| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Repair /Maint of ARD Unit for electrical control panel of various lift room at Northern and Southern part of Garrison under GE (Utilities) Udhampur Contract No: GE/U-32/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Repair and replacement of unservicable spare parts of UPS of rating: Input - 230V AC Single Phase, with voltage limits of 151V-302V, Input Connection Type- 3Pin 16A, Network Frequency - 50Hz, +/-3Hz Auto Sensing, Rated Power - 3000 VA, 2700 W (Efficiency- 95%), Harmonic Distortion- Less than 5%, Transfer Time- 2ms typical, Wave Type- Line Interactive Sine Wave, UPS Connectivity- Serial Port, USB Port with available expansion slot, Noise Suppresion- Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449, Acoustic Level - 45dBA, Heat Dissipation - 275 BTU/hr as mentioned below; |
| 3 | UPS Control Card |
| 4 | SMPS Circuit Module |
| 5 | Static bypass switch |
| 6 | Transformer 230V/48V |
| 7 | LCD Display |
| 8 | Repair and replacement of unservicable spare parts of UPS of rating: Input - 230V AC Single Phase, with voltage limits of 151V-302V, Input Connection Type- 3Pin 16A, Network Frequency - 50Hz, +/-3Hz Auto Sensing, Rated Power - 1000 VA, 670 W (Efficiency- 95%), Harmonic Distortion- Less than 5%, Transfer Time- 2ms typical, Wave Type- Line Interactive Sine Wave, UPS Connectivity- Serial Port, USB Port with available expansion slot, Noise Suppresion- Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449, Acoustic Level - 45dBA, Heat Dissipation - 275 BTU/hr as mentioned below; |
| 9 | UPS Control Card |
| 10 | SMPS Circuit Module |
| 11 | Static bypass switch |
| 12 | Transformer 230V/48V |
| 13 | LCD Display |
| 14 | Servicing and caliberation of 3000VA, 230V, 50Hz, 14A UPS System alongwith connected accessories, connection cables, ports, plug and socket, overload module, controller drive, etc. complete all as specified and directed by Engineer-in-charge. |
| 15 | Servicing and caliberation of 1000VA, 230V, 50Hz, 6A UPS System alongwith connected accessories, connection cables, ports, plug and socket, overload module, controller drive, etc. complete all as specified and directed by Engineer-in-charge. |
| 16 | Supply and fix SMF lead-acid battery of 12V 18 AH for UPS ARD of Lifts/Elevators complete all as specified and directed by Engineer-in-charge. |
| 17 | Supply and fix SMF lead-acid battery of 12V 7.2 AH for UPS ARD of Lifts/Elevators complete all as specified and directed by Engineer-in-charge. |
| 18 | Repair and maintenance of Lift Alarm System with Control Card and siren mechanism, complete all as specified and directed by Engineer-in-charge. Make- Omega/TKE/KONE |
| 19 | Supply & Fix in replacement of electronic CTU card of lift, make as per sample complete all as specified and directed by Engineer-in-charge. Make- Omega/TKE/KONE |
| 20 | Supply & Fix in replacement of Main Circuit Board (MCU) of lift for UPS Panel, make as per sample complete all as specified and directed by Engineer-in-charge. Make- Omega/TKE/KONE |
| 21 | Supply & Fix in replacement of Push button of lift, make as per sample complete all as specified and directed by Engineer-in-charge. Make- Omega/TKE/KONE |
| 22 | Supply & Fix in replacement of electronic CCU card of lift, make as per sample complete all as specified and directed by Engineer-in-charge. Make- Omega/TKE/KONE |
| 23 | Supply and fix single phase preventer with phase sequence detection of rating 415V, 50Hz +/-20%, 3VA for protection against single phasing with phase unbalance trip of 40V +/- 6V, time delay of 3.5 sec and automatic resetting mode complete all as specified and directed by Engineer-in-charge. Make- Minilec/Rapid Controls |
| 24 | Supply and fix MCCB 4 Pole, Ics = 100% Icu, breaking capacity of 25 KA, 415 Volts, 100 Amps, with thermal adjustable and adjustable magnetic setting, having line load reversibility, with spreder terminal supplied by the OEM of MCCB as ARD Panel Incomer, complete all as specified and directed by Engineer-in-charge. |
| 25 | Supply and fix MCCB 4 Pole, Ics = 100% Icu, breaking capacity of 25 KA, 415 Volts, 125 Amps, with thermal adjustable and adjustable magnetic setting, having line load reversibility, with spreder terminal supplied by the OEM of MCCB as ARD Panel Incomer, complete all as specified and directed by Engineer-in-charge. |
| 26 | Supply and fix MCCB 4 Pole, Ics = 100% Icu, breaking capacity of 18 KA, 415 Volts, 40/63A Amps, with thermal adjustable and adjustable magnetic setting, having line load reversibility, with spreder terminal supplied by the OEM of MCCB as ARD Panel Incomer, complete all as specified and directed by Engineer-in-charge. |
| 27 | Supply and fix replacement of electronic ATS, 100 Amps, 415V, 50/60Hz, l closing=3A/230V, l tripping=0.5A/230v for lifts, complete all as specified and directed by Engineer-in-charge. |
| 28 | Supply, laying, jointing and testing XLPE insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5 core X 25 Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed by Engineer-in-charge. |
| 29 | Supply and fix in replacement of door motor of lift, make as per sample complete all as specified and directed by Engineer-in-charge. |
| 30 | Supply & Fix in replacement of call card of lift, make as per sample complete all as specified and directed by Engineer-in-charge. |
| 31 | Supply & Fix in replacement of Landing circuit Unit ((LOP/LCU) of lift, make as per sample complete all as specified and directed by Engineer-in-charge. |
| 32 | Supply & Fix in replacement of interlock limit switch of lift, make as per sample complete all as specified and directed by Engineer-in-charge. |
| 33 | Supply and fix in replacement of door sensor of lift cabin, make as per sample complete all as specified and directed by Engineer-in-charge. Make- Omega/TKE/KONE |
| 34 | Supply & Fix in replacement of Emergency Cabin light of 9 watt of lift , make as per sample complete all as specified and directed by Engineer-in-charge. |
| 35 | Supply & Fix in replacement of Shaft light of 12 watt of lift , make as per sample complete all as specified and directed by Engineer-in-charge. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |