Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Schedule \\"A\\" Part – I to Schedule \\"A\\" Part – XX:NOTE: Schedule \\"A\\" Part – I to Part – XX are prepriced by MES. Bidders shall insert their Lumpsum amount in Green coloured field under Column - 6 only |
| 2 | Lumpsum price worked out by the contractor for \\"Buildings & Structures\\", as listed in Schedule \\"A\\" Part – I . |
| 3 | Lumpsum price worked out by the contractor for \\"Site Clearance / Earthwork/ Excavation\\", as listed in Schedule \\"A\\" Part – II . |
| 4 | Lumpsum price worked out by the contractor for \\"Pile foundation\\", as listed in Schedule \\"A\\" Part – III |
| 5 | Lumpsum price worked out by the contractor for \\"Internal Electrification\\", as listed in Schedule \\"A\\" Part – IV . |
| 6 | Lumpsum price worked out by the contractor for \\"Internal Water Supply\\", as listed in Schedule \\"A\\" Part – V . |
| 7 | Lumpsum price worked out by the contractor for \\"Sewage Disposal B/R\\", as listed in Schedule \\"A\\" Part – VI . |
| 8 | Lumpsum price worked out by the contractor for \\"External Water Supply\\", as listed in Schedule \\"A\\" Part – VII |
| 9 | Lumpsum price worked out by the contractor for \\"External Electrification\\", as listed in Schedule \\"A\\" Part – VIII |
| 10 | Lumpsum price worked out by the contractor for Roads/Paths/Hard Standing\\", as listed in Schedule \\"A\\" Part – IX . |
| 11 | Lumpsum price worked out by the contractor for \\"Area drainage\\", as listed in Schedule \\"A\\" Part – X |
| 12 | Lumpsum price worked out by the contractor for \\"Chain link fencing/ Wall/ Gate\\", as listed in Schedule \\"A\\" Part – XI |
| 13 | Lumpsum price worked out by the contractor for \\"Fire fighting and fire alarm system\\", as listed in Schedule \\"A\\" Part – XII |
| 14 | Lumpsum price worked out by the contractor for \\"Lightning Protection\\", as listed in Schedule \\"A\\" Part – XIII |
| 15 | Lumpsum price worked out by the contractor for \\"PVC Conduit\\", as listed in Schedule \\"A\\" Part – XIV |
| 16 | Lumpsum price worked out by the contractor for \\"Solar water heater\\", as listed in Schedule \\"A\\" Part – XV |
| 17 | Lumpsum price worked out by the contractor for \\"Central Air conditioning \\", as listed in Schedule \\"A\\" Part – XVI . |
| 18 | Lumpsum price worked out by the contractor for \\"Arboriculture\\", as listed in Schedule \\"A\\" Part – XVII |
| 19 | Lumpsum price worked out by the contractor for \\"Cooling Appliances\\", as listed in Schedule \\"A\\" Part – XVIII |
| 20 | Lumpsum price worked out by the contractor for \\"Mechanical laundry\\", as listed in Schedule \\"A\\" Part – XIX |
| 21 | Lumpsum price worked out by the contractor for \\"Retaining wall \\", as listed in Schedule \\"A\\" Part – XX |
| 22 | Schedule \\"A\\" Part - XXI [Miscellaneous Items] |
| 23 | Internal Electrification |
| 24 | Point Wiring complete with 1100 Volts, FRLSH Grade, 1.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor Cable, confirming to IS - 694 drawn through and including heavy duty PVC Conduit, 20 mm dia including all accessories concealed in Walls / Roofs / Floors / Ceiling etc. and Pressed Metal Flush Box made out of 2mm thick MS Sheet of suitable size and 3 mm thick Hylam Sheet top cover for fixing switches, fittings, regulators etc concealed in walls, including 1100 Volts, FRLSH Grade, 1.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor cable as earth continuity conductor with colour coding and connecting to Earth Dolly for One Light / Fan Point / Bell Point controlled by One Switch complete all as specified. |
| 25 | All as per Serial Item No. 21 above but One 3 Pin Switch Socket Outlet 5 Amps on Independent Board complete all as specified. |
| 26 | All as per Serial Item No. 21 above but One 3 Pin Switch Socket Outlet 5 Amps on same Board complete all as specified. |
| 27 | All as per item No.21 here-in-before but controlled by two two way switch complete all as specefied and directed. |
| 28 | All as per Serial Item No. 21 above but one 3 Pin Switch Socket Outlet 16 Amps on independent board, with 1100 Volts, FRLSH grade, 4.0 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor Cable confirming to IS - 694 and including 1100 Volts, FRLSH grade, 4.0 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multistranded Copper Conductor Cable as Earth Continuity Conductor. |
| 29 | Supply and fixing of ceiling fan complete with blades, down rod and other accessories, AC 230 Volts, 1200 mm sweep, min air delivary 210 CFM with service value 6.00, BEE, 5 star rated with brushless direct current motor [BLDC] including connecting with 1.0 Sqmm, 2 core copper conductor from ceiling rose complete all as specified and as directed. |
| 30 | Supply and fixing exhaust fan, 250mm sweep, plastic body, heavy duty with louvers, AC single phase, 230 volts, connection with 1.0 sqmm copper conductor flexible wire from ceiling rose including making necessary opening and making good the disturbed surface complete all as specified and as directed. |
| 31 | Supply and fixing exhaust fan, 300 mm sweep, metallic body, heavy duty , AC single phase, 230 volts , 5 star rating, connection with 1.0 sqmm copper conductor flexible wire from ceiling rose including making necessary opening and making good the disturbed surface complete all as specified and as directed. |
| 32 | S&F energy efficient LED Tube light fitting with tube 5W or nearest size, 240 Volts, 50 Hz, surface mounted, decorative ultra slim square profile LED light fixture with extruded polycorbonate environmental friendly, energy efficient ready to use pack of complete mounting brackets including connecting up with 1.0 Sqmm 3 core flexible copper conductor cable complete all as specified as directed |
| 33 | S&F energy efficient LED Tube light fitting with tube 10W or nearest size, 240 Volts, 50 Hz, surface mounted, decorative ultra slim square profile LED light fixture with extruded polycorbonate environmental friendly, energy efficient ready to use pack of complete mounting brackets including connecting up with 1.0 Sqmm 3 core flexible copper conductor cable complete all as specified as directed |
| 34 | S&F energy efficient LED Tube light fitting with tube 18/20W or nearest size, 240 Volts, 50 Hz, surface mounted, decorative ultra slim square profile LED light fixture with extruded polycorbonate environmental friendly, energy efficient ready to use pack of complete mounting brackets including connecting up with 1.0 Sqmm 3 core flexible copper conductor cable complete all as specified as directed |
| 35 | S & F energy efficient LED security light fitting with tube 30 watts new generatiion energy saving & environmental friendly long life, made up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having top opening separate driver compartment with IP66 protection pre-wired and connecting up with with 1.0 Sqmm copper conductor cable upto connector including 1.5 metre long GI tubing light grade bracket of 32 mm dia bend to shape for fixing on wall/ pole with suitable MS bracket nuts, bolts etc., complete all as specified and directed. |
| 36 | Supply, Install, testing and commissioning of AC three phase static electronic meter of accuracy class 1.0, 240 Volts, 50 Hz, with backlite LCD display of rating 10-60 Amps six month history with the following specifications complete all as specified and directed.[a] AC Three Phase Four wire, tamper proof, Static Meter of Class 1.0, 415 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with incuilt 865-867 MHz Radio Frequency communication facility with self healing Mesh network with default and on demand display, biling data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry.[b] Meter should support the following data: 30 Min instantaneous data for voltage, current, power factor, power, cumulative energy and frequency, 30 load survey data for energy, monthly billing survey for cumulative energy and Max Demand.[c] Meter should have connect/ disconnect functionally operable from prepaid billing software.[d] The meter should support open communication protocolDLMS with the software MAKE: Secure, L&T Schneider |
| 37 | M & L for sub-main wiring with 4.0 sqmm nominal area two single core PVC insulated unshethed multi-stranded FRLS copper conductor cable including one 4.0 sqmm PVC insulated unshethed multi-stranded copper conductor cable for earth wire drawn through 20 mm dia PVC conduit complete all as specified and as directed.Note :(i) Two run of 4.0 Sqmm + one run of 4.0 Sqmm as a earth wire cable + one run of PVC conduit shall be measured as an one Unit. |
| 38 | Supply and fix polycarbonate meter box as per IS 14772 with IP -55 weather proof and temperature proof,fire retardant suitable for three phase smart pre-paid meter viewing glass, concealed hinge and earth bolt plugged including cable glands for incoming and outgoing cables and locking arrangement for top cover of the box without affecting communication complete all as specified and directed. |
| 39 | M & L for sub-main wiring with 10.0 sqmm nominal area four single core PVC insulated unshethed multi-stranded FRLS copper conductor cable including one 10.0 sqmm PVC insulated unshethed multi-stranded copper conductor cable for earth wire drawn through PVC conduit of suitable size complete all as specified and as directed.Note :(i) Four run of 10.0 Sqmm + one run of 10.0 Sqmm as a earth wire cable + one run of PVC conduit shall be measured as an one Unit. |
| 40 | S & F MCCB DB, vertical double door, TPN, 4 way, sheet steel, with 200 Amps rated bus bar, 415 Volts, 50 Hz, IP : 43 protection,concealed in walls, including provision of MCCB FP 40 Amps, 10 KA as incommer and outgoing circuits, filling the empty with blanks, making good the disturbed area as per existing surface complete all as specified and as directed. |
| 41 | S & F MCB DB, vertical double door, TPN, 6 way, sheet steel, , 415 Volts, 50 Hz, IP : 43 protection,concealed in walls, including provision for fixing RCBO, FP as incommer and outgoing circuits, MCB SP/TP filling the empty with blanks, making good the disturbed area as per existing surface complete all as specified and as directed. |
| 42 | Supply and fixing wall mounted fan, 450mm sweep, AC single phase, 230 volts, connection with 1.0 sqmm copper conductor flexible wire from ceiling rose, 5 star rating complete all as specified and as directed. |
| 43 | Earthing complete with Galvanised steel earth plate electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of plate not less than 1.50 m below normal ground level connected to 25 X 4mm GI Strip [Earth Lead] and GI pipe 50 mm, Medium Grade for earthing lead protection to the extent of maximum 7.5m, Earth Plate Electrode surrounded by 150mm thick packed layers of Charcoal and Common Salt filled in alternate layers, connected to the plate by means of GI Bolts & Nuts complete all as per Electrical plate No. 3 of SSR Part - I, connected to panel / DB including testing on completion including main earthing, Charcoal, Common Salt, PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm Angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. complete all as specified and as directed. |
| 44 | Earthing complete with Galvanised steel earth plate electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of plate not less than 1.50 m below normal ground level connected to 32 X 6mm GI Strip [Earth Lead] and GI pipe 50 mm, Medium Grade for earthing lead protection to the extent of maximum 7.5m, Earth Plate Electrode surrounded by 150mm thick packed layers of Charcoal and Common Salt filled in alternate layers, connected to the plate by means of GI Bolts & Nuts complete all as per Electrical plate No. 3 of SSR Part - I, connected to panel / DB including testing on completion including main earthing, Charcoal, Common Salt, PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm Angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. complete all as specified and as directed. |
| 45 | Internal Water Supply |
| 46 | S & F 15 mm dia Bib taps, long body, fancy type, chromium plated screwed down, screwed for iron pipe or for brass ferrule and fixed complete all as specified and as directed. |
| 47 | S & F 15 mm dia Bib taps, long body, fancy type, chromium plated cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed complete all as specified and as directed. |
| 48 | S & F CP mixer for mixing hot and cold water fancy type, chromium plated, screwed down for pipe, with two outlets going (one for bib tap and other for shower) complete all as specified and as directed. |
| 49 | S & F 15 mm dia bib tap two way, fancy type screwed down and fixed suitable for 16 mm outer dia CPVC pipe complete all as specified and as directed.Note: The maximum flow rate will be 03 LPM |
| 50 | S & F 15 mm health faucet, chromium plated, fancy type with steel flexible complete suitable for 16 mm outer dia CPVC pipe complete all as specified and as directed. |
| 51 | S & F CP mixer swan neck for mixing hot and cold water fancy type, chromium plated, fancy type screwed down for pipe, with two outlets going (one for hot and one for cold) kitchen complete all as specified and as directed. |
| 52 | External water supply |
| 53 | Material and labour for trial borewells by DTH/Rotary driling method upto 100 mtrs for each borewell in any type of soil/hard rock/soft rock inculding trial bore dia 300 mm complete all as specified and directed. |
| 54 | Material and labour Development of trial bore by reaming 300 mm to 400 mm but depth upto 30 mtrs or onward below ground level complete all as specified and directed.NOTE:- (a) Quantity under serial No 48 & 49 have been account for four (04) Nos trial bore. (b) The rate quoted by the contractor shall be deemed to include for transportation of suitable truck mounted drilling with DTH & ODEX attachment alongwith necessary accessories and T&P and site clearance for setting of machinery, data collected from electical logging etc., (d) Contractor should take into cognizance the conditions as INS chilka (Restricted area) while quoting the rates.(e) Rate quoted shall be deemed to include the soil collection sample of every 3 mtrs deep for lab testing. |
| 55 | Supply, assembling, lowering and levelling 200 mm nominal bore UPVC ASTM SCD 120 ISI marked casing blank pipe having wall thickness as per ASTM and jointing with proper Cement cealing in random length of 3 to 6 mtr, including necessary fitting i.e., upto a depth of 30 metre from below ground level complete all as specified and directed by Engineer-in- Charge. |
| 56 | Supply, assembling, lowering and levelling 150 mm nominal bore UPVC ASTM SCD 120 ISI marked casing blank pipe having wall thickness as per ASTM and jointing with proper Cement cealing in random length of 3 to 6 mtr, including necessary fitting i.e., depth from 30 to 400 metre from below ground level complete all as specified and directed by Engineer-in- Charge. |
| 57 | Supply, assembling, lowering 150mm nominal bore UPVC ASTM Sch 80 ISI marked slotted pipe conforming to IS-4270-1992 with slot of suitable size and numbers as per location of intermediate aquifers including jointing with Cement cealing in random length of 3 to 6 mtr screwed and socketed in random length of 3 to 6 mtr, including necessary fitting i.e complete all as specified and directed. |
| 58 | Supply and packing 'P' (Pea) gravels of size 4 to 10mm all around the linear assy up to the entire depth of bore hole upto ground level including all necessary cement works complete all as specified and directed by Engineer-in-Charge. |
| 59 | Foundation of size 100 x 100 x 100 cm at ground level for holding tubewell made of plain cement concrete 1:2:4 type B-2 (using 40mm graded aggregates) complete all as specified and directed by Engineer-in-charge Note: Rate quoted is deemed to include necessary Earth work, excavation, returning filling, removal etc., |
| 60 | Supply, install, levelling, testing and commissioning of submerssible pumping set with outer dia of pump not exceeding 200mm having capacity 15 HP, 3 phase, 440 Volts at minimum 60 mtr Head complete all as specified and directed. |
| 61 | Devlopment of borewell by means of compressor and after pumping by pump 25% extra capacity, complete all as specified and directed. |
| 62 | S&F Submerssible cable 3 core, 10 sqmm, PVC sheathed 1100 Volts grade with copper conductor including making connections and fixing complete all as specified and directed. |
| 63 | Yield test for the borewell by continuously pumping for 4 hours to determine safe pumping yield complete all as specified and directed. |
| 64 | Supply and fix in position mild steel cap made of MS plate 6mm thick with an internal threading and locking arrangement having opening for column pipe and submersible cable, for housing pipe of 200mm dia complete all as specified and directed by Engineer-in-Charge |
| 65 | Sample strata box made out of 20mm thick veneered particle board and 12mm thick plywood with 25mm x 25mm aluminium angle 2mm thick base overall length 1200mm x 750mm x 100mm with front glass sheet sliding type cover with aluminium frame all around with 2 Nos key holes plates of size 40mm x 25mm and 3mm thick complete showing name of tube well location and strata chart of ground data showing different types of strata and selection of casing pipe complete all as specified and directed. |
| 66 | S&F UPVC reducer (8 inch to 6 inch ) , for 04 Nos of borewell complete all as specified and directed by Engr-in-Charge |
| 67 | S&F Bail plug for 04 Nos ( min 3 mts long) of borewell complete all as specified and directed. |
| 68 | S&F 100 mm dia Strainer 'Y' type conforming to IS complete complete all as specified and directed. |
| 69 | Borewell logging geologist charges to measure the physical and chemical properties of the surrounding geological formation and soil before digging the borewell complete all as specified and directed. |
| 70 | S & F for saline sealing per borewell all as specified |
| 71 | Water analysis test regarding Physical, Chemical and microbiological examination and potability test report from authorised Govt approved agency for the following parameter :- (a) Colour (Hazen), Odour, Taste, Turbidity (NTU), PH value. (b) Total Hardness as CaCo3 (Mg/L), Iron (Mg/L), Chloride as Cl (Mg/L), Flouride as F (Mg/L), Coliforms (MPN/100ml), Sulphate as SO3 (Mg/L). (c) Total alkalinity (Mg/L), Calcium as Ca (Mg/L), Magnesium as Mg (Mg/L), Nitrate as NO3 (Mg/L), Total dissolved solids (Mg/L). (d) Cadmium as Cd (Mg/L) Copper as Cu (Mg/L) , Zinc as Zn (Mg/L), Chromium as Cr (Mg/L) , Lead as Pb (Mg/L), Maganese as Mn (Mg/L). (e) Mercury as Hg (Mg/L), Aluminium as Al (Mg/L), Arsenic as As (Mg/L). (f) Any other mandatory tests as per world Health Organisation.(g) Total suspended solids, (h) Total dissolved solids (j) Microbiological tests. |
| 72 | Supply, install, testing and commissioning of 15 HP, Three Phase 13.2- 20 A Automatic Star Delta Submersible Pump Controller accomadate in SS sheet box type enclosure IP54 and adequate space for cable terminations, Inclusive of cable gland box complete all as specified and directed. |
| 73 | Supply , install, testing and commissioning of indoor meter box panel board , CPRI Approved ,IP 42 made out of CRCA sheet 2 mm thick vermin proof factory made with 40 x 40 x6 mm MS angle/channel duly painted with two coats of synthetic enamel powder coated paint over a coat of metal primer with bus bar chamber comprising of high conductivity copper bus bar of capacity 200 Amps three phase and half the capacity for neutral including internal wiring with 6 sqmm copper conductor (FRLS) including PCC foundatoin suitable to accommodate the following as specified and as directed.:(a) MCCB 415 V, 125 Amps, 4 pole with electronic release Electronic Earth leakage module with over load , short circuit and earth fault protection with earth module breaking capacity 16 KA- 01 Nos.(b)Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting with LED indication lamp complete and all as per standard pratice - 1 Job(C) Panel mounted automatic star delta starter 20 HP-2 Nos (d) MCB TP 63 A , 'C' curve ,Breaking capacity of 10kA -5 Nos Note :-(i) All MCCBs / instruments / MCBs /Bus Bar shall be housed in a separate housing with on- off latches in the housing and Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting with LED indication lamp for each outgoing complete and all as per Eng in charge. |
| 74 | Supply , install, testing and commissioning of indoor meter box panel board , CPRI Approved ,IP 42 made out of CRCA sheet 2 mm thick vermin proof factory made with 40 x 40 x6 mm MS angle/channel duly painted with two coats of synthetic enamel powder coated paint over a coat of metal primer with bus bar chamber comrising of high conductivity copper bus bar of capacity 400 Amps three phase and half the capacity for neutral including internal wiring with 6 sqmm copper conductor (FRLS) including PCC foundatoin suitable to accommodate and including the following as specified and as directed.:(a) MCCB 415 V,200 A, 4 pole with electronic release Electronic Earth leakage module with over load , short circuit and earth fault protection with earth module breaking capacity 25 KA- 01 Nos.(b) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting with LED indication lamp complete and all as per standard pratice ---1 Job(c) MCCB 415 V,100 A, 4 pole with electronic release Electronic Earth leakage module with over load , short circuit and earth fault protection with earth module breaking capacity 16 KA- 03 Nos (c) MCCB 415 V,40 A, 4 pole with electronic release Electronic Earth leakage module with over load , short circuit and earth fault protection with earth module breaking capacity 16 KA- 05 Nos (d) MCB TP 32 A , 'C' curve ,Breaking capacity of 10kA -2 Nos (e) Panel mounted automatic star delta starter 50 HP-2 Nos Note :- (i) All MCCBs / instruments / MCBs /Bus Bar shall be housed in a separate housing with on- off latches in the housing and Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting with LED indication lamp for each outgoing complete and all as per Eng in charge. |
| 75 | Material and Labour for laying of Ductile Iron pipe with spigot and socket end centrifugally cast(spun) class K-9 of 250 mm dia pipe conforming to IS-8329 including testing and commissioning all as specified and as directed. |
| 76 | Material and Labour for laying of Ductile Iron pipe with spigot and socket end centrifugally cast(spun) class K-9 of 200 mm dia pipe conforming to IS-8329 including testing and commissioning all as specified and as directed. |
| 77 | Material and Labour for laying of Ductile Iron pipe with spigot and socket end centrifugally cast(spun) class K-9 of 100 mm dia pipe conforming to IS-8329 including testing and commissioning all as specified and as directed. |
| 78 | Material and Labour for laying of Ductile Iron pipe with spigot and socket end centrifugally cast(spun) class K-9 of 200 mm dia pipe conforming to IS-8329 including testing and commissioning all as specified and as directed. |
| 79 | S & F sluice valve of 250 mm dia size with cast iron body, PN 1.6, with both ends flanged, drilled at both the ends, conforming to IS-780, having SS spindle with iron wheel at top complete with nuts and bolt, washers, 3 mm rubber gasket 02 Nos complete all as specified and as directed. |
| 80 | S & F sluice valve of 250 mm dia size [Non raising type] Non-return with cast iron body, PN 1.6, with both ends flanged, drilled at both the ends, conforming to IS-780, having SS spindle with iron wheel at top complete with nuts and bolt, washers, 3 mm rubber gasket 02 Nos complete all as specified and as directed. |
| 81 | Supply and fix Cast Iron Air Valves with single air Outlets, conforming to IS 14845 of size 80 mm dia bore and fixing up in ductile Iron Water supply mains of size 200/250 mm dia complete all as specified and as directed. |
| 82 | Supply and fix foot valve of size 100 mm Complete all as specified and as directed. |
| 83 | Supply and fix foot valve of size 200 mm Complete all as specified and as directed. |
| 84 | supply ,install, testing and commisioning of Electrical Motor Driven Horizontal Centrifugal multistage type Pump of Capacity 29 LPS (104.4 M3/HR), 70 mtr head, 37 KW, (50 HP) motor, Cast Iron Body, CI impeller, Carbon steel shaft (C-40), fitted with Gland Packing, base frame, coupling, coupling guard etc., complete set,. complete all as specified and as directed.Make : CAT No. RKB 125/27, 3 Stage (MOC-01) of KIRLOSKAR or its equivalent make as approved by GE |
| 85 | M&L for 110x 95 mm DWC with UV stabilized high density polyethylene pipes for road crossing of cable or for cable protection laid in trenches or above ground surface complete all as specified and directed. Make- Prince/Dutron/National |
| 86 | M&L for Cutting the road / hard standing for laying of pipes in trenches of size 900x600mm and making good with PCC 1 :2 :4 Type B1 complete and painting with black paint , if necessary, to match with existing bituminous road colour complete all as specified and as directed. |
| 87 | M & L for masonry valve chamber of size 900 X 900 X 900 mm [interanl dimensions] comprising of 50mm thick PCC for valve including excavation and earth work in any type of soil and 200 mm thick PCC 1:4:8 type D2 foundation, brick work in CM (1:6) plastring internal surface 15 mm tick in CM (1:4) PCC (1:3:6) type B1 couping 50 x50x6 mm angle iron 3 mm thick MS plate cover complete with locking arrangement painting steel and iron surface with two coat of synthetic enamel paint over a coat of zinc chrome primer all as specified and as directed. |
| 88 | Supply and install open well Monoblock pump set 15 HP, three Phase, 415 Volts RPM 30000, 50 Hz, minimum head 60 mtr, Body and impeller: cast iron , Shaft: SS and Sealing: Mechanical sealing complete as directed |
| 89 | External Electrification |
| 90 | Supply, Install, testing & commissioning of Factory Made 11 kV, 630 Amps, 21kA for 3 Seconds, AFLR, SF6 Insulated, Motorised, Outdoor 6 Way RMU Consisting of 2 Nos VCB as Incomer and 4 Nos of VCBs as Outgoing complete all specified and as directed and shall comprise of the following: The make of Vacuum Interrupter & VCB of same make as the Ring Main unit.Note: The RMU should be manufactured at OEM factory only. No other mode of manufacturing is accepted. [A] RMU shall be 11 KV, 630 Amps, 21 kA for 3 Seconds, Internal Arc 21kA/1Sec, AFLR, SF6 Insulated, Motorized, Outdoor, 6 Way RMU, Left side Extensible, Right Side Metering Unit, SACADA compatable Overload and earth fault protection Relay (Ashidha / CSPDR) with Air Insulated Bus Connected Metering unit (Type +VVVVVV+M), Type tested in line with latest IEC Standards, suitable for operations at a height up to 1000 Meters above sea level and at 40ºC Ambient Temperature, |
| 91 | Switchgear and Busbar shall all be contained in a Stainless Steel Enclosure [2.5MM thickness SS 304], nominal operating gas pressure 1.3 BAR @20 Deg C, RMU Tank shall provide Full Insulation and Switchgear shall be insensitive to the environment with Degree of Protection of IP67, Switchgear Operating Mechanism shall have an IP2X Protection and Cable Chamber shall have IP3X Protection, Outer Enclosure shall be IP 54 type tested, Painting (FRONT COVER RMU: RAL7035 & (FOR MIMIC RAL7043)) & ENCLOSURE: RAL7035 & (TOP COVER & BASE STAND IN RAL 7043)). The unit shall be internal arc proof 21kA for 1 se with AFLR clasification. tested and totally safe for human beings. The gas release & personnel safety from internal arc shall not depend on plinth design. The release of gas to be from the top of the unit, so that, even if the person is operating the unit, opening the cover, & there are personnels near the sides of the RMU/plinth, top release will ensure their safety. The hot gas release, in case of an internal arc, in no case should be from any side or bottom of the unit, as the same is unsafe for the operating personnel/pedestrian or general public. Bidder shall provide type test report to prove compliance to the Internal Arc fault IAC-AFLR as per IEC 62271-200. Internal arc testing shall be done with enclosure door in open condition, with switching devices in operation mode as per specified standard. |
| 92 | [c] Vacuum Circuit Breaker [VCB] Each shall be comprising of the following: [i] 11 KV, 630 Amps, 21 kA/ 3s, 3 Pole Manual/ Motorised VCB with 3 pole manual disconnector and 3 pole manual earth switch, manual/ motorized Spring Assisted Mechanism and Series Trip Coil – 1 No. [ii] Self Powered Relay with O/C, S/C, E/F Protection – 1 No[iii] CT Ratio 200-100/1A, Class - 1.0, 2.5VA for Metering and CT Ratio 200-100/1A, Class 5P10, 2.5 VA for Protection – 1 Set each[iv] Live Cable Indicator with indications at the Front and Three Inlets to check the Synchronization of Phases – 1 No[v] Cable Termination Bushing suitable for up to 1 Run, 3 Core, 185 Sq.mm, XLPE Cable – 1 Set[vi] Cable Termination Cover Boots [Push on type] – 1 Set[D] Air Insulated Bus Connected Metering Unit comprising the following: – 1 Set[i] Air Insulated Enclosure with necessary Bus Connection – 1 No[ii] PT 11KV / RT 3 / 110V / RT3, 25 VA, Class-1.0 – 1 Set[iii] Voltmeter with Selector Switch – 1 No[iv] R / Y / B Indicating Lamps – 1 Set[v] 11 KV / 230V AC, Class 1, 500VA Control Transformer – 1 No[vi] Battery and Battery Charger, 12 Ah, [I/P-230V AC, O/P - 24V DC]–1 No |
| 93 | Note:[a] An operator situated in front, lateral and rear [A-FLR 21 kA – 1 Sec, Downwards Exhaust, for Tank as well as Cable Compartment] of the RMU Switch board during an internal fault shall not be exposed to the effects of Arcing. Internal Arc Type Test Report for IAC AFLR 21 kA for 1 Sec for both Tank & Cable Box shall be for minimum as per OEM standards.[b] All operations shall of the RMU shall be as per OEM standards. [c] Copy of the Type Test reports as per latest IEC shall be submitted along with drawings for approvals. |
| 94 | Supply, install, testing and commissioning of LT indoor type panel board of suitable size, pedestal mounted, CPRI approved totally enclosed, dust and vermin proof, front side openable, type IP 54 protection made of CRCA sheet outer and inner shell 2.00 mm thick and 50x50x6 mm frame of size as per IS and having proper locking arrangement by key in front and back side door suitable for 440 volts, 50 Hz, 3 phase 4 wire system including bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size of cable glands of suitable size for incoming and outgoing cables and comprising the dimension of outer shall be adequate to accommodate inner shell described below 50mm space all around and shall be fabricated in such way that inner shell along with its control gear and accessories and including following accessories and mounted on PCC Plat form min 35 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.25 m all round the panel board. Complete with the following items housed in:-BUSBar:- Copper bus bar rated 1.5 times of incoming MCCB/ACB |
| 95 | (a) Incomming :- (i) ACB 1600 Amps, 4 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) - 01 No (iii) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting . - 01 Nos (iv) LED indicating lamps - 1 [set of 3](b) Outgoing :- (i) ACB 800 Amps, 3 pole, 50 KA, 415V - 01 Nos (Adjustable Type) (ii)MCCB 500 Amps, 3 pole, 36 KA, 415V - 01 Nos (Adjustable Type) (iii) MCCB 250 Amps, 3 pole, 36 KA, 415V - 02 Nos (Adjustable Type) 01 Nos Spare (iv) MCCB 200 Amps, 3 pole, 36 KA, 415V - 02 Nos (Adjustable Type) (v) LED indicating lamps-1 set of 3 |
| 96 | LT Panel board made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, strickering of Switcher gear about termination of switch gear, cable connector for connecting multi cables located in cable chamber terminated form the switchergear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 300 A capacity complete with powder coating, necessary internal electric connection as required and provision of the following |
| 97 | a) MCCB 200 A AC 3 Phase 415 V, 50 Hz 4 pole breaking capactiy 25 kA with adjustable type thermal and magnetic setting relays - 01 Nos.( DG incoming)b) MCCB 100 A AC 3 Phase 415 V, 50 Hz 4 pole breaking capactiy 25kA with adjustable type thermal and magnetic setting relays - 08 Nosc) MCCB 32 A AC 3 Phase 415 V, 50H z 4 pole breaking capactiy 25 kA with adjustable type thermal and magnetic setting relays - 01 Nod) MCB10 A SPN AC 1 Phase 230 V, 50 Hz 2 pole capactiy 10kA - 02 Nose) MCB 32 A SPN AC 1 Phase 230 V, 50 Hz 2 pole capactiy 10kA - 03 Nosf) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs g) LED Indicating Lamps for each phase with colour coed Red Yellow Blue for R, Y and B Phases |
| 98 | Supply, install, testing and commissioning of LT indoor type panel board of suitable size, pedestal mounted, CPRI approved totally enclosed, dust and vermin proof, front side openable, type IP 54 protection made of CRCA sheet outer and inner shell 2.00 mm thick and 50x50x6 mm frame of size as per IS and having proper locking arrangement by key in front and back side door suitable for 440 volts, 50 Hz, 3 phase 4 wire system including bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size of cable glands of suitable size for incoming and outgoing cables and comprising the dimension of outer shall be adequate to accommodate inner shell described below 50mm space all around and shall be fabricated in such way that inner shell along with its control gear and accessories and including following accessories and mounted on PCC Plat form min 35 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.25 m all round the panel board. Complete with the following items housed in :-BUSBar:- Copper bus bar rated 1.5 times of incoming MCCB/ACB |
| 99 | (a) Incomming :- (i) ACB 800A, 4pole thermal magnetic - 01 No (ii) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting . - 01 Nos (iii) LED indicating lamps-1 set of 3(b) Outgoing :- (i) MCCB 250 Amps, 3 pole, 36 KA, 415V - 01 Nos (Adjustable Type) (ii) MCCB 160 Amps, 3 pole, 36 KA, 415V - 05 Nos (Adjustable Type) (iii) LED indicating lamps-1 set of 3 |
| 100 | Supply, install, testing and commissioning of LT indoor type panel board of suitable size, pedestal mounted, CPRI approved totally enclosed, dust and vermin proof, front side openable, type IP 54 protection made of CRCA sheet outer and inner shell 2.00 mm thick and 50x50x6 mm frame of size as per IS and having proper locking arrangement by key in front and back side door suitable for 440 volts, 50 Hz, 3 phase 4 wire system including bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size of cable glands of suitable size for incoming and outgoing cables and comprising the dimension of outer shall be adequate to accommodate inner shell described below 50mm space all around and shall be fabricated in such way that inner shell along with its control gear and accessories and including following accessories and mounted on PCC Plat form min 35 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.25 m all round the panel board. Complete with the following items housed in :-BUSBar:- Copper bus bar rated 1.5 times of incoming MCCB/ACB |
| 101 | (a) Incomming :- (i) MCCB 200 Amps 4 Pole 36 KA, 415 V -01 No (ii) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting . - 01 Nos (iii) LED indicating lamps-1 set of 3(b) Outgoing :- (i) MCCB 63 Amps, 3 pole, 16 KA, 415V - 05 Nos (Adjustable Type) (ii) MCCB 40Amps, 3 pole, 16 KA, 415V - 02 Nos (Adjustable Type) (iii) LED indicating lamps-1 set of 3 |
| 102 | Supply, installing, testing and commissioning of LT indoor type panel board of suitable size, pedestal mounted, CPRI approved totally enclosed, dust and vermin proof, front side openable, type IP 54 protection made of CRCA sheet outer and inner shell 2.00 mm thick and 50x50x6 mm frame of size as per IS and having proper locking arrangement by key in front and back side door suitable for 440 volts, 50 Hz, 3 phase 4 wire system including bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size of cable glands of suitable size for incoming and outgoing cables and comprising the dimension of outer shall be adequate to accommodate inner shell described below 50mm space all around and shall be fabricated in such way that inner shell along with its control gear and accessories and including following accessories and mounted on PCC Plat form min 35 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.25 m all round the panel board. Complete with the following items housed in :-BUSBar:- Copper bus bar rated 1.5 times of incoming MCCB/ACB |
| 103 | (a) Incomming :- (i) MCCB 250 Amps 4 Pole 36 KA, 415 V, (Microprocessor release) (ii) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting - 01 Nos (iii) LED indicating lamps-1 set of 3(b) Outgoing :- (i) MCCB 100 Amps, 3 pole, 16 KA, 415V - 3 Nos (Adjustable Type) (ii) MCCB 63 Amps, 3 pole, 16 KA, 415V - 3 Nos (Adjustable Type) (iii) LED indicating lamps-1 set of 3 |
| 104 | Supply, installing, testing and commissioning of LT indoor type panel board of suitable size, pedestal mounted, CPRI approved totally enclosed, dust and vermin proof, front side openable, type IP 54 protection made of CRCA sheet outer and inner shell 2.00 mm thick and 50x50x6 mm frame of size as per IS and having proper locking arrangement by key in front and back side door suitable for 440 volts, 50 Hz, 3 phase 4 wire system including bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size of cable glands of suitable size for incoming and outgoing cables and comprising the dimension of outer shall be adequate to accommodate inner shell described below 50mm space all around and shall be fabricated in such way that inner shell along with its control gear and accessories and including following accessories and mounted on PCC Plat form min 35 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.25 m all round the panel board. Complete with the following items housed in :-BUSBar:- Copper bus bar rated 1.5 times of incoming MCCB/ACB |
| 105 | (a) Incomming :- (i) MCCB 400 Amps 4 Pole 36 KA, 415 V, (Microprocessor release) (ii) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting - 01 Nos (iii) LED indicating lamps-1 set of 3(b) Outgoing :- (i) MCCB 63 Amps, 3 pole, 16 KA, 415V - 13Nos (Adjustable Type) (ii) LED indicating lamps-1 set of 3 |
| 106 | Supply, installing, testing and commissioning of LT indoor type panel board of suitable size, pedestal mounted, CPRI approved totally enclosed, dust and vermin proof, front side openable, type IP 54 protection made of CRCA sheet outer and inner shell 2.00 mm thick and 50x50x6 mm frame of size as per IS and having proper locking arrangement by key in front and back side door suitable for 440 volts, 50 Hz, 3 phase 4 wire system including bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size of cable glands of suitable size for incoming and outgoing cables and comprising the dimension of outer shall be adequate to accommodate inner shell described below 50mm space all around and shall be fabricated in such way that inner shell along with its control gear and accessories and including following accessories and mounted on PCC Plat form min 35 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.25 m all round the panel board. Complete with the following items housed in :-BUSBar:- Copper bus bar rated 1.5 times of incoming MCCB/ACB |
| 107 | (a) Incomming :- (i) MCCB 160 Amps 4 Pole 36 KA, 415 V, (Microprocessor release) (ii) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting - 01 Nos (iii) LED indicating lamps-1 set of 3(b) Outgoing :- (i) MCCB 63 Amps, 3 pole, 16 KA, 415V - 08 Nos (Adjustable Type) (ii) MCCB 40 Amps, 3 pole, 16 KA, 415V - 1 Nos (Adjustable Type) (iii) Timer electronic type 01 Nos |
| 108 | Supply, installing, testing and commissioning of LT indoor type panel board of suitable size, pedestal mounted, CPRI approved totally enclosed, dust and vermin proof, front side openable, type IP 54 protection made of CRCA sheet outer and inner shell 2.00 mm thick and 50x50x6 mm frame of size as per IS and having proper locking arrangement by key in front and back side door suitable for 440 volts, 50 Hz, 3 phase 4 wire system including bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size of cable glands of suitable size for incoming and outgoing cables and comprising the dimension of outer shall be adequate to accommodate inner shell described below 50mm space all around and shall be fabricated in such way that inner shell along with its control gear and accessories and including following accessories and mounted on PCC Plat form min 35 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.25 m all round the panel board. Complete with the following items housed in :-BUSBar:- Copper bus bar rated 1.5 times of incoming MCCB/ACB |
| 109 | (a) Incomming :- (i) MCCB 250 Amps, 4 pole, 36 KA, 415V - 05 Nos (Adjustable Type) (ii) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting . - 01 Nos (iii) LED indicating lamps-1 set of 3(b) Outgoing :- (i) MCCB 160 Amps, 3 pole, 36 KA, 415V - 01 Nos (Adjustable Type) (ii) MCCB 125 Amps, 3 pole, 36 KA, 415V - 02 Nos (Adjustable Type) (iii) MCCB 100 Amps, 3 pole, 36 KA, 415V - 01Nos (Adjustable Type) (iv) MCCB 63 Amps, 3 pole, 36 KA, 415V - 01Nos (Adjustable Type) |
| 110 | Supply, installing, testing and commissioning of LT indoor type panel board of suitable size, pedestal mounted, CPRI approved totally enclosed, dust and vermin proof, front side openable, type IP 54 protection made of CRCA sheet outer and inner shell 2.00 mm thick and 50x50x6 mm frame of size as per IS and having proper locking arrangement by key in front and back side door suitable for 440 volts, 50 Hz, 3 phase 4 wire system including bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size of cable glands of suitable size for incoming and outgoing cables and comprising the dimension of outer shall be adequate to accommodate inner shell described below 50mm space all around and shall be fabricated in such way that inner shell along with its control gear and accessories and including following accessories and mounted on PCC Plat form min 35 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.25 m all round the panel board. Complete with the following items housed in :-BUSBar:- Copper bus bar rated 1.5 times of incoming MCCB/ACB |
| 111 | (a) Incomming :- (i) MCCB 400 Amps 4 Pole 36 KA, 415 V, (Microprocessor release) (ii) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting - 01 Nos (iii) LED indicating lamps-1 set of 3(b) Outgoing :- (i) MCCB 100 Amps, 3 pole, 16 KA, 415V - 06 Nos (Adjustable Type) (ii) MCCB 63 Amps, 3 pole, 16 KA, 415V - 02 Nos (Adjustable Type) (iii) LED indicating lamps-1 set of 3 |
| 112 | Supply, installing, testing and commissioning of LT indoor type panel board of suitable size, pedestal mounted, CPRI approved totally enclosed, dust and vermin proof, front side openable, type IP 54 protection made of CRCA sheet outer and inner shell 2.00 mm thick and 50x50x6 mm frame of size as per IS and having proper locking arrangement by key in front and back side door suitable for 440 volts, 50 Hz, 3 phase 4 wire system including bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size of cable glands of suitable size for incoming and outgoing cables and comprising the dimension of outer shall be adequate to accommodate inner shell described below 50mm space all around and shall be fabricated in such way that inner shell along with its control gear and accessories and including following accessories and mounted on PCC Plat form min 35 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.25 m all round the panel board. Complete with the following items housed in :-BUSBar:- Copper bus bar rated 1.5 times of incoming MCCB/ACB |
| 113 | (a) Incomming :- (i) MCCB 100 Amps 4 Pole 36 KA, 415 V, (Microprocessor release) (ii) Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting - 01 Nos (iii) LED indicating lamps-1 set of 3(b) Outgoing :- (i) MCCB 63 Amps, 3 pole, 16 KA, 415V - 02 Nos (Adjustable Type) (ii) MCCB 40 Amps, 3 pole, 16 KA, 415V - 1 Nos (Adjustable Type) (iii) Timer electronic type 01 Nos |
| 114 | Supply, fix ,connecting , testing and commissioning of OEM Manufactured APFC Panel (automatic and manual operation) with 7% Aluminium reactor of capacity 450 KVAR (Output) @ 440 V AC interconnection with LT Panel/ Transformer (outdoor/ indoor) with appropriate size of electric power cable 1.1KV . The stage rating shall be (9 X 50) . The APFC Panel shall be fully type tested at an independnt Laboratory and shall comply with IEC 61439-1&2 and IEC 61921, IS-16636-2017. The degree of protection of enclosure system of the APFC Panel shall be min IP 54 (Outdoor) in accordance with IEC 60529. The capacitor bank shall be internet of things (IoT) enabled and communicable / integrable with BMS . The APFC Panel shall be Outdoor type confirming to IS 13341:1992 & IS13440:1993 floor mounted design fabricated out of 14 SWG CRCA Sheet treated through chemical with 8 tank process method of degreasing, derusting and phosphating powder coating (60-80 microns), painted in SIEMENS GREY (RAL 7032) shade powder coating paint, weather, dust and vermin proof suitable for humidity upto 95% and having four Nos iron legs made of 50x50x6mm thick, 60cm long angle iron below frame with front door and side/ back opening having locking arrangement prewired with copper conductor PVC insulated wire size 2.5sqmm/ extension strips and connected with suitable size thimbles & lugs. The legs duly embedded in ground (45cm) in PCC 1:3:6 type C1 (using 20mm aggregate). Cable entry from bottom. Transparent Acrylic sheet/Bakelite sheet will be provided for shrouding. Average daily temperature :+35 degree celcius max, Ambient temperature :-5 degree celcius to 40 degree celcius, Maximum altitude 2000m. Approved Make of Panel:-ABB/SCHNEIDER/SIEMENS/L&T/CMKL . The OEM 's specified cannot authorize any other partners / sub vendors to manufacture APFC Panels on their behalf . |
| 115 | The APFC Panel manufacturered by OEM's only will be accepted & factory acceptance test (FAT) will be carried out at OEM's plant only.The APFC Panel shall be comprising of the following:- |
| 116 | S & F street light terminal boxes made out with SMC matterial shock and dust proof of inside size 295 X 195 X 100 mm as per IS and including 50 Amps TPN busbar fixed on insulator 01 No 10 Amps SP MCB earth termination with nuts and bolts and including 02 Nos of flat iron clamps of size 25 x 6 mm, nuts, bolts and washers including two coat of aluminium paint over a coat of primer on exposed steel surface and connecting all incoming and outgoing wires with Aluminium lugs of appropiate size Complete all as specified and as directed |
| 117 | S&F 3 core PVC insulated cable 3 core x1.5 sqmm for connecting street light to junction box Complete all as specified and as directed |
| 118 | M&L for Cutting the road / hard standing for laying of pipes in trenches of size 300x300mm and making good with PCC 1 :2 :4 Type B1 complete and painting with black paint , if necessary, to match with existing bituminous road colour complete all as specified and as directed. |
| 119 | S&F Precast Reinforced Cement Concrete 1:2:4 (20mm graded aggregate) of size 900x250x75mm Cable Route Indicator including embossing 'DANGER/11KV CABLE/MES' on both sides and painted Letters with approved Colour, burried in ground for a depth of 45 Cm including necessary Earth Work, complete all as specified and as directed. |
| 120 | Fire fighting and fire alarm system |
| 121 | Supply and fix Control Panel for automatic starting of terrace pump with suitable Star Delta Automatic Starter for terrace pump , Contactors , single phase preventers and phase indicators etc., Including mounting arrangements and necessary connections etc.., complete all as specified and as directed. Note: Star -delta starter shall be measured and paid seperately. |
| 122 | Supply and fix fully automatic star delta starter suitable for 15 HP motor complete all as specified and directed. |
| 123 | Supply and fix 6 kg Capacity dry chemical power (ABC) fire exinguishers consisting of welded MS cylindrical body squeeze lever discharge valve fitted with pressure indicating guage internal discharge tube, 30 cm long high pressure discharge hose discharge nozles, suspension brackets comforming to IS finished exernally with red enamel paint and fixed to walls with brackets complete all as specified and directed. |
| 124 | Supply and fix 4.5 kg Capacity CO2 type (light weight squeeze grip type) fire exinguishers consisting of welded MS cylindrical body squeeze lever discharge valve fitted with pressure indicating guage internal discharge tube, 30 cm long high pressure discharge hose discharge nozles, suspension brackets comforming to IS finished exernally with red enamel paint and fixed to walls with brackets complete all as specified and directed. |
| 125 | Supply and fix 9 Ltr Capacity mechanical foam type fire exinguishers consisting of welded MS cylindrical body squeeze lever discharge valve fitted with pressure indicating guage internal discharge tube, 30 cm long high pressure discharge hose discharge nozles, suspension brackets comforming to IS finished exernally with red enamel paint and fixed to walls with brackets complete all as specified and directed. |
| 126 | Supply and fix fire buckets (dry sand) , as per IS 2546 , all as specified and as directed. |
| 127 | Supply and fix fire buckets stand suitable to hold 02 fire buckets , all as specified and as directed. |
| 128 | Supply , installation, testing and commissioning of indoor meter box panel board , CPRI Approved ,IP 42 made out of CRCA sheet 2 mm thick vermin proof factory made with 40 x 40 x6 mm MS angle/channel duly painted with two coats of synthetic enamel powder coated paint over a coat of metal primer with bus bar chamber comrising of high conductivity copper bus bar of capacity 200 Amps three phase and half the capacity for neutral including internal wiring with 6 sqmm copper conductor (FRLS) including PCC foundatoin suitable to accommodate the following as specified and as directed.:(a) MCCB 415 V,100 A, 4 pole with electronic release Electronic Earth leakage module with over load , short circuit and earth fault protection with earth module breaking capacity 16 KA- 01 Nos.(b)Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting with LED indication lamp complete and all as per standard pratice ---1 Job |
| 129 | Supply and fix foot valve of size 150 mm dia Complete all as specified and as directed. |
| 130 | Supply and fix 2 core 1.5 sqmm FRLS armoured copper cable as per IS:1554 in suitable dia steel conduit including all fixing accessories all as specified and directed. |
| 131 | Supply and fix in repair Air release valve made from gun metal single air outlets confirming to IS of size 25 mm dia fixed on the top of downcomer pipe of dia 100 mm including necessary slot making, welding , and making good the disturbed surface , applying two coats of synthetic enamal paint over a coat of red oxide primer etc with complete all as specified and as directed. |
| 132 | Supply and fix 24 V Electronic Hooter & making connection to the cable and making good the disturbed surfaces complete all as specified and directed. |
| 133 | Lightening Protection |
| 134 | M & L for sub-main wiring with 1.5 sqmm nominal area one single core PVC insulated unshethed multi-stranded FRLS copper conductor cable including one 1.5 sqmm PVC insulated unshethed multi-stranded copper conductor cable for earth wire drawn through 20 mm dia PVC conduit complete all as specified and as directed.Note :(i) Two runs of 1.5 Sqmm + one run of PVC conduit shall be measured as an one Unit. |
| 135 | PVC Conduit |
| 136 | Supply and fix telephone sockets (Jack type) RJ 11-1 with shutter 1 module with all accessories complete all as specified and directed. |
| 137 | Supply and fix TV co-axial socket 1 module with all accessories complete all as specified and directed. |
| 138 | CENTRAL AIR CONDITIONING |
| 139 | Supply,install, testing and commissioning of LT Outdoor type panel board of suitable size, pedestal mounted, CPRI approved totally enclosed, dust and vermin proof, front side openable, type IP 54 protection made of CRCA sheet 3.15 mm thick of size as per IS and having proper locking arrangement in front and back side door suitable for 440 Volts, 50 Hz, 3 phase 4 wire system including cable glands of suitable size for incoming and outgoing cables and comprising with and including following accessories and mounted on PCC Platform min 35 cm from ground level and grouted in PCC 1:3:6, 100 mm thick, 0.25 m all round the panel board complete with the following items housed in :-BUSBAR :- 600 Amps rated Alumunium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite / DMC insulator bus bar support (Square / round) insulators of suitable size and good insulation resistance (Busbar to MCCB shall be connected through suitable size of aluminium rigid / flexible busbar). (a) Incomming :- (i) MCCB 400 Amps Microprocessor based released , 4 pole, 35 KA, 415 V - 01 Nos (iii) LED Multifunction with meters. - 01 No (iv) LED indicating lamps-1 [set of 3](v) MCB SP 06 Amps 'C' curve-03 Nos(b) Outgoing :- (i) MCCB 63 Amps, 4 pole, 25 KA, 440Volts - 01 No (ii) MCCB 100 Amps thermal based , 4 pole, 25KA, 440 Volts - 09 Nos |
| 140 | Supply and HDPE double wall corrugated pipe of 90 mm outer dia for cable protection laid in trenches complete all as specified and directed. |
| 141 | Arboriculture |
| 142 | M&L for preparing the soil base for planting Bermuda grass by levelling the base to required slopes over spreading seeet earth to an average thickness of 200mm including mixing te natural fertilizers like cow dung, vermi complst etc : to imporve the fertility of the soil int he required roprotion and fianlly preparing the sil base suitable of Bermuda grass with maintenance for the period of one year complete all as specified and as directed. Note-(Supply and spreading of sweet earth and separently) Note- Rates to be deemed as inclusive of one year maintenance period. |
| 143 | Supply plantation and developing of Ficus Black (Ficus benjaminal) Height of plant not less than 1.00 mtr above ground level of age 6 months wit proprotional girth evergreen species including preparation of ground 0.60 mtr deep and of size 600x600mm and filling of good earth and compst and watering etc., complete all as specified and as directed |
| 144 | Supply and spreading sweet earth obtained from outside of MD and land from stone and pebbles (shall not exceeding 4.36mm) to an average thickness of 200mm suitable for giving sufficient strength to plantation complete all as specified and as directed. |
| 145 | S &F 20mm dia brass water spinkler complete all as specified and as directed |
| 146 | Cooling Appliances |
| 147 | Supply and fix refrigerator electric driven [single phase] 240 litres capacity double door inverter type not less than 3 star rating, 240 Volts, 50 Hz complete all as specified and as directed |
| 148 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally oil cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 with accuracy ± 2.5% and of capacity 2 KVA complete all as specified and as directed |
| 149 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally oil cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 with accuracy ± 2.5% and of capacity 5 KVA complete all as specified and as directed |
| 150 | Mechanical laundry |
| 151 | Supply, install, testing and commissioning of Washer Extractor (Front loading type) of capacity 60Kg, basket volume not less than 600 ltrs, G force not less than 320 GS, Steam heated, C.E. Certified machine heavy duty, high spin soft mount, Front loading open pocket, Fully programmed microprocessor up to 30 customised Pre set programmes, top suspension with hydraulic cushion, full stain less steel cabinet, SS inner cylinder & outer drum and loading door, single motor variable frequency drive, 5 Compartment Soap dispenser complete all as specified and as directed |
| 152 | Supply, Install, testing and commissioning Drying Tumbler, Front loading, Basket volume not less than 200 ltrs not less than 60 KG capacity, steam heated, C.E Certified machine, open pocket, SS Inner cylinder, Reversible doubled walled outer drum, Auto digital Time & Temperature & Auto digital control for drying and Cool down Time, Separate Motors Drive & suction Blower complete all as specified and as directed. |
| 153 | Supply, Install, testing and commissioning of vaccum finishing table Rectangular table top with SS Heater, Size 1200mmx750mm [Minimum] Extended Exhaust duct with rack and tube light & with swivelling arm assembly for utility buck of size 800x300x200mm (minimum) along with Electric steam Iron and Teflon shoe complete all as specified and directed |
| 154 | Supply Install, testing and commissioning of flat work drying ironer, chest heated, front feed, rear return, pneumatic operated ironing chest, adjustabel ironing pressure, variable frequency inverter drive conveyor belt feed, perforated roller with centrifugal moisture suction galvanized springs with polyster padding, Roller size 530mm dia x 3000mm L minimum, C.E. Certified machine, steam heated, complete all as specified and directed |
| 155 | Supply, Install, testing & commissioning of Flat bed press pneumatically operated with front push buttons, Auto Digital Time release and Bed with centrifugal moisture suction, adjustable ironing pressure teflon line head, Head size 1500x750 mm (Minimum), Steam heated complete all as specified and directed |
| 156 | Supply, lnstall, testing commissioning of Dry cleaning machine, high spin, Soft mount, Multi solvent, Computer controlled, not less than 15 KG capacity, Basket volume not less than 150 ltrs, Front loading, open pocket, Minimum 16 pre set programme, top suspension with hydraulic Cushions, Single motor variable frequency drive, Two solvent tanks with twin pumps not less than 75% solvent recovery complete all as specified and directed |
| 157 | Supply,install, testing & commissioning of Stain removing spotting machine, Stainless steel large work station with SS swivelling sleeve arm, SS Rack for solvent container, Stainless steel spotting guns, heavy duty \\"Steam-Air\\" Cold & Hot spotting device for Pre & Post spotting, Ecological Chemical Suction and lighting device complete all as specified and directed |
| 158 | Supply Install, testing & comnissioning of Diesel fired Boiler of capacity 600 Kg, Non IBR HSD, 10.54 Kg/Sg cm, MS ducting for chimney including 2000 Itrs water storage capacity tank on 3 mtr high with supporting MS structure complete all as specified and directed |
| 159 | Supply, Install, teasting and comissioning of Air Compressor, 10 HP minimum fully automatic, double stage , tank capacity 500 litre and pressure 8 Kg/ Sq Cm, complete all as specified and directed |
| 160 | Supply only washing room trolley totally stainless steel outer & inner body over all size : 850x650x800 mm (Minimum) complete all as specified and directed |
| 161 | All as per item above but wet liner trolley |
| 162 | Supply, Install, testing & commissioning of Water softener plant of capacity 300 ltrs/hr Cation exchange ALI (for water hardness less than 500 ppm) including feed pump service tank of capacity 300 ltrs including necessary connections of inlet and outlet connection complete all as specified and directed |
| 163 | Suppy & fix Fuel tank 1000 Itrs capacity for diesel fired boiler fixing on raised MS structure and pipe line connection of MS pipe for provide of steam to machineries with all necessary fittings inchuding valves of various sizes complete all as specified and directed |
| 164 | Supply , install, testing and commissioning of indoor meter box panel board , CPRI Approved, IP 42 made out of CRCA sheet 2 mm thick vermin proof factory made with 40 x 40 x6 mm MS angle/channel duly painted with two coats of synthetic enamel powder coated paint over a coat of metal primer with bus bar chamber comrising of high conductivity copper bus bar of capacity 400 Amps three phase and half the capacity for neutral including internal wiring with 6 sqmm copper conductor (FRLS) including PCC foundation suitable to accommodate the following as specified and as directed.:(a) MCCB 415 V,200 A, 4 pole with electronic release Electronic Earth leakage module with over load , short circuit and earth fault protection with earth module breaking capacity 25 KA- 01 Nos.(b)Digital Panel Meter Multifunctional type for Amps, Volts, KWH, Power Factor and other parameters flush mounting with LED indication lamp complete and all as per standard pratice ---1 Job |
| 165 | Suppy, install, testing and commissioning of centrifugal Monoblock pump set 7.5 KW/10 HP motor 3 phase 415 volts, 3000 RPM, body and impeller : cast iron, Shaft : SS and sealing : mechanical sealing complete all as specified and directed. |
| 166 | DG Set |
| 167 | Supply, install, testing and commissioning of silent Diesel Engine Generating set including accoustic enclosure as per latest CPCB norms 415 Volts 160 KVA, 3 Phase, 0.8 power factor, 50 Hz, 1500 RPM self excited self regulated brushless AC generator including accoustic enclosure suitable for ambient condition and conforming to condition under IS-4722, BS-5514/2613/5000 with AMF Panel and including the following including accoustic enclosure suitable for ambient condition at sea area and conforming to Engine as per IS:10002, ISO-3046, BS-5514 and Alternator as per IS:4774, BS EN 60034-1 with the following accessories including necessary suitable size PCC foundation, GI pipe for laying of cables etc., all as per manufacturers instructions complete all as specified and directedMake: Kirloskar/ Cummins/Ashok Leyland/ Jyoti/ Crompton Please Enable Macros to View BoQ information |
| 168 | Supply, install, testing and commissioning of silent Diesel Engine Generating set including accoustic enclosure as per latest CPCB norms 415 Volts 160 KVA, 3 Phase, 0.8 power factor, 50 Hz, 1500 RPM self excited self regulated brushless AC generator including accoustic enclosure suitable for ambient condition and conforming to condition under IS-4722, BS-5514/2613/5000 with AMF Panel and including the following including accoustic enclosure suitable for ambient condition at sea area and conforming to Engine as per IS:10002, ISO-3046, BS-5514 and Alternator as per IS:4774, BS EN 60034-1 with the following accessories including necessary suitable size PCC foundation, GI pipe for laying of cables etc., all as per manufacturers instructions complete all as specified and directedMake: Kirloskar/ Cummins/Ashok Leyland/ Jyoti/ Crompton Please Enable Macros to View BoQ information |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail