| 1 | Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in any type of soil (i.e. soft/ loose or hard/ dense soil) complete all as specified and as directed. |
| 2 | Returning, filling in trenches, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in soil complete all as specified and as directed. |
| 3 | Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed. |
| 4 | M&L for cutting of existing road for removing / laying UG Cables/ pipe line, depth of cutting not exceeding 90cm and width 45cm and filling the trench of road i.e. excluding top 20cm with existing aggregate obtained from cutting, watered and properly rammed to satisfaction of EIC and finally provide with & including 20 cm thick PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate to entire width of trench & finally match the top surface to road & disposal of debris to a distance not exceeding 250 metre and depositing where directed complete all as directed. |
| 5 | M&L for filling approved dry river sand for cushioning and cover for protection of under ground electric cable in trenches 8 cm before laying cable and 15 cm deep over the cable and punning to 18 cm total thickness complete all as specified and as directed. Notes :-(i) Approved dry sand free from vegetations, grass and other deleterious substances shall be used.(ii) For the purpose of payment, only punned thickness shall be measured. |
| 6 | Taking down carefully old existing LT PCC Cable Cover of Class LV of any type & size complete all as specified & as directed. |
| 7 | Laying only LT PCC cable covers of any type & size for protection of UG LT electric cables in trenches, obtained serviceable from serial item No. 6 here-in-above, complete all as specified & as directed. |
| 8 | Supply and laying un-reinforced precast concrete cable cover, Class LV, Type-1, Flat, size 250mm x 150mm x 40mm for protection of underground electric cable in trenches complete all as specified and as directed. |
| 9 | Supply and laying/fixing 40 mm bore High Density Polyethylene (HDPE) Pipes of Grade ‘PE 100’, Pressure Class ‘PN 8’, ‘SDR-17’, ISI marked, with all fittings, laid in trenches, under floors or roads/ along poles etc for protection of electric cables, fixed in repairs, complete all as directed. |
| 10 | M&L for Galvanized iron tubing, 100mm bore light grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls etc with required size of flat iron (minimum 25mmx3mm) clamps, bolts, nuts and washers for protection of HT/LT electric cable including taking down old unserviceable protection pipe with clamps complete all as specified & as directed.Note :- Excavation & earthwork shall be measured & paid for separately. |
| 11 | All as per serial item No. 10 here-in-above, but 80mm bore. |
| 12 | All as per serial item No. 10 here-in-above, but 50mm bore. |
| 13 | Supply, laying, jointing and testing LT XLPE (cross linked polyethylene) insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric cable (heavy duty) with aluminium stranded conductor 1100 Volt grade cross sectional area 240 sqmm 3½ Core (ISI marked) laid in trenches/ducts, through pipe, under floors or roads/ along poles etc including dismantling & taking out old unserviceable cable complete all as specified & as directed.Note : Sand cushioning, cable protection covers, protection pipe, jointing kits and excavation & earth work shall be measured & paid for separately. |
| 14 | All as per serial item No. 13 here-in-above, but cross-sectional area 185 Sqmm 3½ Core. |
| 15 | All as per serial item No. 13 here-in-above, but cross-sectional area 120 Sqmm 3½ Core. |
| 16 | All as per serial item No. 13 here-in-above, but cross-sectional area 95 Sqmm 3½ Core. |
| 17 | All as per serial item No. 13 here-in-above, but cross-sectional area 70 Sqmm 3½ Core. |
| 18 | All as per serial item No. 13 here-in-above, but cross-sectional area 35 Sqmm 3½ Core. |
| 19 | All as per serial item No. 13 here-in-above, but cross-sectional area 25 Sqmm 3½ Core. |
| 20 | All as per serial item No. 13 here-in-above, but cross-sectional area 16 Sqmm 4 Core. |
| 21 | All as per serial item No. 13 here-in-above, but cross-sectional area 10 Sqmm 4 Core. |
| 22 | M&L for cable jointing kit for 1100 V grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 2 to 4 core PVC/XLPE armoured aluminium conductor cable of size 6 Sqmm to 16 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed. |
| 23 | M&L for cable jointing kit for 1100 V grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 sqmm to 50 sqmm including dismantling & taking out old unserviceable jointing kit complete all as specified & as directed. |
| 24 | All as per serial item No. 23 here-in-above, but size 70 Sqmm to 120 Sqmm. |
| 25 | All as per serial item No. 23 here-in-above, but size 150 Sqmm to 185 Sqmm. |
| 26 | All as per serial item No. 23 here-in-above, but size 240 Sqmm to 300 Sqmm. |
| 27 | M&L for preparation of old painted steel surfaces by cleaning, removing rust, grease and apply one coat of 1st quality synthetic enamel paint of approved tint (Spray painting outside /inside surfaces) by removing and re-fitting of switch gears/ busbar of the feeder pillar box/ LT Panels Outdoor/ Indoor type of any size complete with prior permission of Engineer in Charge. Base frame shall be painted with Black synthetic enamel paint and including writing the SM No. / MES No. on Panel/ Feeder pillar box in white synthetic enamel paint complete all as specified and as directed. |
| 28 | M&L for LT danger notice plate of size 20x15 cm made of aluminium sheet 1 mm thick fixed with Nut, bolts and washers or riveting on LT panels/ feeder pillar boxes with vitreous enamelled white back ground with letters(in English, Hindi & Gujarati), figures and conventional skull and bones in signal red colour complete all as specified & as directed. |
| 29 | S&F in repair Junction Box made from FRP sheet 2.00 mm thick readymade of size 400mm x 300mm x 200mm, aluminium busbar 200 Amp, 4 wire system, 415 Volt fixed to pole/ Wall with MS clamp of FI 25 x 5mm and suitable size of nut, bolts and washers complete all as specified & as directed. |
| 30 | S&F in repair LED type R/Y/B/G indicating lamp complete all as directed. |
| 31 | S&F in repair selector switch suitable for Voltmeter 3 phase, 415V, AC, Voltage between Phases with OFF 6 Amp in existing panel complete all as specified & as directed. Make: L&T Cat No. 61312 SAB13TDYR or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 32 | S&F in repair selector switch suitable for Ammeter 3 phase, 415V, AC, Line Currents with OFF with CT 6 Amp in existing panel complete all as specified & as directed. Make: L&T Cat No. 61325 SAB13TDYR or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 33 | S&F in repair copper bus bar of required size, shape, length and making drilling for fixing in LT panel/ feeder pillar/ change over switch etc including necessary addition/ alteration to existing panel with welding cutting to steel structure complete all as specified & as directed. |
| 34 | S&F in repair aluminium bus bar of required size, shape, length and making drilling for fixing in LT panel/ feeder pillar/ change over switch etc including necessary addition/ alteration to existing panel with welding cutting to steel structure complete all as specified & as directed. |
| 35 | S&F in repair Air Circuit Breaker (ACB), 630 Amp, 4 Pole, 50 kA, drawout version, single frame, manual and electrical Versions, including advanced self powered electronic protection units and shunt coil, close coil, working on 220-250 V AC, Neutral Overload protection OFF-50%-100%, inbuilt temperature protection, LCD Display, Real terminals - vertical or horizontal connection with bars to be fixed onto plate-4P, fast operation type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition/ alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified and as directed. Make : Legrand ‘ACB : Cat No 6695 42’, ‘Electronic Protection Unit : Cat No 0281 67’ & ‘Real terminals : Cat No. 0288 97’ or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 36 | S&F in repair MCCB with thermal magnetic protection unit rating 630 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4220 09 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 37 | S&F in repair MCCB with thermal magnetic protection unit rating 400 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4220 07 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 38 | S&F in repair MCCB with thermal magnetic protection unit rating 320 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4220 06 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 39 | S&F in repair MCCB with thermal magnetic protection unit rating 250 Amp, 4 Pole, 25 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4202 19 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 40 | S&F in repair MCCB with thermal magnetic protection unit rating 160 Amp, 4 Pole, 25 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 57 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 41 | S&F in repair MCCB with thermal magnetic protection unit rating 100 Amp, 4 Pole, 16 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 15 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 42 | S&F in repair MCCB with thermal magnetic protection unit rating 125 Amp, 4 Pole, 16 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 16 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 43 | S&F in repair MCCB with thermal magnetic protection unit rating 63 Amp, 4 Pole, 16 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 13 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 44 | S&F in repair MCCB with thermal magnetic protection unit rating 160 Amp, 3 Pole, 16 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 07 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 45 | S&F in repair MCCB with thermal magnetic protection unit rating 100 Amp, 3 Pole, 16 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 05 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 46 | S&F in repair MCCB with thermal magnetic protection unit rating 125 Amp, 3 Pole, 16 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 06 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 47 | S&F in repair MCCB with thermal magnetic protection unit rating 63 Amp, 3 Pole, 16 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type in existing panel boards connecting with proper size link set at incoming and outgoing cable end with cable connections and including necessary addition / alteration to existing panel with welding cutting to steel structure and providing new steel items and taking down old item complete all as specified. Make: Legrand Cat Part No. 4200 03 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 48 | S&F in repairs MCB TPN 32 Amp, 415 V, 50 Hz, AC supply, 10 kA, 'C' Curve, with proper size lugs complete all as directed. Make: Legrand Cat No. 4086 80 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 49 | S&F in repairs MCB TPN 63 Amp, 415 V, 50 Hz, AC supply, 10kA, 'C' Curve, complete all as directed. Make: Legrand Cat No. 4086 83 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 50 | S&F in repairs MCB SPN 6 to 32 Amp, 240 V, 50 Hz, AC supply, 10 kA, 'C' Curve, complete all as directed. Make: Legrand Cat No. 4086 09 to 4086 17 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 51 | S&F in repairs MCB SPN 40 to 63 Amp, 240 V, 50 Hz, AC supply, 10 kA, 'C' Curve, complete all as directed. Make: Legrand Cat No. 4086 18 to 4086 20 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 52 | M&L for servicing of feeder pillar box after dismantling the incoming and outgoing connections from MCCB/ Bus bar and replacing the old burnt/ overheated unserviceable lugs, terminals, nuts, bolts, washers supporting insulators etc and checking the serviceability of MCB/ MCCB, earth continuity conductor and strip etc complete all as specified and as directed. Notes : (i) Spare parts such as terminals, lugs, nut bolts, insulators etc shall be measured and paid for separately as ‘Supply only’ under respective items of this Schedule 'A' (BOQ). (ii) Labour cost for fixing of the spare parts deemed to be included in the rate quoted for this item. |
| 53 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 400 Sqmm |
| 54 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 300 Sqmm |
| 55 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 240 Sqmm |
| 56 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 150 Sqmm |
| 57 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 120 Sqmm |
| 58 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 95 Sqmm |
| 59 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 70 Sqmm |
| 60 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 50 Sqmm |
| 61 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 35 Sqmm |
| 62 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 25 Sqmm |
| 63 | Supply only aluminium lugs (crimping terminals) of any type/ shape of capacity 16 Sqmm |
| 64 | Supply only GI bolts with Nuts & washers of required sizes and as directed. |
| 65 | Supply only bus bar Insulators Epoxy type as required at site minimum size 45mm x 50mm dia. |
| 66 | S&F in repair Extension link (Spreader), Set of Four, suitable for MCCB 125 to 160 Amp, 4 Pole. Make: Legrand Cat Part No. 6250 06 or equivalent in Havells/ Standard/ IndoAsian / C&S/ ABB/ GE / L&T / Schneider / Siemens / HPL |
| 67 | S&F in repair Extension link (Spreader), Set of Four, suitable for MCCB 250 Amp, 4 Pole. Make: Legrand Cat Part No. 6250 18 or equivalent in Havells/ Standard/ IndoAsian / C&S/ ABB/ GE / L&T / Schneider / Siemens / HPL |
| 68 | S&F in repair Extension link (Spreader), Set of Four, suitable for MCCB 400 to 630 Amp, 4 Pole. Make: Legrand Cat Part No. 6250 08 or equivalent in Havells/ Standard/ IndoAsian / C&S/ ABB/ GE / L&T / Schneider / Siemens / HPL |
| 69 | S&F in repair 3 Pole Power Contactor, 40 Amp AC3 rating, 2 NO + 2 NC, including necessary connections for incoming and outgoing complete all as directed. Make : L&T ‘Type ML 3’ Cat No. SS90721 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 70 | S&F in repairs Astro digital time switch, 1 Out put 16 A, 1 channel mounting in existing panel, suitable for switching ON/OFF light and other electric devices according to the rising/setting of the sun with combination function for creating switching programs in which devices are switched according to astronomical time and/or fixed preset times and also suitable for daily astronomical calculation of the sunrise/sunset time based on the entered location or location coordinate complete all as directed. Make: Legrand Cat No. 4126 54 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 71 | S&F in repair Volt meter, Digital type, 3 phase, 415 V in existing panel including wiring from bus bar to volt meter terminals complete all as specified. Make: L&T Cat Part No. WDS301FEV00 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 72 | S&F in repair Ammeter, digital type, 3 phase, 415 V in existing panel including wiring from bus bar to Ammeter terminals complete all as specified. Make: L&T Cat No. WDS301FCA00 or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 73 | S&F in repair Current Transformer of rating from 100/5 to 400/5 CT ratio in existing panel complete all as specified. Make : AE/ Kappa or equivalent in makes mentioned in Appendix 'B' here-in-after. |
| 74 | Taking down rusted portion of sheet of feeder pillar boxes, damaged hinges etc and S&F new mild steel hinges heavy duty type, MS sheet (of existing thickness) patch work by cutting, welding and fabricating at site as required not exceeding 1 Sqm, painting with two coats of 1st quality synthetic enamel paint over one coat of red oxide primer complete all as specified and as directed. |
| 75 | Disconnecting, dismantling & taking down old unserviceable LT Panel Box of any size & capacity including all fixtures/accessories and Supply, installing, commissioning and testing factory made and tested (CPRI approved manufacturer) new outdoor type LT Panel Box cubical type of suitable size (minimum depth 500mm) to accommodate the following accessories, 415 Volt, 3 Phase & neutral, 4 wire, 50 Hz, AC supply system, made out of 3.15 mm thick MS CRCA sheet (outer body, doors, etc), inside partitions & cover made out of 2mm thick MS CRCA sheet, with modular hinges, powder coated inside & outside with 7 tanks process in approved shade, protection class IP-55 with coloured insulation sleeve, rubber gasket, insulators, outdoor type, totally enclosed, weather, dust and vermin proof as per IS, Front & Rear opening with double door shutters having suitable aldrop bolt locking arrangement, with insulators, including internal wiring with PVC insulated stranded copper conductor FRLS cables of appropriate size as directed with proper ferrule & cable glands including connecting incoming and outgoing cables, including danger notice plate, necessary PCC 1:3:6 type C1 in foundation and frame made out of 65 x 65 x 6mm angle iron grouted at minimum 45cm above ground level and 30cm below ground level, comprising & including the following accessories complete all as specified and as directed :- (a) MCCB 250 Amp, 4 Pole, 36 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 01 No as incoming.description of item contd.... |
| 76 | Description of serial item No. 75 contd…(b) MCCB 200 Amp, 4 Pole, 25 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 01 No. as outgoing.(c) MCCB 100 Amp, 4 Pole, 25 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 02 Nos as outgoing.(d) RCBO Four Pole 63 Amp - 01 No. (e) RCBO Four Pole 32 Amp - 01 No.(f) RCBO Double Pole 40 Amp - 01 No.(g) Multifunction Meter – 01 No. Make: L&T/ C&S/ Legrand/ SECURE or equivalent in makes mentioned in Appendix 'B' here-in-after. (h) Bus bar minimum 400 Amp copper with R/Y/B coloured for three Phases and 150 Amp for Neutral Black colour insulation sleeves - 01 Set(j) Indicator Set RYB, “LED” type (set of three) -01 Setdescription of item contd.... Please Enable Macros to View BoQ information |
| 77 | Description of serial item No. 75 contd…(b) MCCB 200 Amp, 4 Pole, 25 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 01 No. as outgoing.(c) MCCB 100 Amp, 4 Pole, 25 kA, 415 Volt grade, AC, 50 Hz, adjustable Thermal - Magnetic release type - 02 Nos as outgoing.(d) RCBO Four Pole 63 Amp - 01 No. (e) RCBO Four Pole 32 Amp - 01 No.(f) RCBO Double Pole 40 Amp - 01 No.(g) Multifunction Meter – 01 No. Make: L&T/ C&S/ Legrand/ SECURE or equivalent in makes mentioned in Appendix 'B' here-in-after. (h) Bus bar minimum 400 Amp copper with R/Y/B coloured for three Phases and 150 Amp for Neutral Black colour insulation sleeves - 01 Set(j) Indicator Set RYB, “LED” type (set of three) -01 Setdescription of item contd.... Please Enable Macros to View BoQ information |