| 1 | Rewiring for light point/ fan point/ exhaust fan point/call bell point with 1.5 sq.mm FRLS/HFFR PVCinsulated copper conductor single core cable and 1.5sq.mm FRLS/HFFR PVC insulated copper conductorsingle core cable as earth wire in existing surface/recessed steel/PVC conduit including dismantling asrequired. |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required.a)3 x 4 sq. mm (Circuit wiring and Power wiring) |
| 3 | b)2 X 6 sq. mm + 1 X 6 sq. mm earth wire for submain wiring (Excluding conduit) |
| 4 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 5 | Supplying and fixing following piano type switch/socket on the existing switch box/cover i/c connections etc as reqd.a) 5/6 A Switch |
| 6 | b)3 pin 5/6 A socket outlet |
| 7 | c)15/16 A switch |
| 8 | d)6 pin 15/16 A socket outlet |
| 9 | Supplying and fixing of minimum 3mm thick phenolic laminated sheet cover i/c cutting for fixing switch , socket , drilling holes etc as required. surface or recess on different size of metal boxes etc as reqd. |
| 10 | Supplying and fixing of following ways surface/ recessmounting, vertical type, 415 V, TPN MCB distributionboard of sheet steel, dust protected, duly powderpainted, inclusive of 200 A tinned copper bus bar,common neutral link, earth bar, din bar for mountingMCBs (but without MCBs and incomer ) as required .(Note : Vertical type MCB TPDB is normally usedwhere 3 phase outlets are required.) |
| 11 | Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earthbar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator)8 way , Double door |
| 12 | Supplying and fixing following way, single pole and neutral,sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earthbar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator)12 way , Double door |
| 13 | Providing and fixing following rating and breaking capacity andpole MCCB with thermomagnetic release and terminalspreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required a)100 A,30KA,FPMCCB |
| 14 | Supplying & fixing 5 AMP to 32 AMP rating 240 /415 volt 'C' curve MCB sutiable for inductive road of following poles in the existing MCB DB complete with connections testing and commisoning etc as reqd.a) Single pole |
| 15 | b) Double pole |
| 16 | Supplying and replacement of 1200 mm sweep size ceiling fan i/c connection, testing etc complete as reqd. |
| 17 | Supplying and installation of 300 mm sweep extra size exhaust fan i/c connection, testing etc complete as reqd. |
| 18 | Supplying and fixing of following sizes of PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as req 20 mm |
| 19 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80 , Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K / 5700°K /6000°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm)18- 22 Watt |
| 20 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP 66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C) 90 Watt |
| 21 | Supplying and fixing of MS pipe of 50 mm dia having 1.5 mtr length to mount the LED fixture i/c clamping , fixing and connection etc, as required, |
| 22 | Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3 x 1.5 sq. mm |
| 23 | Supplying and fixing of following sizes of PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as req 20 mm |
| 24 | Overhead laying and fixing of one number PVC insulated and PVCsheathed / XLPE power cable of 1.1 KV grade offollowing size on street light poles ( i/c tower wagon) |
| 25 | Supplying and fixing of PVC box of size 8 inch x 6 inch x 4 inch on street light poles with fixing arrangement, 2 nos 16 Amp SP MCBs, 2/4 way strip connector i/c testing & connection etc complete asrequired(i/c clamp for cable fixing) |
| 26 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 27 | Providing and fixing 25 mm X 5 mm G.I. strip onsurface or in recess for connections etc. as required |
| 28 | Providing and laying in position 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) reinforced cement concrete foundation slab of size 1300mm x 1000 mm x 500 mm deep) including excavation of earth, refilling, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 16mm. dia-1400mm long (approx) 8Nos, and reinforcement ring of cold twisted bar of 10mm dia -3400mm long (approx) -12 nos, (with suitable spacing) including centering & shuttering as required with providing, fixing and positioning of one set of foundation bolts comprising of 4 nos., 24 mm dia, 500 mm long J-Type MS bolts ( additional 100 mm Threaded portion shall be galvanized) along with 3 nos. GI nuts and 2 nos. GI washers etc. per bolt and 1 no. anchor plate (3mm thick) of suitable size. |
| 29 | Shifting & Installation of 7 mtr old GI poles from office store to site ( within 5 km) including testing , commissioning & etc complete as required |
| 30 | Supplying & fixing of hot dip Galvanized minimum 1000 mm long bracket made out of suitable sized round pipe B-Class on octagonal pipe (3.60 mm Thick), 48 mm outer dia with canopy 300 mm long galvanized overhang with tightening bolts etc. as reqd. Tilt angle shall be around 10 degree.a) double arm bracket Please Enable Macros to View BoQ information |