| 1 | Item Rate BoQ BoQ_Ver4.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: HQ CWE (AF) NAGPUR Name of Work: PROVISIONING OF 82.5 KVA DG SET FOR STANDBY POWER SUPPLY AT ASD-30 AND WATER SUPPLY PIMP HOUSE AT 11 BRD UNDER GE (AF) OJHAR Contract No: CWE (AF) /OJH / OF 2026-27 Name of the Bidder/ Bidding Firm / Company : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl. No. Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE inclusive of all taxes in Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Quoted Amount in Words Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Supply, installation, testing and commissioning of silent diesel engine driven ,factory assembled, floor mounted generating set with suitable Automatic on Mains failure control panel (AMF) suitable for out put, 82.5 KVA, 415 volts, 3 phase, 4 wire, 50 HZ,1500 RPM Liquid Cooled complete with safety control and metering equipment mounted on & including common base frame on new PCC foundation as recommended by manufacturer all as specified and comprising of the following :-Prime Mover: Directly coupled diesel engine with blower fan, suitably matching under NTP condition of BS:5514 for driving 82.5 KVA capacity, alternator electric start, four stroke confirming to latest IS-10001/10002 Part -II 19801 for continuous running and capable for taking 10% over load for 1 hours in every 12 hours complete with following accessories :- (i) Engine (ii) Fly wheel to suitable coupling with guard (iii) Air cleaner with filters (Dry type, Replaceable paper element air cleaner with restriction indicator)(iv) Spin on filters-fuel, lube oil filter ,(v) Lubricating oil gauge. (vi) Anti- vibration pad as recommended by manufacturers (vii) PT pump with governor of suitable capacity & flywheel housing and flywheel to suit single bearing alternator (viii) Electric starters-self starter 12 Volt DC |
| 3 | (ix) 12 volts, dry maintenance free +B12 battery supplied along with the in charged condition along with flexible copper battery lead and connector & Battery charging alternator(x) Standard safety devices. (xi) Daily services fuel tank ( Tank complete with level indicator, fuel inlet and outlet, air vent , drain plug including arrangement for direct filling ) for full running capacity of DG set for min 08 hours enclosed within the canopy all as per CPCB with level indicator, fuel outlet drain pug, air vent and locking arrangements etc including fuel pipe connections with connected GI pipe medium grade from fuel tank to DG set and over flow from the DG set to fuel tank complete with gate valve. (xii) Exhaust system shall be provided with thermal insulation by using fire retardant / non igniting foam to prevent excess heat radiation on the engine and sage for operator, Critical grade silencer suitable optimized to meet stringent sound emission standards laid down by MOEF/CPCB, Stainless steel exhaust flexible bellows to meet emission norms & Exhaust system shall not be based on (Exhaust Gas regeneration) i.e. EGR (a) Integrated DG set controller (DG set should have a microprocessor based controller with LCD display for engine and alternator parameter) Integrated Electronic Control Panel (displaying the following Engine parameters): (1) Engine Metering: Oil pressure, Engine temperature, starting battery voltage, Engine running hours. (2) AC Alternator Metering : L-L Voltage and L-N Voltage, (3) Current (phase and total), KVA (phase and total), Frequency, (4) Engine Protection : Low lube oil pressure, Battery Over/under/Weak Volts, Fail to Crank/Start, Sensor failure, cranking lockout MODBUS interface (RS 485 RTU) (5) AC Alternator Protection : Over/Under Voltage, Over/Under Frequency, Loss of AC sensing. (6) Safety Control (Trip & Indication) |
| 4 | (7) High water temperature (hwt) (8) low lube oil pressure (llop) (9) Battery Over/Under/Weak Volts. (10) Failed to start, over crank lockout stop pressed. (b) Alternator: 82.5 KVA / 66KW at 0.8 power factor, and shall be able to give rated current output self regulated 3 phase with neutral 415 volts 50 Hz 1500 RPM with brushless excitation, Band of Voltage regulation + 1% of rated voltage, from no load to full load, Insulation Class \\"H\\" The alternator generally confirms to BS EN : 60034-1 / IS:4722.(C) Repair/Maint tools to be supplied with DG set are as under :-(i) Cutting pliers 10 \\" - 01 No with all auxilary tools (d) ACOUSTIC ENCLOSURE : Floor Mounted Acoustic Enclosure suitable for 82.5 KVA DG Set as per CPCB Norms of Make: Kirloskar KOEL Equivalent in Volvo or Caterpillar or PowericaThe DG set shall be guaranteed against faulty workmanship/poor material quality and against failures due to the same, for minimum of two years or 5000 Hrs of operation whichever is earliest, from the date of commissioning complete all as specified and directed. Make: Kirloskar / KOEL Green or equivalent in Crompton Greaves/ Volvo/ Caterpillar / Powerica Note:(1) Excavation over area for PCC work, Returning Filling in including spreading, leveling, watering & well ramming in layers n. exc 25 cm and Removing excavated material exc 500 m & n exc 1.50 Km is to be done by contractor in quoted rate . (2) PCC concrete Type B1 1:2:4 using 20 mm graded stone aggregate cement concrete foundation is as per manufacturer recommendation and included under quoted rate. (3) DG set testing will be carried out by IEM/Accepting officer on successfully installation of DG Set . Load test of 12 hrs including one hour at 10 % above full load. Fuel consumption shall be recorded at 25 %, 50 %, 75 %, 100 % load and 10% above full load. In case actual load rated capacity is not available , contractor will make arrangement to carry out water load test. All gear, tackles, ropes, electrode, salt, water tank, of suitable capacity. Cable etc will be the responsibility of contractor . First filling of lubricating oil for DG Set testing will be provided by contractor. Contractor has to arrange fuel for testing. |
| 5 | Supply & Fixing LT XLPE insulated armoured heavy duty cable 1100V with stranded alumium conductor, Cross sectional area 70 Sqmm 4 core including necessory connection with privision of lugs and cable gland & fixing arrangement all as specified and directed. |
| 6 | Supply and laying Double walled corruyated (DWC) Duct (Dura- Guard) as per IS-14930 Part - II for LT UG cable protection including coupler, elbows, T- Joint, Bends, etc and test report Make :- Dura- line/Gemini/Rex. Of size 75 mm Outer Dia |
| 7 | M&L for earthing for earthing complete with GI earth plate electrode 600x600x6 mm thick,burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level ) with top edge of the pl;ate not less than 1.5 Mtr below normal ground level,connected to GI strip 25x4 mm as earth lead by means of bolts,nuts ,washer and check nut of galvanized steel, protected by and including GI pipe 50 mm bore (light grade) and connected to main switch / MCB DBs box point / LP test point as directed and including cement concret pit in 1:2:4 type B1 using 12.5mm graded aggregate, with cast iron miled steel frame embedded in the concrete enclouser fineshed flushed & PCC cover of size (300mmx300mm) all as shown under electrical plate of SSR Pt - I 2009 and as directed including painting the external surface of chamber & cover with enamel paint in diffrent colour as directed and writing earth results & date of test carried out with white paint on black painted background, wiremesh funnel 20 mm bore GI pipe medium grade for watering adequate quantity of charcol and common salt in alternate layer of 15cm 3ft x 3ft thick all around the electrode including necessery excavation & earth work in any type of soil complete testing on completion all as directed. Note:- i) Filling the pit with black cottan soil brought at site. ii) The excavated soil will be removed & paid separtely.Note:-(a).Earth resitance should be less than 5 Ohm up to Warranty period one year. (b).In case earth resitances not found satisfactorily contractor will redo the same earthing. |
| 8 | Excavation in trenches n. exc 1.5 Mtr wide and n. exc 1.5 mtr in depth and getting out soft/loose type soil complete all as specified and directed. |
| 9 | Returning Filling in including spreading, leveling, watering & well ramming in layers n. exc 25 Cm complete all as specified and directed. |
| 10 | Removing excavated/Surplus soil n exc 50 Mtr & depositing where directed at a level n. exc 1.5 Mtr above the starting point complete all as specified and directed. |
| 11 | Supply, install, testing and commissioning cubical type LT panel board, indoor type manufactured by CPRI approved factory made floor mounted totally enclosed, dust and vermin proof (front and rear opening) with locking arrangement &backelite plate made of CRCA sheet of 2mm thick IP 43 protected as per IS-5039 duly powder coated of approved shade. The panel shall be suitable for 415 volts, 50 Hz, 3 phase, 4 wire system with suitable size of PVC insulated copper conductor cables, thimbles, glands and shall be suitable for housing with rotary handel& spreader mechanism .INCOMMING (a) Incoming MCCB 4 pole 3 phase, 200 Amps, 415 volts AC rupturing capacity 36 KA . (b) Copper bus bar three phase and neutral of capacity 1.5 times of incomer MCCB , 3 phase 4 wire including bus bar mounting insulators, nuts, bolts etc. (c) Multifunction Meter Digital type showing V,A,F,Pf, Kw,KWH in built Selector switch with CT coiles for three phase. Cat No MFM4410 LED meter CI 1 with RS485 1 of L&T or Equivalent in siemens. with selector switch digital CT type and including CT's as in incoming in selector switch, MCB 2 Amps for protection.-01No. |
| 12 | OUTGOING (d) Out going MCCB's TP 80 Amps repturing capcity 25KA for starters cat no 4200 44 of Legrand - 02 Nos (e) Fully automatic star-Delta starter(3RT2038-230 V coil) 80 Amp - 02 Nos + 3RT2035, 230 V coil-40 amps - 01 Nos with auxilary NO & NC block -03 Nos+ 3RU2136-4RB0 (70-80 amp) Bimetallic relay-01 nos+ 3RP1574-NM208K timer-01 nos) + SDF(3KL821) & HRC (3NA78300RC- 100 amp) SwItch fuse units of suitable ratings of Make :Siemens or equivalent in L&T /Legrand 415 volts with 50Hz, 3 phase suitable for 50 HP motors with set of Push button ON & OFF etc for each starter (Qty- 02 Nos of star delta starter for 50 HP motor each are to be included in the panel) (g) Volt meter 0-500 volts range square flush type 96x96mm size digital type with selector switch-- 1 Nos (h) Ammeter 0 to 50 Amps range with selector switch digital CT type and including CT's as in outgoing on each starter -02 Nos (at each pump outlet)(j) Indicator lamp neon type (RYB) with holder, one set for each incoming and out going - 02 Sets.(k) Single phase preventor suitable for starter - 02 Nos(l) Capacitor of suitable capacity with capacitor duty contactor to achieve PF not less than 0.99- As per requirement(m) Complete internal wiring with suitable sizes/cross section copper conductor PVC insulated cable to carry current as per corresponding switch gear ratings and equivalent current rating copper lugs & cable gland at incomer& outgoing side comple all as specified or directed by Engineer -In Charge . (m) Complete internal wiring with suitable sizes copper conductor PVC insulated cable with suitable copper lugs at inlet all as per 's instructions. |
| 13 | Note :-1. The cost of the PCC plinth /foundation deemed to be included in the quoted rate of the above said item. 2. ALL MCCB should be operated by veri depth rotary handle.3.Bus bar directly connected to incomer of outgoing MCCB,s ,not by PVC flexible wires.4.Proper air ventilation in case of IP43 Protection.5.Every MCCB and star delta starter shall has separate compartment6.V curve ( upper portion) 50 mm outside from both side7.Panel should be operated from front side only(dead Rear side)8.Neoprene gasket at doors9.Outdoor panel sheet thickness 3.15 mm and indoor panel sheet thickness 2 mm unless otherwise specified.10.Panel handle should be rubber grip insulated or polycarbo-nate handle( panel should Not opened by Nude steel handle )11. All cables (incoming and outgoing) should pass through bottom gland plate with proper size of gland for protection of lizard,snakeetc12.Cable connection by MCCB's should be by proper lugs and lugs pressed by proper tools . Bimetallic lugs use in case of copper bus bar.13.Line diagram stick on inner side of door ( coloured paper sheet and laminated)14.Every compartment has permanent nomeclaturep-late,made of steel,riveted joint( not sticker) like( Example-MCCB,160Amps,4P,36KA)15.Danger notice plate ,made of steel,riveted joint (not sticker)16.Name plate,made of steel ( Manufacturer name,Year of manufacturing,IP -54/43) The Contactor, relay, , timer, switch fuse, MCB/MCCB, shal be conformed to BOQ and of Make Legrand/siemens/ABB Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |