| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Executive Engineer Electric Division -II JPDCL Jammu Name of Work: Rate contract for creation of 250 KVA Distribution Substations in the jurisdiction of Electric Division-II Jammu during the Financial Year 2026-27 on Turnkey Basis. Contract No: E-Nit No. 12 of 2026-27 Dated 27-04-2026 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # |
| 2 | Item Description |
| 3 | Creation of 11/0.433kV, 250 KVA, 3-phase Distribution Substation |
| 4 | Supply, Installation & commissioning of 11/0.433 KV, 250 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, \\"BIS Marked\\" (Copper Wound) alongwith LV Cable Box having detachable Alumnium Gland plate including Transportation ( As per Latest Ammendment upto date) |
| 5 | Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface. |
| 6 | Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type |
| 7 | Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 8 | Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A |
| 9 | Providing & Fixing of Single Phase PVC Cable 240 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 240 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt) |
| 10 | 11kV Polymeric composite Disc Insulator 12kV with Fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 11 | Supply, Transportation, Fabrication & Fixing of GI Channel Iron, GI Cross arms, GI Angle Iron Braces, GI Clamps etc duly fabricated including all necessary GI Nut & Bolts & Washers etc. |
| 12 | Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 13 | Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 14 | LT Fuse Switch with Aluminium Strip and Bus Bar insulators |
| 15 | Providing & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI stranded wire complete |
| 16 | Providing & Fixing of Danger Plates with Clamps |
| 17 | Providing & Fixing of Anti Climbing device with Clamps |
| 18 | Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole Total in Figures 0.0 0.0 Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 No Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Executive Engineer Electric Division -II JPDCL Jammu Name of Work: Rate contract for creation of 400 KVA Distribution Substations in the jurisdiction of Electric Division-II Jammu during the Financial Year 2026-27 on Turnkey Basis. Contract No: E-Nit No. 12 of 2026-27 Dated 27-04-2026 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # |
| 19 | Item Description |
| 20 | Creation of 11/0.433kV, 400 KVA, 3-phase Distribution Substation |
| 21 | Supply, Installation & commissioning of 11/0.433 KV, 400 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, \\"BIS Marked\\" (Copper Wound) along with LV Cable Box having detachable Alumnium Gland plate including Transportation (As per Latest Amendment upto date ) |
| 22 | Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface. |
| 23 | Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type |
| 24 | Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 25 | Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A |
| 26 | Providing & Fixing of Single Phase PVC Cable 400 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 400 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt) |
| 27 | 11kV Polymeric composite Disc Insulator 12kV with fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 28 | Supply, Transportation, Fabrication & Fixing of GI Channel Iron, GI Cross arms, GI Angle Iron Braces, GI Clamps etc duly fabricated including all necessary GI Nut & Bolts & Washers etc. |
| 29 | Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 30 | Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 31 | LT Fuse Switch with Aluminium Strip and Bus Bar insulators |
| 32 | Construction of Cement Platform 8'x8'x3' (3feet above & 3feet below ground level ) for 400 KVA SubStation along with the mesh fencing around the Periphery. (complete Job) |
| 33 | Providing & Fixing of Danger Plates with Clamps |
| 34 | Providing & Fixing of Anti Climbing device with Clamps |
| 35 | Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole |
| 36 | Providing & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GI stay rod & 7/3.15 mm dia GI stranded wire complete Total in Figures 0.0 0.0 Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 No Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: Executive Engineer Electric Division -II JPDCL Jammu Name of Work: Rate contract for creation of 630 KVA Distribution Substations in the jurisdiction of Electric Division-II Jammu during the Financial Year 2026-27 on Turnkey Basis. Contract No: E-Nit No. 12 of 2026-27 Dated 27-04-2026 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # |
| 37 | Item Description |
| 38 | Creation of 11/0.433kV, 630 KVA, 3-phase Distribution Substation |
| 39 | Supply, Installation & commissioning of 11/0.433 KV, 630 KVA 3-Phase Distribution Transformer with Bi-metallic terminal Connectors, Energy Level: 2, \\"BIS Marked\\" (Copper Wound) alongwith LV Cable Box having detachable Alumnium Gland plate including Transportation (As per latest IS) |
| 40 | Supply, Transportation, Erection of 9 Mtr Long ST Pole (ST-410 SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface. |
| 41 | Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type |
| 42 | Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type |
| 43 | Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A |
| 44 | Providing & Fixing of Single Phase PVC Cable 400 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 400 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt) |
| 45 | 11kV Polymeric composite Disc Insulator 12kV with Fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 46 | Supply, Transportation, Fabrication & Fixing of GI Channel Iron, GI Cross arms, GI Angle Iron Braces, GI Clamps etc duly fabricated with all necessary GI Nut & Bolts & Washers etc. |
| 47 | Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 48 | Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 49 | LT Fuse Switch with Aluminium Strip and Bus Bar insulators |
| 50 | Construction of Cement Platform 8'x8'x3' (3feet above & 3feet below ground level ) for 630 KVA SubStation along with the mesh fencing around the Periphery. (complete Job) |
| 51 | Providing & Fixing of Danger Plates with Clamps |
| 52 | Providing & Fixing of Anti Climbing device with Clamps |
| 53 | Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole |
| 54 | Providing & Fixing of Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete Total in Figures 0.0 0.0 Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 No Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |