| 1 | Supply, testing, laying, connecting & commissioning of 240 sq. mm, 1.1kV grade, 3.5-core, Aluminium Conductor, XLPE Sheathed Armoured Cable (ISI Marked), including PVC tagging after every 7 metres. The cable is to be laid as per the instructions of the site engineer. The Job includes providing and fixing of MS Clamps (for fixing of cable onto wall or as per instructions of site engineer) wherever required. |
| 2 | Supplying and making end termination with Aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 3 | 3 1/2 × 240 sq. mm (62 mm) |
| 4 | 3 1/2 × 300 sq. mm (70 mm) |
| 5 | Laying of one number additional PVC insulated and PVC sheathed XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 6 | Above 185 sq. mm and upto 400 sq. mm |
| 7 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 8 | 315 mm dia (OD-315 mm & ID-275 mm nominal) |
| 9 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 10 | Providing and fixing 25 mm × 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 11 | Constructing brick masonry manhole in cement mortar 1:4 (1 cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate 20 mm nominal size), complete as per standard design including. excavation, reinforcement, shuttering, finishing and all allied items required for complete job including making the site good after completion of work as directed by engineer in chargeInside size 90×80 cm and 60 cm deep including C.I. cover with frame (Medium /Heavy duty) as per requirement at site. |
| 12 | Supply, installation, testing and commissioning of 320A, 4 Pole, MCCB, Adjustable Thermal & Adjustable Magnetic, Rated Ultimate Shortcircuit Breaking Capacity Icu at 415 V (kA rms) 36, Rated Service short circuit Breaking Capacity Ics = % Icu at 415 V (kA rms) 100%.The Job includes providing and fixing of associated enclosures (wherever required), as per the instructions of site engineer. Please Enable Macros to View BoQ information |