| 1 | Item Rate BoQ 82550/E8 BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: CWE JAIPUR Name of Work: PROVN OF BORE WELLS (QTY-02 NOS) ALONGWITH CONNECTED ITEMS FOR OTM ACCN AT PARA SF SITE IN NIWARU MIL STN UNDER GE JAIPUR CA NO: CWE/JPR- OF 2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # NUMBER # SNo Item Description Item Code / Make Qty Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency Rate in Figure Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT With Taxes Rate in Words Total Amount |
| 2 | Boring / Drilling Trial bore holes of 200 mm diameter bore in all kinds of soils, unconsolidated & semi-consolidated formations, Sandy soil formation, rocks by using suitable method by direct rotary Rig method upto 200 metre depth below ground level in any type of soil rock/ hard rock / loose boulders with sand including collection of strata samples in transparent polybags @ 3m or whenever there is any change in strata, selection of site for boring by standard method/ practice disposal of materials obtained (sand, soil, boulders, etc) from boring to distance not exceeding 50 metre including complete in all respects with all labour, materials, tools and tackles, equipments, rig, etc. all as specified in IS : 2800 and as directed by Engr-in-charge complete all as specified and directed. |
| 3 | Widening / Reaming of bore well from 200mm to 500 mm drilling using suitable method by reverse rig method or auguring by hammering or any other suitable drilling method or any approved method at site below ground level in any kind of soil strata incl hard stone/boulder complete all as specified in IS : 2800 and directed. |
| 4 | Supply fixing and lowering bail plug, suitable for 200 mm bore plain pipe thickness 8 mm complete including welding and painting of pipes complete all as specified and directed. |
| 5 | Supplying and lowering in the bore hole ERW MS pipe 200 mm Internal Dia, 8mm thick slotted pipe having slots of 1.59 mm wide 3\\" long IS-8110 as laid down and with all necessary fittings and painting of pipe with two coats of anti corrosive approved paint on outside surface of pipe before lowering including supplying all labour, equipments and materials all around welded with 3 Nos stiffeners of flat iron 40 x 6 mm, 300 mm long complete as per IS and specified and directed. Note:- Location and length of the strainer pipe shall be as per electro logging result. |
| 6 | Supplying and lowering in the bore hole, the ERW MS pipe plain assembly MS casing pipe Fe 410 and Fe 450 grade steel as per IS-4270 and nominal bore of pipe 200 mm Internal Dia & 216 mm Outer Dia and wall thickness of 8 mm including welding of pipe at site with two coats of approved anti-corrosive paint on outer faces of the pipe and specials including supply of all labour, equipments and materials all around welded with 3 Nos stiffeners of flat iron 40 x 6 mm, 300 mm long complete all as specified and directed. |
| 7 | Supply of Pea gravel size ranging from 5mm to 12 mm. All gravel shall consist of hard well rounded particles reasonably uniform with uniformity coefficient of less than 2 including packing in the annular space between casing pipe & drilled bore complete all as specified and directed |
| 8 | M & L for Development of bore wells including flushing out tree roots, silt, fine sand by air compressor and subsequently by a vertical turbine pump of suitable capacity not less than 450 CFM at 150 PSI & over pumping (25% extra capacity pump) to make water free from turbidity till the bore well yields sand and silt free clear water is obtained from bore well complete all as specified and directed |
| 9 | M & L for electro logging by means of electric logger of the complete tube well of 500 mm bore and submission of report along with its interpretations by GWM scientist complete all as specified and directed by Engineer-in-Charge. |
| 10 | M & L for Yield test of bore well after completion of development of bore well by V notch method or any method of compressor or by pumping as required complete all as per IS and as directed.Note: Necessary equipment such as collection V notch, water collection Tank, motor pump set for testing for yield test shall be arranged by the contractor. The cost of the same shall deemed to be included with unit rate of item. |
| 11 | Supply, lowering, testing and commissioning of Submersible pump and motor as per IS-9283 (latest), for a long and trouble-free life, corrosion and abrasion-resistant parts, pumping capacity/discharge of pump 350 L /Min to 500 L /min, at respective head 220 m-190 m, multistage, outlet size 80 mm, Sand Fighter designs - Innovative Sand Fighter Designs restrict the entry of sand in motors, protect the pump and motor bushes to perform well in sandy bore wells, and increase the pump set life, Dynamically Balanced Rotating Parts - Minimum vibrations protect components from damage during operation, resulting inconsistent performance as concentricity is maintained, Longer and Trouble-Free Life - High-grade engineering materials like Graded Cast Iron Components, Stainless Steel Shaft, Noryl Impellers, Bronze Bushes, Heavy duty Carbon + SS Thrust Plate, 99.9% Electro Grade Copper Rotor and Winding Wires for longer and trouble-free life complete all as specified and directed |
| 12 | S&F 10 Sqmm X 3 Core Flat Submersible Cable as per IS:694/1990 with multi-stranded copper conductor 1100 volts grade heavy duty including all accessories for connection pump from panel board, testing and commissioning complete all as specified and directed. |
| 13 | S&F heavy duty galvanised iron column pipe of size 80 mm dia 3 metre long both end flanged, welded suitable for submersible pump having suitable cuts for passing through submersible cable including nuts, bolts & rubber gasket complete all as specified and directed by Engineer-in-Charge. |
| 14 | Supply and erection of housing clamp fabricated out of MS flat iron bend to shape 50 mm x 80 mm thick including nuts , bolts and washers as per IS-2800. |
| 15 | M & L for Construction of foundation of tube well of size 1.00 m x 1.00 m having 0.5 m thick PCC 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) over 75 mm thick PCC 1:3:6 type C-2 with GI Pipe 80mm dia medium grade 4 Nos embedded through out the block with GI plug and socket fixed on end and all as directed. |
| 16 | Supply, erection, testing and commissioning of pressure gauge (0 to 10.6 kg/sqcm) complete with needle valve and connection pipe complete all as specified and directed. |
| 17 | M & L for Strata sample wooden box made of deodar wood with glazed shutter and pigeon hole for every three metre depth including marking complete all as specified and directed by Engineer-in-Charge. |
| 18 | M&L for Testing of water from approved Govt Lab for potability by doing chemical analysis as per norms of WHO and submitting of test reports to the entire satisfaction of Engineer-in-Charge. |
| 19 | M&L for preparation & installation of strata chart of ground data showing different type of strata and selection of casing pipe on good quality Rig sheet paper, duly framed with glazed front side size of chart paper ( 80 cm x 30 cm) complete all as specified and directed by Engineer-in-Charge. |
| 20 | Supply and laying steel water tubing , 80 mm nominal bore medium grade , ISI marked as per IS-1239 Part-I galvanised with all fittings such as bends, tees, elbows, reducers, unions, plugs, sockets, etc, laid in trenches complete all as specified and directed by engineer-in-Charge. |
| 21 | Supply, Installation, testing and commissioning of LT panel board outdoor cubical type IP55 protection, vermin and dust proof factory made of CRCA sheet 3.15 mm thick back door detachable type fixed with nuts and bolts and front door fixed with hinges and knobs, powder coated for 3 Phase 415 volts,50 Hz, AC supply complete all as specified and directed by Engr in Charge and comprising of the following:-(a)Copper Bus bar fixed on epoxy insulators capacity 200 Amp and bakelite insulation sheet at the back with coloured tape - 01 Set (3 phases and one neutral)(b) Incoming MCCB 100 Amp 25 KA capacity - 01 No.(c) Out going MCCB 63 Amp 4 P 25 KA with thermal and magnetic release -02 Nos (one working + one standby)d) Outgoing MCB TP 32 Amp 06 KA capacity - 02 Nose) Electronic Digital type Ammeter flush type 0-300 Amp with selector switch and CTs. - 02 Nosf) Electronic Digital type Voltmeter flush type 0-500V with Selector Switch-02 Nosg) Set of indicator lamp RYB - 01 Seth) FASD Motor Starter upto 30 HP ML -3 with suitable relay sheet metal encloser -j) Fully automatic phase sequence corrector to correct input reverse phase and also protect against single phasing voltage unbalancing, low/ high voltage, Earth fault protection, short circuit protection and with time delay 4 to 7 seconds and automatic digital timer switch with automatically on/off the motor starter 30 HP as per time setting - 01 No.k) Dry run protection (An electrode sensor shall be lowered along with bore well for sensing of low water level.l) Complete internal wiring with suitable size copper conductor including cable lugs,glands etc.Note :-(i) Earth work, PCC base etc is deemed to be included with unit rate of item.(lIl All MCCB to be installed vertically therefore panel shall be designed accordingly. |
| 22 | Supply, Installation, testing and commissioning of LT panel board outdoor cubical type IP55 protection, vermin and dust proof factory made of CRCA sheet 3.15 mm thick back door detachable type fixed with nuts and bolts and front door fixed with hinges and knobs, powder coated for 3 Phase 415 volts,50 Hz, AC supply complete all as specified and directed by Engr in Charge and comprising of the following:-(a)Copper Bus bar fixed on epoxy insulators capacity 200 Amp and bakelite insulation sheet at the back with coloured tape - 01 Set (3 phases and one neutral)(b) Incoming MCCB 200 Amp 25 KA capacity - 01 No.(c) Out going MCCB 100 Amp 4 P 16 KA with thermal and magnetic release -03 Nos (Two working + one standby)d) Electronic Digital type Ammeter flush type 0-300 Amp with selector switch and CTs. - 02 Nose) Electronic Digital type Voltmeter flush type 0-500V with Selector Switch- 02 Nosf) Set of indicator lamp RYB - 01 Setg) Complete internal wiring with suitable size copper conductor including cable lugs,glands etc.Note :-(i) Earth work, PCC base etc is deemed to be included with unit rate of item.(lIl All MCCB to be onstalled vertically therefore panel shall be designed accordingly. |
| 23 | Supply and Laying Cable XLPE insulated screened PVC bedded galvanized steel strips or wire armoured, cables (heavy duty) ISI marked with stranded aluminium conductor, 95 Sqmm 3.5 core, 1100 volts grade and connecting and testing in trenches, under floors/ roads or on walls. Note : Earth work, excavation shall be measured & paid separately under respective item of Schedule. |
| 24 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for foundation/ cable trench, not exceeding 10 Sq mm on plan and getting out in soft/loose soil complete all as specified and directed. |
| 25 | Returning, filling in, including spreading, leveling and well ramming in layers not exceeding 25 cm thick in soil complete all as specified and directed. |
| 26 | Removal of surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed |
| 27 | Supplying, spreading and punning sand for cushioning to cables in trenches complete all as specified and directed. Note: Punned thickness will only be measured |
| 28 | M&L for brick protection with sub Class'B' bricks old size laid dry, flat over cable perpendicular across the cable in trenches complete all as specified and directed. |
| 29 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed. |
| 30 | Schedule of Credit Total in Figures 0.0 0.0 0.0 Quoted Rate in Figures Select 0.0 0.0 Zero Only 0.0 Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |