| 1 | Supplying. erecting & terminating FR XLPE insulated. galvanised steel formed wire armoured (strip) cable. 1100 V 4 core 16 sq. mm. aluminium conductor complete erected with glands & lugs on wall/trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL DSR NO.7-1-29 |
| 2 | Making trench in Soft soil having 0.75m depth and minimum 0.3m width forlaying provided cables up to voltage level of 1.1kV complete as per specification no. CW-EXN-CTR DSR NO.16-1-1 |
| 3 | Supplying & erecting three phase, 415V, street light control panel upto the max load of 6kW, TPN MCB 40A. powder coated CRCA 14 SWG sheet, outdoor Type, having IP54. IK10 protection, suitable rating contactor, 24 hrs. astronomical time switch with minimum 5 years battery back up, auto/manual selector 3 switch. ON/OFF push buttons, indicator lamps, control wiring, metering device, etc. for automatic operation Witil overentem, short circuit, earth fault protection.on. provided iron frame / C foundation as per specification SW-STCP.DSR NO.5-2-5 |
| 4 | Supplying and erecting LED Strip light Max. 95 W IP20 class having minimum lumens output of 1600 Lumens/m, min. efficacy of 90 lumen/W.CRI>80, CCT upto 5000K, Beam Angle of 110 deg., THD<10%, p.f. >0.95, operating range of 230-270V, Life class of 30,000 Hrs at L70B50 including driverwith uninimum 1 year warranty as per specification No. FG-IDF/LED.. DSR NO.2-1-11 |
| 5 | Supplying & erecting mains with 2x2.5 sqimm FRLSH copper PVC insulated wire laid in provided 5 conduit/trunking/inside pole/bus bars, or any other places, as per specification no. WG-MA/BW DSR NO.1-3-2 |
| 6 | Supplying & erecting mains with 2x4 sq.mrı FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places, as per specification no. WG-MA/BWDSR NO.1-3-3 |
| 7 | Supplying and erecting PVC trunking (PVC casing-n-capping) of size 20mm with accessories on wall/ceiling as per specification no. WG-MA/CON.DSR NO.1-2-6 |
| 8 | Supplying and erecting PVC Surface modular switch box with double mounting plate for 4 module complete. DSR NO.1-6-29 |
| 9 | Supplying and erecting 6 to 32A. 10kA, SPMCB suitable to fix in 1 module of modular switch in provided box complete & duly concealed with necessary material and connected. DSR NO.1-6-44 |
| 10 | Supplying and erecting integrated LED flood light fitting Max, SOW IP65 & IK07 class having pressure dic-aluminium housing, having system lumens output of Min. 5000 Lumens, min. efficacy of 100 lumen/W, CRI>70. CCT upto 6500K. THD<10%, p.f. >0.90, operating range of 140-270V, inbuilt surge protection of 4 kV. Life class of 50.000 Hrs at L70B50 including cdriver with U shaped bracket with minimum 2 Years warranty as per specification No. FGODF/FL.DSR NO2-3-13 |
| 11 | Supplying, erecting, testing & comunisioning metal work in CRCA sheet including Iron work for supports with fabrication of boxes, panel boards, etc. including cutting. 11 bending. drilling welding, riveting, treated with anti-rust treamer and painted with one coat of red lead paint and roats of enamel paint or powder coating complete as per specification no. CP/SH/CR DSR NO.6-1-1 Please Enable Macros to View BoQ information |