| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Repair /Replacement of LT Security Light/ Perimeter Security Light of Northern Part under GE (Utilities) Udhampur Contract No: GE/U-27/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Taking down carefully Unserviceable Security light 60/90/120/150 watt /Flood Light/ High Mast light fitting from pole/Structure complete all as specified and directed by Engineer-in-charge. |
| 3 | Refixing the U/S light fitting after visual inspection at complaint cell/power house and replacing the unservicable parts such as Driver,SPD,Connecting wires, nut,bolts/ Screws as per requirement and connecting accesories such cables conductors 2.5 sqmm/4sqmm,drivers, service brackets along with nut bolts etc without any extracost to the contractor by the department complete all as specified and directed by Engineer-in-charge. |
| 4 | Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cable PVC tape PVC sheathed 2.5 Sqmm aluminium solid conductor 2 core nominal cross section laid in trenches/fixed to walls/ passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specified and directed by Engineer-in-charge.Make :KEI/Polycab/Havells |
| 5 | Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cable PVC tape PVC sheathed 4 Sqmm aluminium solid conductor 2 core nominal cross section laid in trenches/fixed to walls/ passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specified and directed by Engineer-in-charge.Make :KEI/Polycab/Havells |
| 6 | Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cable PVC tape PVC sheathed 6 Sqmm aluminium solid conductor 2 core nominal cross section laid in trenches/fixed to walls/ passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specified and directed by Engineer-in-charge.Make :KEI/Polycab/Havells |
| 7 | Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cable PVC tape PVC sheathed 10 Sqmm aluminium solid conductor 2 core nominal cross section laid in trenches/fixed to walls/ passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specified and directed by Engineer-in-charge.Make :KEI/Polycab/Havells |
| 8 | S&F in replacement modular box of size 333 x 233 x 120 mm made of FRP inpact resistance plastic & heat resistant materials including MCB SP 6 A, Connector terminal block 4 pole 16 A capacity and fixing to the street light or post top light pole with suitable sizes of clamps, nuts and bolts complete all as specified and directed by Engineer-in-charge. |
| 9 | S&F in replacement MS bracket for street light fittings made out of 40 mm dia GI pipe of medium grade 1.5 mtr long each bent to required shape & size and fixed to pole with and including flat iron clamps 02 Nos made out of 32x6 mm flat iron including GI Nuts, bolts and washers and painting of clamps and street light brackets with two coat of aluminium paint over a coat of red oxide primer and fittings bracket to street light fittings complete all as specified and directed by Engineer-in-charge. |
| 10 | S&F in replacement 250 Watt LED Flood light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 110 lumen/Watt (Minimum lumen output of luminarie should be 13200 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specified and directed by Engineer-in-charge.Make : Crompton/Bajaj/Philipsor/Wipro |
| 11 | S&F in replacement 200 Watt LED Flood light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 110 lumen/Watt (Minimum lumen output of luminarie should be 13200 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specified and directed by Engineer-in-charge.Make : Crompton/Bajaj/Philipsor/Wipro |
| 12 | S&F in replacement 150 Watt LED Flood light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 110 lumen/Watt (Minimum lumen output of luminarie should be 13200 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specified and directed by Engineer-in-charge.Make : Wipro (LF20-192-060-57-G2)/Bajaj/Philips. |
| 13 | S&F in replacement 120 Watt LED Flood light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 110 lumen/Watt (Minimum lumen output of luminarie should be 13200 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specified and directed by Engineer-in-charge.Make : Crompton/Bajaj/Philipsor/Wipro-(LR02-102-XXX-57-G2) |
| 14 | S&F in replacement 120 Watt LED street light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 9000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specified and directed by Engineer-in-charge.Make : Crompton/Bajaj/Philipsor/Wipro |
| 15 | S&F in replacement 90 Watt LED street light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 9000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specified and directed by Engineer-in-charge.Make : Crompton/Bajaj/Philipsor/Wipro |
| 16 | S&F in replacement 60 Watt LED street light (suitable for fixing on 40 mm dia MS pipe) Clamp with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 6000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specified and directed by Engineer-in-charge. Make : Crompton/Bajaj/Philipsor/Wipro-(LR02-102-XXX-57-G2) |
| 17 | S&F in replacement 45 Watt LED street light (suitable for fixing on 40 mm dia MS pipe) with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 6000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specified and directed by Engineer-in-charge.Make :Wipro-(LRO2-671-XXX-57-G3)/Bajaj/Philips. |
| 18 | Supply and fix 15/16 Watt new generation, Post top lantern, energy saving, enviornmentla friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminarie with high power LEDs with IP-65 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 1500 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided, complete all as specified and directed by Engineer-in-charge.Make : Crompton/Bajaj/Philipsor/Wipro |
| 19 | Supply and fix 35 Watt new generation, Post top lantern, energy saving, enviornmentla friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminarie with high power LEDs with IP-65 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 1500 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided, complete all as specified and directed by Engineer-in-charge.Make : Crompton/Bajaj/Philipsor/Wipro |
| 20 | Supply and Fixing 10/12 Watt Fantasy Bollard LB14 Bollard, LB14 Bollard, made of extruded aluminium housing, to redefine landscape with better light quality and enhance architectural dsign, rated IP65 complete all as specified and directed by Engineer-in-charge.Make : Crompton/Bajaj/Philipsor/Wipro |
| 21 | M&L in replacement of Aluminium lugs suitable for 630 sqmm copper cable including taking down the existing unserviceable one, complete all as specified and directed by Engineer-in-charge. |
| 22 | Description all as per Ser Item No 20.00 here-in-before, but of size 500 sqmm |
| 23 | Description all as per Ser Item No 20.00 here-in-before, but of size 400 sqmm |
| 24 | Description all as per Ser Item No 20.00 here-in-before, but of size300 sqmm |
| 25 | Description all as per Ser Item No 20.00 here-in-before, but of size185 sqmm |
| 26 | Description all as per Ser Item No 20.00 here-in-before, but of size 150 sqmm |
| 27 | Description all as per Ser Item No 20.00 here-in-before, but of size 120 sqmm |
| 28 | Description all as per Ser Item No 20.00 here-in-before, but of size 95 sqmm |
| 29 | Description all as per Ser Item No 20.00 here-in-before, but of size 70 sqmm |
| 30 | Description all as per Ser Item No 20.00 here-in-before, but of size 50 sqmm |
| 31 | Description all as per Ser Item No 20.00 here-in-before, but of size 35 sqmm |
| 32 | Description all as per Ser Item No 20.00 here-in-before, but of size 25 sqmm |
| 33 | Description all as per Ser Item No 20.00 here-in-before, but of size 16 sqmm |
| 34 | Description all as per Ser Item No 20.00 here-in-before, but of size 10 sqmm |
| 35 | Dismantling of unserviceable steel tubular pole swaged pole/PCC pole including PCC complete with acessories, complete all as specified and directed by Engineer-in-Charge. |
| 36 | Dismantling of old unserviceable/broken/jointed ACSR conductor or earth wire from poles and removing from site of work complete all as specified and directed by Engineer-in-Charge. |
| 37 | Taking down existing old cross arms of MS channel or angle sections etc complete all as specified and directed by Engineer-in-Charge. |
| 38 | Cleaning the existing exposed surfaces of steel tubular pole of 9.0 mtr long including cross arms, brackets, clamps etc and painting with two coats of synthetic enamel paint (Aluminium shade) marking five black & white bands at lower portion of pole, each 300 mm wide alternately and marking pole No. with yellow paint on black base at suitable height complete all as specified and directed by Engineer-in-Charge. |
| 39 | Supply, laying, jointing & testing in replacement XLPE insulated, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade cross sectional area 10 Sqmm 4 core laind in trenches or passing through pipe or fixed on poles complete all as specified and directed by Engineer-in-Charge. |
| 40 | Description all as per serial item No 38.00 here-in-before, but of size 16 Sqmm 4 core |
| 41 | Description all as per serial item No 38.00 here-in-before, but of size 25 Sqmm 4 core |
| 42 | Description all as per serial item No 38.00 here-in-before, but of size 35 Sqmm 3.5 core |
| 43 | Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and directed by Engineer-in-Charge. |
| 44 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes foundations of poles/stays/pipes etc .not exc 10 Sqm area on plan and getting out in soft/loose soil complete all as specified and directed by Engineer-in-Charge. |
| 45 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and directed by Engineer-in-Charge. |
| 46 | Removing of excavated soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 47 | S&F double walled corrugated (DWC) pipe of size 77 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT cable in under ground complete all as specified and directed by Engineer-in-Charge.Make: REX/Tirupati Plastomatics Pvt Ltd |
| 48 | M&L for cement concreate 1:2:4 type D-2 (using 40 mm graded stone aggregate) as in coping etc including necessary form work and finishing the surface with cement mortar 1:4, 5mm thick finished to the portion of PCC muffs above ground level complete all as specified and directed by Engineer-in-Charge. |
| 49 | M&L for PCC 1:4:8 type D-2 (using 40 mm grade stone aggregrate in foundation, mass concrate) as in foundation of poles & stay etc complete all as specified and directed by Engineer-in-Charge. |
| 50 | Supply and Laying in replacement Galvanised iron steel tubes, ISI marked light grade of size 40 mm bore for cable protection along the poles under road under drains, laid in trenches/fixed on walls/poles with suitable clamps bolts nuts etc including taking down of old unserviceble pipe complete all as specified and directed by Engineer-in-Charge. |
| 51 | S&F in replacement erecting steel tubular swaged poles erected to truly vertical or planted as strut complete with 6mm thick mild steel base plate(300mmx300mm), welded to pole, finial taper plug, bolts, nuts, and screws poles made out of ERW MS tubing conforming to IS-2713 Part-II Type 410 SP-31, 9mtr long including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bitumenous paint internally and portion embedded in concrete, making five black & white bands at lower portion of pole each 300mm wide alternately upto the height and marking pole No. with black paint at suitable height including making two nos holes of suitable size in steel tubular pole by gas welding for passing PVC cable connection from junction box to security lights through pole where junction box to be fitted in pole complete all as specified and directed by Engineer-in-Charge.Note: - Excavation and Earth Work, PCC in foundation shall be measured and paid for separately. |
| 52 | S&F in replacement Tri color(Tiranga)LED rope/Strip for outdoor application like lighting poles beautification,Monuments,residenstial/institutional bldg beautification ,18 mtrs roll with 120 nos LED per meter, having combination of saffron, white and green colour with IP-65 degree protection complete all as specified and directed. Make :Wipro-(LRO2-671-XXX-57-G3)/Bajaj/Philips. |
| 53 | S&F in replacement Power contactor 3 phase 415 Volts, 40 Amps, coil voltage of rating 240 Volts including taking down old unserviceable power contactor complete all as specified and directed by Engineer-in-Charge. |
| 54 | S&F in replacement Power contactor 4 pole 240 Volts, 30 Amps , coil voltage of rating 240 Volts including taking down old unserviceable power contactor complete all as specified and directed by Engineer-in-Charge. |
| 55 | Supply only Driver for LED energy saving & enviornment area light fitting > 75 watts security light with active power factor correction (APFC) electronic driver. LED driver 75 Watt with operating voltage between 100-270 V of existing specifications & make complete all as specified and directed by Engineer-in-Charge. |
| 56 | Supply only Driver for LED energy saving & enviornment area light fitting > 45 watts security light with active power factor correction (APFC) electronic driver. LED driver 45 Watt with operating voltage between 100-270 V of existing specifications & make complete all as specified and directed by Engineer-in-Charge. |
| 57 | Supply only Surge protection 5 KV devices compatible with industrial & outdoor LED fixtures upto rated power of 45 W & up to 150 W with operating voltage between 100-270 V of existing specifications & make complete all as specified and directed by Engineer-in-Charge. |
| 58 | S&F in replacement of Battery 12 Volt, 26 Ah of lift , make as per sample complete all as specified and directed by Engineer-in-Charge. |
| 59 | S&F in replacement of Battery 12 Volt, 42 Ah of lift , make as per sample complete all as specified and directed by Engineer-in-Charge. |
| 60 | M&L for carry for carry out Servicing/Calibration of UPS (5KV 10KVA) with 12 Volt 26AH & 42AH Bty Make as per sample complete all as specified and directed by Engineer-in-Charge. |
| 61 | S&F in replacement MS Channel/angle iron/flat iron of required size and bend to shape as cross arms, bracing and support including, MS clamps back plates with bolts, nuts, and washers drilled for insulators including painting two coats of synthetic enemel paint (Aluminium shade) over a coat of red oxide primer complete all as specified and directed by Engineer-in-Charge. |
| 62 | S&F in replacement Aluminium conductor steel reinforced (ACSR) any size on poles, stretched on LT poles without any kink and bends of various sizes complete including fixing to insulator with Aluminium binding wire complete all as specified and directed by Engineer-in-Charge. |
| 63 | S&F in replacement MCCB four pole 63 Amps, 50 Hz with breaking capacity 16KA, Ics = 100% Icu , 415 Volts, Adjustable thermal & Fixed magnetic setting including making all incoming/ outgoing connections complete all as specified and directed by Engineer in Charge. |
| 64 | S&F Onload change over switch FP 200 Amps, 415 Volt, 4 pole complete all as specified and directed by Engineer-in-Charge. |
| 65 | S&F Onload change over switch FP 100 Amps, 415 Volt, 4 pole complete all as specified and directed by Engineer-in-Charge. |
| 66 | S&F Onload change over switch FP 63 Amps, 415 Volt, 4 pole complete all as specified and directed by Engineer-in-Charge. |
| 67 | M&L in replacement for heat shrinkable End joint for PVC/XLPE insulated armoured cable of size upto 50Sqmm 3.5/4 core complete all as specified and directed by Engineer-in-Charge. |
| 68 | Description all as per serial item No 66.00 here-in-before, but LT cable size of 70 to 150 Sqmm. |
| 69 | M&L for road cuttig existing road for crossing of underground electric cable for laying of any size GI tubing including necessary excavation and earth work including repairing the same as per existing with pre mix bituminious carpet complete all as specified and directed by Engineer-in-Charge.Note: - Width of trench shall be 15 cm and depth shall be upto 30 cm. |
| 70 | S&F in replacement Automatic Street Light Switch using Infrared Sensor based NATURE SWITCH for automatic switching of Street Lights. Nature Switch operation should be based on Natural Light Lux* level. Required Illuminance Level for Switching ON is ≤ 30 Lux and for Switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 hrs. to max. 12 hrs. The Sensor along with suitable Power Contactor, Incoming- Outgoing MCBs and Auto-Manual (Sensor By-Pass) selection option should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP66. The Circuit should be suitable enough to take Single-Phase load of 8kW with Contactor & Incoming-Outgoing MCB rating of 63 Amps & Circuit wiring: min. 16 sq.mm complete all as specified and directed by Engineer-in-Charge.Make of Nature Switch: Kakatiya Energy Systems model No Swadeep-66-8KW1P or equivalent makes in Bajaj/ Healer. |
| 71 | S&F in replacement Automatic Street Light Switch using Infrared Sensor based NATURE SWITCH for automatic switching of Street Lights. Nature Switch operation should be based on Natural Light Lux* level. Required Illuminance Level for Switching ON is ≤ 30 Lux and for Switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 hrs. to max. 12 hrs.The Sensor along with suitable Power Contactors, Incoming- Outgoing MCBs and Auto-Manual (Sensor By-Pass) selection option should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP66.The Circuit should be suitable enough to take 12kW load equally distributed over 3-phase with Contactors & Incoming-Outgoing MCB rating of 40 Amps & Circuit wiring: min. 10 sq.mm complete all as specified and directed by Engineer-in-Charge.Make of Nature Switch : Kakatiya Energy Systems model No Swadeep-66-12KW3P or equivalent makes in Bajaj/ Healer. |
| 72 | M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth wire 4 mm as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common salt including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron 40x40x5mm frame, GI medium grade watering pipe 20 mm bore and funnel with wire mesh light grade protection pipe 20 mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by Engineer-in-Charge.Note: - On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge. |
| 73 | Supply & Fixing Insulation Tape of size 25x3mm with (25 mtrs lenght) including taking down the existing unserviceable one, complete all as specified and directed by Engineer-in-Charge. |
| 74 | Supply and Fixing LT Junction box cubical type of size 60x40x30 cm, 415 volts for outdoor use made out of CRCA Sheet 3.15 mm thick powder coated, machine passed front opening with sigal door with privision of rubber beading and locking system including aluminium bus bar 4 srip of size 30mm wide and 6mm thick with provision of hole on bus bar fixing of cable mounted on PVC/ epoxy insulators, mounted on angle legs of size 25x25x5mm frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC(1:2:4) Type B-1 (using 20 mm graded stone aggregate) complete including all provision of opening for incomming/Outgoing cables and testing complete all as specified and directed by Engineer-in-Charge. |
| 75 | Note for item Nos 9.00 to 18.00, 38 to 41:- All LED/Street/Flood lights and Cable shall be embossed from the Company/Contractor by GE (U) Udhampur and CA No Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |