| 1 | DSR Item No.1.8 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulatedcopper conductor single core cable in surface/ recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 2 | Group C |
| 3 | DSR Item No.1.23 Supplying and fixing following piano type switch/socket on the existing switch box/ cover including connections etc. as required. |
| 4 | Telephone socket outlet |
| 5 | DSR item no.8.7LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output .LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness >0.50 mm) |
| 6 | 22 watt |
| 7 | DSR item no.8.13 LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -5 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K/6500°K(As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 8 | 45 watt |
| 9 | DSR 8.10 LED Batten light (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , Flicker free (flicker should be below 5 %), life time (LED, Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).Powder Coated CRCA Sheet Body (Thickness > 0.50 mm)18- 22 Watt |
| 10 | DSR Item no. 8.16LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt) Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -5 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement deg, suitable tilt able fitting, life time (LED, Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size andCCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). |
| 11 | 100 watt |
| 12 | DSR 9.1 Brush Less Direct Current (BLDC) fan with remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (prefreably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistancemore than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req.1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 13 | Supply and Erection of B.L Holder on the existing junction box/ wooden block including making the connection etc as required. The job includes the all labour and petty material charges required to complete the job to the entire satisfaction of E.I.C. of work. Approved makes: Anchor/ Goldmedal/ Lauritz Knudsen / Havells make only. |
| 14 | S/E of LED Bulk Head Luminaries weather proof frosted light with PMMA/ PC reflector and silicon gasket to be installed on surface. The LED fitting should have minimum system Lumen output minimum 1000 Lumen at 100 lm/ watt (minimum) and the driver of the fitting should be workable on 140-260 Volt. The colour temperature of LED should be minimum 5000 degree Kelvin. The fitting should be of Philips/ Bajaj/ Wipro/ Havells/ Jaquar/ Crompton/ Panasonic/ Surya/ LT/ Trilux make only. The fitting should be of IP-65/66. The LED should have a life of 50000 burning Hours. The fitting should have THD<15% and power factor 0.9 or above. The job includes the cost of testing, commissioning and making connection with copper wire from adjacent light point, other petty material and labour etc. as required to complete the same to the entire satisfaction of Engineer In Charge. |
| 15 | S/E of MS bracket (F shape) made from 40mmx40mmx5mm thick angle iron to be installed on existing parapet/ wall with the help of suitable size of nuts/ bolts etc for erection of flood light/ street light fittings. the job includes cost of painting of bracket with superior quality of paint and other all petty material etc as required to complete the job. |
| 16 | Supply and Laying of PVC insulated and PVC sheathed Aluminum conductor cable of 1.1 KV grade as per IS 7098 (Part-I) 1988 (amended upto date) of the following size to be laid on wall surface as required at site to the entire satisfaction of the Engineer-in-Charge. The job included labour charges of laying the cable and making connections etc. |
| 17 | Size 10 Sq.mm 4 core PVC Al. Unarmoured conductor cable. |
| 18 | Supply and Erection of Cement Collar and Jn. Box at the base of the pole with the detailed specification as given below.: |
| 19 | Jn. Box Construction: |
| 20 | Supply & fixing of OEM made Junction box IP-66/67 made out of Polycarbonate with Glass fiber reinforced of size 205x255x112 (mm) (minimum) with 5 Nos. OEM made connectors/ terminal blocks. The Jn. Box and connectors/ terminal blocks should be supplied by OEM. The terminal blocks/ connectors should be of Hensel / Wago /Elmax / Siemens make only and junction box shall be of Hensel make KF 2525 G or its equivalent Clipsal / Legrand / Rittal / Schneider / ABB make only. The Junction box shall be fire retardant and self extinguishing. The gasket material shall be polyurethane and the gasket shall be internally embedded. The job includes all labour and petty material required to complete the job to the entire satisfaction of the Engineer in Charge of work. |
| 21 | Cement Collar: |
| 22 | The box shall be enclosed in a Cement Collar made from Cement Concrete 1:2:4 with outside dia 16” as required at site. |
| 23 | The collar shall be embedded in the ground upto 6” shall stand 9” above ground shall have height equal to PVC Junction box and 6” top over the box. |
| 24 | The collar shall be provided with 2 Nos. DWC Pipes of 50mm dia 45cm long each to facilitate the entry of cables in the Jn. Box. |
| 25 | The collar shall be plastered, properly finished and painted with 2 coats of exterior apex of superior quality. |
| 26 | The item includes other petty material to complete the job including new thimbles & making connections. |
| 27 | The job includes all labour and petty material inclusive of putty required to complete the job to the entire satisfaction of the Engineer In Charge of the work. |
| 28 | Supply and Erection of sheet metal cubical pedestal of suitable dimensions made from 50x50x6mm thick MS angle iron frame on the base of pedestal, covered with 16 gauge MS sheet duly welded on five sides and front side hinged complete with locking arrangement 4 nos. switchgear supporting members each of MS flat 50mmx6mm thick of suitable length duly welded. The cubical pedestal shall have 4 Nos. legs made out from 50x50x6 mm thick MS angle iron each 60 cm long including painting bonding to the existing earth etc. the same shall be erected in the 1:2:4 cement concrete platform of suitable dimensions 15cm high from ground level and 45 cm thick. The cubical pedestal shall be 15cm from the top of cement concrete platform. The shutter of the cubicle pedestal should be of ‘U’ shape supported from internal side for additional strength with 16 GMS sheet. |
| 29 | Cubical size 900 mm x 600 mm x 350 mm deep. |
| 30 | DSR item no.2.3Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 31 | 12 way , Double door |
| 32 | DSR No. 1.17Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 33 | 3x 1.5 sq. mm |
| 34 | 3x 2.5 sq. mm |
| 35 | 3x 4 sq. mm |
| 36 | DSR No.1.21Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 37 | 25 mm |
| 38 | DSR No.1.29Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recesswith suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A piano type switch, connections, painting etc. as required. |
| 39 | DSR No.1.30Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recesswith suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 &connections, painting etc. as required. 15/16 A socket outlet and 15/16 A piano type switch, |
| 40 | DSR No.1.33Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 41 | DSR No.2.4Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 42 | 6 way (4 + 18), Double door |
| 43 | DSR item no.2.10Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 44 | Single pole |
| 45 | Triple pole and neutral |
| 46 | Supply & erection of Exhaust Fan (heavy duty motor with copper wound metallic body) following size complete with motor, metallic blades, double ball bearing with minimum power consumption, rigid frame with rubber mounting for silent operation, epoxy powder coating along with metallic louver to be installed in the existing opening including cost of making the hole to suit the size of above fan making good the damage, Carriage Charges connection, testing, commissioning etc. as required to complete the job to the entire satisfaction of EIC. |
| 47 | Size 15 inches (380mm) Sweep, 900 RPM Heavy Duty Exhaust fan (Single Phase) with louver of Havells (Turbo Force SP)/ Orient (Industrial Heavy Duty)/ Usha (Turbo HDEF)/ Crompton (EXHD380-6-1)/ Bajaj (Supreme Plus) make only. |
| 48 | DSR item No. 5.1Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt) as required. |
| 49 | DSR item no.5.7Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required. |
| 50 | DSR item no.5.12Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 51 | DSR Item No 15.16Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
| 52 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 53 | Supply and Laying of following XLPE insulated and PVC sheathed, armored, aluminum conductor cable of 1.1KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid in existing trench/ DWC/RCC/HUME pipe as required at site. The job include the cost of making connections with suitable size of Al. Lugs/ thimbles, testing, commissioning etc. as required to the entire satisfaction of Engineer In Charge. |
| 54 | Size 16 Sq.mm 4 core PVC Al. Arm. Cond. Cable |
| 55 | S/E of 5 mtr. long G.I. Pipe pole made out of 2.5” dia G.I. Pipe pole (5 mtr.) of B-Class ISI marked G.I. Pipe. The pole shall be erected 1mtr. below ground level in 6” internal dia readymade RCC muff. The gap between the pole and the muff shall be filled with cement concrete 1:2:4. The job includes the cost of fabrication, Welding, Grinding, making hole for entry of wire, labour, all petty material, carriage etc. required to complete the job to the entire satisfaction of the E.I.C. The cost includes all labour and material including fabrication charges of Pole & carriage to the site of work. The G.I. pipe should B-Class ISI marked Jindal / Hindustan make only. |
| 56 | Supply and fixing of G.I box of size 200 mm x 150 mm suitable for accommodate the following accessories along with piano type and Bakelite sheet for switches in recess / surface etc as required for Computer Point with 4 Nos. 5/6 Amp. Piano type switch and 4 Nos. 3 pin 5/6 Amp. Piano type socket outlet. The job includes the cost of making interconnections with suitable copper wire, painting of box with approved paint and other petty material required to complete the job to the entire satisfaction of Engineer-in-Charge at site. Please Enable Macros to View BoQ information |