| 1 | Note - Only Electric Poles & conductor will be provided by SECL. |
| 2 | Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand :6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. Above 10.00 metre and upto 12.00 metre |
| 3 | Erection of steel tubular or rail pole strut in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling and secured with holding clamps, bolts, nuts, etc. as required. (Above 12 meter height upto 16 meter ) |
| 4 | Supplying and erection of galvanised stay set for 11 KV over head lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 4.00 mm dia G.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required. |
| 5 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) V shape cross arm for two 11 KV over head line conductors complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc. as required . |
| 6 | Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) pole top bracket/ cross arm for single 11 KV over head line conductor complete with 50 mm X 6mm flat iron clamp,bolts, nuts and washers including drilling holes for insulator pins, bolts and nuts etc as required . |
| 7 | Erection of pole top/ straight two wire/ V shape two wire, angle iron/ channel iron, cross arm on steel tubular/ rail/ PCC pole for 11/22/33 KV as required. |
| 8 | Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) double pole cross arm for three wire 11KV over head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/ fittings, bolts, nuts and washers etc. as required . |
| 9 | Erection of double pole 3 wire cross arm for 11KV/ 22KV/ 33 KV over head lines as required. |
| 10 | Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required. |
| 11 | Supplying and erection of 11 KV disc insulator for 11 KV over head lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required. |
| 12 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, Al/Cu conductor cable of upto11 kV grade as required: Upto 70 Sq. mm |
| 13 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, Al/Cu conductor cable of upto 11 kV grade as required: upto 70 sq. mm |
| 14 | Supplying and fixing of light class G.I. pipe of 100 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required. |
| 15 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of upto 11 kV grade of following size in the existing masonry open duct as required : upto 120 sq. mm (For HT Cu Cable) |
| 16 | Erection/ Stringing of ACSR Dog Conductor including binding etc. as required |
| 17 | Erection/ Stringing of ACSR Rabbit Conductor including binding etc. as required including Running conductor as required |
| 18 | Transportation of new /old electric HT poles within mine boundary / switchyard /workshop (departmental veh. will be provided by SECL) |
| 19 | Supply of 8 SWG GI Wire for running earth and pole earthing |
| 20 | Erection of G.I. Wire No. 8 SWG including binding etc. as required for running earth and pole earthing etc. |
| 21 | Dismantling of overhead lines comprising of Aluminium overhead line , GI wire, Cross arm , insulator , cross arm etc. |
| 22 | Dismantling of pole standard/strut embedded in cement concrete foundation etc. as required |
| 23 | Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, upto 11 KV overhead lines with rated voltage 6 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required. |
| 24 | Supply & Erection of Carpar Cradel Guarding with required GI wire , 1.5 meter angle bracket , clamp nut bolts & binding etc. |
| 25 | Tree branch cutting , bush cutting , cleaning & clearing site suitable for HT OHL installation including VCBs, Substations, exisitng/old HT line inside mine at interval of 03 months |
| 26 | Painting of HT pole upto height of 10 meter above ground & Numbering of pole |
| 27 | Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 28 | Supply & fixing of Barbered wire anti climbing arrangement at each pole |
| 29 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 30 | Shifting , erection & commissioning of 25 / 63/ 100 KVA/200/315/500 KVA Transformer on existing strucutre including Bi-metallic Clamp , ACSR/AAAC conductor i/c colour code sleeve for connection form HT line to Transformer as required |
| 31 | Supply installtion testing commissioing of DO fuse assembly with brass part contact for 11KV DP strucutre set of 03 nos. with fuse barrel i/c required fuse element & other material as per specification on exisitng DP structure as required |
| 32 | Supplying installing, testing & commissioning of outdoor H.T., AB switch assembly set gang operated with brass contact parts, including required GI pipe operating rod, handle & locking arrangement on OnOff position conforming to IS complete with required material and installing on existing DP structure to complete the job as required as per specification.(Set of3 nos.) 11 KV 400 Amp |
| 33 | Total impact of GST for the purpose of CTC Please Enable Macros to View BoQ information |