size ISI Marked machine made |
| 48 | Providing of Pre-cast cement concretecable identification route marker (1 cement: 2 coarse sand 4 graded stone aggregate 6mm nominal size) reinforced with 1.6 mm dia mild steel wire including centring and shuttering, roughening cleaning, fixing and finishing in cement mortar 1:3 (1cement : 3 fine sand) etc. complete, excluding the plastering of jambs, sills and soffits as per design, drawing and specification of TSECL. The marker snail be embossed |
| 49 | Supply of 2.5 mtr. Long, 40mm dia G.I.Pipe (Make: TATA/ JINDAL) |
| 50 | Supply of 60Kg Salt & 55Kg Charcoal ( For 1 Pit). |
| 51 | Carriage of . of 9.0 mtrs long PCC Poles by Mechanical Transport from the Electrical Sub-Divisional Site Store to working site Vis-a-vis, including loading, unloading and stacking as required a) Upto the lead range 25 KM i) For maximum 8 (eight) poles From MMD Store to Sub Division Store |
| 52 | Carriage of line materials from Agartala store AD Nagar to Kamalpur ESD store Yard |
| 53 | Carriage of 11/0.430, 3-Phase 63 KVA by Mechanical Transport trom the Site/Store/Worshop to working site Vis-a-vis including loading, unloading and placing on base, as requireda) Upto the lead range 25KM From MMD Storeto Sub Division Store |
| 54 | Carriage of materials such as Cable,AAC, AAAC, ACSR, G.I,Wire,Cross-Arm,Stay Set,lnsulators etc., by Mechanical Transport from the ESD Site Store to working site Vis-a-vis, including loading, unloading and stacking as required, upto the lead of 25KM & 50KM.a) Upto the lead range 25KM From MMD Store to Sub Division Store |
| 55 | Sub Station Fancing one job Please Enable Macros to View BoQ information |