Tender For Maintenance And Repair To Water Supply Scheme @ Sinner....Retrofit Of Damaged Ht 11 Kv Vcb, Cable, Capacitors And Other Miscellaneous Work @ Palse Jackwell. Rs. 1998968.00, Nashik-Maharashtra
TDR : 55254118
Tender Notice
BOQ
12 Days Left
Nashik
Maharashtra
Tender For maintenance and repair To Water Supply Scheme @ Sinner....Retrofit Of Damaged Ht 11 Kv Vcb, Cable, Capacitors And Other Miscellaneous Work @ Palse Jackwell. Rs. 1998968.00
Name of Work:- M&R to water supply scheme @ Sinner....Retrofit of damaged HT 11 KV VCB, Cable, Capacitors and other miscellaneous work @ Palse Jackwell. Rs. 1998968.00
Sl. No.
Item Description
1
M&R to water supply scheme @ Sinner....Retrofit of damaged HT 11 KV VCB, Cable, Capacitors and other miscellaneous work @ Palse Jackwell.
2
HG 2-8) 11 kV system 1250 Amp 25 kA
3
Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (strip) cable 11 kV(E), 3 x 120 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT
4
Providing and erecting Heat shrinkable outdoor termination kit for 11 KV (E) XLPE HT cable 3x120 to 185 sq. mm. with necessary material as per specification no. CB-JT/HT
5
Providing and erecting Heat shrinkable indoor termination kit for 11 KV (E) XLPE HT cable 3x120 to 185 sq. mm. with necessary material as per specification no. CB-JT/HT
6
Supplying, erecting, testing & commisioning 525 V 3 phase, 50 Hz., APP type capacitor having minimum overcurrent capacity of 1.8 In, peak inrush current capacity 300 In and minimum life 150000 hours kVAr bank of all polypropylene condensers (APP) with the standard capacities of 2, 3, 5, 7, 10, 12.5 and 15 kVAr units of P.F. correction for operation on 3 phase 50 Hz. with externally discharging resistances, earthing terminals and built on angle iron or channel iron frame work and provided with terminal cover box complete erected on provided iron bracket or on floor duly tested by licensee.
7
Supplying and erecting of resin cast HT CT of ratio 300/1-1A as per requirement.
8
Repairs and rewinding of Star Rated (3 STAR) 200 KVA, 3 phase, 50 c/s Oil immersed and naturally cooled indoor /outdoor type, copper wound transformer with delta conn. on HV side & star connection on LV side with additional neutral brought out on load side, voltage rating 11/0.415kV with HV tapping of +/- 2.5% - 5 % continuously rated for full load with standard accessories complete with Test Certificate with losses below 890 watts at 50 % loading and 2700 watt at 100 % Loading as per IS 1180 (Part 1 ) as per specification. Please Enable Macros to View BoQ information
We takes all possible care for accurate & authentic tender information, however Users
are requested to refer Original source of Tender Notice / Tender Document published by
Tender Issuing Agency before taking any call regarding this tender.