| 1 | Survey, Supply, Installation , Testing and Commissioning for 2 nos of 33 kV Line BAY (LILO) at Receiving Station Kud and Patnitop |
| 2 | 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) SCADA compatible Make Megawin, Crompton Greaves, Electricfield or Equvalent . |
| 3 | 33kv Isolator with Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ). |
| 4 | 33kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ). |
| 5 | 33 kV Current transformer (33kv,1 phase multi ratio multi core, outdoor) 1 no per phase |
| 6 | 30 kv Lightening arrestors (30kv,10KA, Polymer, station class, ZnO)gap less |
| 7 | 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible.Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc . |
| 8 | 33 KV voltage transformer(33kv/110 V, 1 phase, multicore, outdoor)1 no per phase |
| 9 | 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m station type |
| 10 | CONTROL CABLES : i) 12 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 11 | ii) 4 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 12 | iii) 2 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 13 | Galvanised Pipe/ Steel Structures |
| 14 | Galvanised Nuts & Bolts |
| 15 | Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor( 200 mtr),including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job |
| 16 | Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat. |
| 17 | Earthmat by Using G.I. Flat of Size 50 mm x 8mm as grounding Conductor.The mesh Size shall 1 m x 1 m.The Burial Depth of G.I. Flat Shall be minimum 600 mm.The work involves the excavation of trenches for burial of grounding flat,Laying of G.I.Flat including welding & Backfilling of Trenches including earth electrodes(3mm x 40 mm GI pipe). |
| 18 | Survey, Supply, Installation , Testing and Commissioning of 33 KV XLPE Cable |
| 19 | 33kV 3 core Al XLPE 185 sqmm , Armoured, FRLS Cable |
| 20 | 33 kV Indoor Heat Shrinkable Cable Kits for 185 sqmm three core(outdoor) |
| 21 | Shifting of Auxillary Transformer at R/ Stn Patnitop(complete job with earthing) |
| 22 | Survey, Supply, Installation , Testing and Commissioning for Shifting OF 11 KV/ LT LINE coming in the alignment |
| 23 | Supply, Transportation, Erection of 8 Mtr Long ST Poles (ST410-SP56) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 24 | GI Mukhi clamp for shackle insulator / GI Channel iron X-arm of different sizes including clamps,Ties and braces |
| 25 | Shackle Insulator |
| 26 | 30 mm2 ACSR Conductor |
| 27 | Galvinized Nuts and Bolts |
| 28 | Dismantling of existing poles along with allied material and conductor coming in the alignment of 33 KV Line |
| 29 | Survey, Supply, Installation , Testing and Commissioning for Erection OF 33 kV LINE |
| 30 | Supply, Transportation, Erection of 11 Mtr Long ST Poles (ST410-SP56) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 31 | Supply, Transportation, Erection of 13 Mtr Long ST Poles (ST410-SP69) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 32 | GI Channel iron X-arm of different sizes(100 x 50 x 6 mm) and angle iron of sizes (65 x 65 x 6 mm) including clamps,Ties and braces for multi pole structures |
| 33 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 34 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fittings |
| 35 | PG clamps for 100 mm2 ACSR Conductor |
| 36 | Galvinized Nuts and Bolts |
| 37 | Danger Plates with Clamps |
| 38 | Anti-Climbing Device with Clamps |
| 39 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip. |
| 40 | Painting of Poles with Red Oxide and aluminium paint (min 2 coats each) |
| 41 | Cement bottoming 1:2:4 mix as per REC standards .6cum/pole (to be done during erection of poles) |
| 42 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 43 | 100 mm2 ACSR conductor |
| 44 | Guard netting |
| 45 | Creation of Isolation points along the line by way of 33 KV Isolators without earthing blades on ST 11 Mtr Poles and MS Steel etc. Complete job. Please Enable Macros to View BoQ information Compatibility Report for DhunaBOQ.xls Run on 10-07-2021 14:05 The following features in this workbook are not supported by earlier versions of Excel. These features may be lost or degraded when you save this workbook in an earlier file format. Significant loss of functionality # of occurrences This workbook contains data in cells outside of the row and column limit of the selected file format. Data beyond 256 (IV) columns by 65,536 rows will not be saved. Formula references to data in this region will return a #REF! error. 6.0 'BoQ1'!L40 'BoQ1'!F40 Any effects on this object will be removed. Any text that overflows the boundaries of this graphic will appear clipped. 3.0 'BoQ1'!A1:II42 Minor loss of fidelity Some formulas in this workbook are linked to other workbooks that are closed. When these formulas are recalculated in earlier versions of Excel without opening the linked workbooks, characters beyond the 255-character limit cannot be returned. 5Defined Names Some cells or styles in this workbook contain formatting that is not supported by the selected file format. These formats will be converted to the closest format available. 14.0 |