| 1 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core, complete all as specified and directed. |
| 2 | M&L for FRP junction box of size 30 x 25 x 15cm, four strip aluminium bus bar of capacity 63 Amps mounted on epoxy insulators weather proof, MCB SP 6 Amps -01 No including provision for fixing to electric poles with 02 Nos MS clamps of flat 40 x 6mm suitable size complete with nuts & bolts making connection with cable & including thimbles at suitable size, complete all as specified and directed. |
| 3 | Supply and fix in replacement of LED street light fitting 90 watts, made in pressure diecast housing with eppoxy power coated dark graphite grey colour finish.prismatic polycarbonate cover with individual LED lenses with IP 66 complete with all accessories and necessary fixing arrangement on pole at any height and removing old unserviceable street light fitting, complete all as specified and directed. |
| 4 | M&L for steel tubular swaged poles errected to truly vertical position with 6mm thick mild steel base plate of size 300mm x300mm, welded to Pole, B-118 finial taper plug, bolts, nuts and screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II, type 410-SP-31 (9m long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint internally and portion embedded in concrete, making five black and white bands at lower portion of pole each 300mm wide at 300mm spacing alternately and marking pole number. with black paint at suitable height including taking down old unserviceable broken PCC pole of 9 mtr long, complete all as specified and directed.(Note :- Necessary excavation of earth work, removing, returning filling in, PCC foundations of poles, coping etc shall be measured and paid separately) |
| 5 | Supply and fixing PVC 3 core aluminium cable for connecting security lights to junction box of size 1.5 sq mm, complete all as specified and directed. |
| 6 | S & F Street light bracket made out of 32 mm dia GI light grade pipe 1.2 mtr long bend to shape 120 degree and duly fixed alongwith pole / bldg with the help of 2 Nos of MS clamp of sizes 25x3 mm including suitable size of bolt, nuts, and washers, complete all as specified and directed. |
| 7 | Dismantling of overhead ACSR conductor of any size including removing of PG Clamps jumpering etc and kept in safe custody for reuse serviceable ACSR in the work & removing unserviceable conductor from site, complete all as specified and directed. |
| 8 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core, complete all as specified and directed. |
| 9 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core, complete all as specified and directed. |
| 10 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 sq mm 4 core, complete all as specified and directed. |
| 11 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 sq mm 2 core, complete all as specified and directed. |
| 12 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured , electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sq mm 2 core, complete all as specified and directed. |
| 13 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth for laying of cable and foundation of poles stays and getting out in soft /loose soil, complete all as specified and directed. |
| 14 | All as per item No 13.00 here-in-before but exceeding 1.5 m and not exceeding 3 m in depth. |
| 15 | Returning filling in trenches including spreading leveling watering and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed. |
| 16 | Removing of excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed. |
| 17 | M & L for sand cushioning to underground cable, provided with a layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable, complete all as specified and directed.Note: Punned thickness of sand shall be measured for payment purpose. |
| 18 | Supply and laying brick covering with width equal to length of brick as mechanical protection to cable using sub class ‘B’ bricks laid flat, size 230mm x 115mm x 75mm, complete all as specified and directed. |
| 19 | Supply & Laying in GI tubing light grade of 40 MM with necessary fittings as in cable protection in trenches/fixed on wall / floor including necessary clamps bolts and nuts, complete all as specified and directed. |
| 20 | M&L for PCC 1:4:8 (nominal mix) type D-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete of poles and stay/installation paths, complete all as specified and directed. |
| 21 | M&L for plain cement concrete type C-1, 1:3:6 (using 20mm graded stone aggregate) as in poles foundation including necessary form work, complete all as specified and directed. |
| 22 | M&L for plain cement concrete type B-1, 1:2:4 (using 20mm graded stone aggregate) as in coping of poles, benching, hold fasts, water troughs, bed block and the like including weathering, slightly rounded or chamfered angles and throating including necessary form work, complete all as specified and directed. |
| 23 | Supply, installation, testing and commissinoning LT Feeder Pillar box outdoor type of size 1000mm x1000mmx600 mm suitable for working on 3 phase ,4 wire ,415 volts AC, 50Hz ,outdoor cubical type, and tested at CPRI, Outer shell shall be made out of 3.15mm thick CRCA sheet & MS angle iron frame duly powder coated of size 50 x 50 x 6mm frame, with front & back open, double door system lockable, inner shell shall be made out of 2.0 mm thick CRCA sheet and completely vermin & dust proof, entry holes for incoming & outgoing cables as approved by GE. Panel shall have bus bar chamber and switch gear compartment, hinged door with rubber gasket, earthing terminals, and consisting of following: |
| 24 | Incoming MCCB(a) MCCB 200 Amp,4 pole, 50 HZ,415 V having rupturing capacity 35 KA-01 Nos as incoming (thermal magnetic) release and adjustable on load.Outgoing MCCB.(a) MCCB 100 Amp,4 pole, 50 HZ,415 V having rupturing capacity 35 KA-04 Nos as outgoing (thermal magnetic) release and adjustable on load.(b ) MCCB 4 pole 40 amps - 0 2 Nos.(c) Digital voltmeter (0-500) & Digital Ammeter (0-100) Amps with suitable CTs.(d) LED phase indication lamps RYB-01 set(e) Internal wiring with PVC insulated copper conductor multi stranded cable 1100 volts grade and Cupper Bus Bar including Painting etc.(f) Copper bus bar ,TPN 400 Amp rating -04 Nos |
| 25 | Notes: (i) Rates are deemed to be inclusive of PCC platform of suitable size of 45 cm height and 04 nos legs of 50 mm x 50 mmx6mm & 60 cm height for fixing the panel (ii) MCCB & MCB shall be fixed in suitable sheet metal enclosure made up of 3.15mm thick CRCA sheet. (iii) Danger notice plate (02) Nos LT size 20 cmx 15 cm shall be fixed on the panel. (iv) Panel shall be from CPRI approved make. (v) make of panel and drawing shall be approved from GE before placing order for procurement. |
| 26 | Supply, install,testing and commissioning of factory made bus bar chamber panel of size 600mm x900mmx350mm(CPRI approved outdoor type 3.15 mm qith four strips 200 Amps bus bar aluminium with MCCB 40 Amp,FP 16 KA adjustable type duly connected to aluminium strip at incoming side with suitable space for 2 incoming cable and outgoing of cable 2 cable bus bar fixed on insulators in zig zag position,clearance in each strip and clearance in both side should not be less than 125mm with sufficient working space,height of bus bar chamber not less than 1 mtr, mounted on MS angle 50 x50x6mm made of CRCA sheet 2mm thickoutdoor type powder coated after seven tank process both side opening shutter in two parts,cable opening from bottom side with indicators RYB hinges through out the length of shutter with half turn locking arrangements including grounting in PCC, including taking down old bus bar chamber, complete all as specified and directed. |
| 27 | M & L for earthing complete with galvanized steel earth plate eletrode 60cmx60cmx6mm thick buried dirctly in ground vertically (earth pit not less than 2.25 mtr below ground level) with top edge of plat not less than 1.5 mtr below ground level connected to GI earth strip 25x4mm by means of bolts. nuts,check nuts and washers etc including protection pipe 40mm bore GI light grade up to 7.5m length, provision the earth lead to earth connection in ther main distribution box with lugs and GI nuts, bolts, earthing shall be done all as per shown electrical plate No 3 of SSR part 1 Including neccessary excavation in soft disintergrated rock and provision of 20mm dia GI pipe medium grade with funnel for watering, PCC earth chamber of 40mm thick precast RCC cover with suitable precast RCC frame and earth test point and testing in presence of Engr -in -Charge, complete all as specified and directed. Please Enable Macros to View BoQ information |