| 1 | Taking down carefully old LT cable of size 400 Sqm 3.5 core laid in trenches/ air/ on wall / in ducts complete all as specified and directed.Note:- Earth work shall be measured & paid seperately under relevent item.. |
| 2 | All as per items No. 1 above but 300 Sqmm 3.5 core. |
| 3 | All as per items No. 1 here-in-before but 240 Sqmm 3.5 core. |
| 4 | All as per items No. 1 here-in-before but 185 Sqmm 3.5 core. |
| 5 | All as per items No. 1 here-in-before but 150 Sqmm 3.5 core. |
| 6 | All as per items No. 1 here-in-before but 120 Sqmm 3.5 core. |
| 7 | All as per items No. 1 here-in-before but 95 Sqmm 3.5 core. |
| 8 | Excavation in trenches in hard/dense soil not exceeding 1.5 mtr wide and not exceeding 1.5mtr depth for foundation etc or for shafts, wells, cesspits, manholes, pier holes etc and getting out complete all as specified and directed. |
| 9 | Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and directed. |
| 10 | Removing excavated soil to a distance not exceeding 50 metere and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed. |
| 11 | M&L for Sand cushioning using with Ganga sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable completed all as specified.Note:- Punned thickness shall be considered for payment. |
| 12 | M&L for for Factory made unreinforced precast concrete cable covers conforming to IS:5820, class LV, Type I, flat, size 250 mm x 150mm x 40mmfor cable protection complete all as specified and directed. |
| 13 | M&L for cutting of PCC/Hard standing/WBM road not exceeding 30 cm in width not exceeding 60 cm in depth for passing of HT cable and making good of disturbed surface to match with the existing surfaces by using old and new material i.e bitumen/PCC (1:3:6) type C-1 complete all as specified and directed. |
| 14 | M&L for Boring of holes under road pavement hard standing by trenchless technology using ultra sound technic and necessary machine exluding GI pipe of 100 mm dia suitable for 0.4 mpa working pressure upto 2mtr deep, complete all as specified and as directed |
| 15 | Supply and lay GI pipe light grade of following size 100 mm for cable protection laid in trenches or fixed on poles/wall with & including suitable size of F1 clamp, nut, bolt etc, complete all as specified and directed. |
| 16 | Supply and lay GI pipe light grade of following size 80 mm for cable protection laid in trenches or fixed on poles/wall with & including suitable size of F1 clamp, nut, bolt etc, complete all as specified and directed. |
| 17 | Supply and lay GI pipe light grade of following size 50 mm for cable protection laid in trenches or fixed on poles/wall with & including suitable size of F1 clamp, nut, bolt etc, complete all as specified and directed. |
| 18 | Supply and lay GI pipe light grade of following size 40 mm for cable protection laid in trenches or fixed on poles/wall with & including suitable size of F1 clamp, nut, bolt etc, complete all as specified and directed. |
| 19 | Re-laying, jointing and testing of old surviceable LT cable 400 sqmm 3.5 core at existing/ new location, complete all as specified and directed. |
| 20 | Re-laying jointing and testing of old serviceable LT cable 300 Sqmm 3.5 core at existing/ new location, complete all as specified and directed. |
| 21 | Re-laying jointing and testing of old serviceable LT cable of 240 Sqmm 3.5 core at existing/ new location, complete all as specified and directed. |
| 22 | Re-laying jointing and testing of old serviceable LT cable 185 Sqmm 3.5 core at existing/ new location, complete all as specified and directed. |
| 23 | Re-laying jointing and testing of old serviceable LT cable of 150 Sqmm 3.5 core at existing/ new location, complete all as specified and directed. |
| 24 | Re-laying jointing and testing of old serviceable LT of 120 Sqmm 3.5 core cable at existing/ new location, complete all as specified and directed. |
| 25 | Re-laying jointing and testing of old serviceable LT cable of 95 Sqmm 3.5 core at existing/ new location, complete all as specified and directed. |
| 26 | Supply, laying, jointing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 sq mm 3.5 corecomplete all as specified and directed. |
| 27 | All as per items No. 26 above but 300 Sqmm 3.5 core. |
| 28 | All as per items No. 26 here-in-before but 240 Sqmm 3.5 core. |
| 29 | All as per items No. 26 here-in-before but 185 Sqmm 3.5 core. |
| 30 | All as per items No. 26 here-in-before but 150 Sqmm 3.5 core. |
| 31 | All as per items No. 26 here-in-before but 120 Sqmm 3.5 core. |
| 32 | All as per items No. 26 here-in-before but 95 Sqmm 3.5 core. |
| 33 | M&L for Earthing complete with GI earth plate electrode of size 600 mm x 600 mm x 6 mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.65 Mtr below normal ground level connected to GI strip 32 x 6 mm size and earthing lead protected with 50 mm dia GI pipe light grade filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC 1 : 3 : 6 type C1. using 20 mm graded stone aggregate in concrete pit pre-cast RCC 40 mm thick reinforced with 6 mm dia round at the rate of 75 mm C/C both way with 12 mm dia mild steel plain bar lifting handle 2 Nos funnel with wire mesh 20 mm dia GI pipe light grade watering pipe and frame work complete all as shown in electrical plate No. 5 of SSR Part - I 1991 including testing complete. (GI strip upto 7.5 m length in included in unit rate quoted by contractor and beyond this lengths the same shall be measured & paid separately. Please Enable Macros to View BoQ information |