| 1 | Supplying, installing, testing and commissioning, factory assembled silent Diesel Engine driven generator set, fully wired alternator AC, to give an out put of 250 kVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz ± 1% supply, 1500 RPM, CPCB IV+ regulation, directly coupled with diesel engine liquid cooled turbo charged after cooled mounted on common base frame complete with floor mounting fuel tank (with fuel line & accessories, vibration damper pads, microprocessor based genset monitioring controller Engine Safeties & Protections Battery With Leads , including termination and connection of cable with gland and lugs and comprising of following :-LOCATION : (a) NEW CARDIAC CATHERISATION LAB (CCL) AT AICTS PUNE - 01 No.(b) OT, ALC PUNE - 01 No. |
| 2 | (A) Diesel Engine : Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500 RPM 4 stroke, under NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories, Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of classG-3, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/ flexible coupling and coupling guard complete.(a) Radiator with blower fan or heat exchanger with guard.(b) Pipe coupling for engine cooling system piping.(c ) Corrosion inhibitor coolant(d) Paper element filters (i) Fuel filter (ii) Lube oil filter (iii) By pass(e) Fly wheel housing and fly wheel to suit alternator.(f) Engine bearing mechanism in fly wheel housing.(g) Shut off coil with safety for LLOP/HWT/over speed.(h) Dry type air cleaners and vacuum indicators.(j) Residential silencers.(k) Stainless steel exhaust flexible bellows.(l) BLANK.(m) Battery charging alternator. |
| 3 | (B) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:-(i) Battery. -as per manuactrure specified.(ii) Water temperature.(iii) Lubricating oil pressure.(iv) Engine speed -1500 Rpm(v) Engine hours(vi) Frequency.(vii) Voltage.(w) Safety control (Trip and indication).(i) High water temperature(ii) Low lube oil temperature(iii) Overspeed stop(C) Base frame : Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design alonwith AVM pads.(D) Battery : as per manufacturer specified with leads & terminals.(E) Alternator : Suitable rated 250 kVA, 0.8 PF, 415 Volts, 3 Phase, 4 Wire, 50 Hz at 1500 RPM, self excited and self regulated with AVR brushles, screen protected, drip proof, insulation class-H, IP -23, voltage regulation grade - VG 3 self ventilated and conforming to BS : 5000 / IS : 4722 suitable for engine as mentioned here-in before, conformig to IS: 13364 (Part-1)(F) Acoustic Enclosure : Specially design for CPCB norms M&L for acoustic enclosure for the above 250 kVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audiable frequencies as per guide of Central Pollution Control Board and manufacturer's specification and comprising of following from authorised GOEMs of Gen Set manufacturer's specified . |
| 4 | Supply and installation, testing of AMF panel outdoor type suitable for AMF 250 kva with factory made type panel weather proof, vermin proof, fully ventilated both side opening and fabricated out of 3.00 mm thick crca sheet & mounting channel 75 mm having bus bar of aluminum 600 Amps capacity, three phase and one neutral fixed on insulator and bus bar insulated by colored heat shrinkable sleeve & housed in specified compartment both side open able. Including powder coating internally externally the entire steel surfaces. All the cover shall have with suitable locking arrangements, fully internally wired with suitable size of thimbles. Incoming/outgoing internal connection with pvc insulated pvc sheathed multi stranded copper wire of suitable size all as directed The panel shall be provided with 04 Nos 50mm x 50mm x 6mm thick angle iron suppons of not less than each 0.6 mtr height duly painted with anti cormsive black paint and grouted on floor/well atc and suitable fixing amanament as per she requirement connection to the existing earthing., including PCC 1:3:6 & comprising of following :-LOCATION : (a) NEW CARDIAC CATHERISATION LAB (CCL) AT AICTS PUNE - 01 No.(b) OT, ALC PUNE - 01 No. |
| 5 | Under voltage relay 415v AC for main - 1 NoUnder voltage relay 415 v AC for DG - 1 NoAC timer 230 volt, 2 NO. +2 NC - 1 NoDC timer 24 Volt - 1 NoControl mcb sp 16 A - As requiredControl mcb sp 6 A - As requiredAutomatic battery charger 24 volts- 1 NoLed indicating light for main & DG - 6 Nos.Led indicating light for main & Gen. On - 2 Nos.Led indicating light for battery charger - 1 No.VAF Meter - 2 NosAMF Controler 3 Phase 4 wire -1 NoVolt meter selector switch - 1 No.Amp meter selector switch - 1 No.500/5 Amp - 3 Nos.DC volt meter 15/30 V - 1 No.DC amp meter 0-15 A - 1 No.Trickle / boost switch - 1 No.Auto / manual switch - 1 No.Push button start & stop with elements - 2 NosPower contactor 400 Amp 3 pole 415V for DG - 1 NoPower contactor 400 Amp 3 pole 415V for main - 1 NoMCCB 400 Amp 35 ka 3 pole for main & dg supply - 2 NosControl relay -1 setOver load relay 2.5-4 A - 1 No.Bus bar 600 A, 3 strips & n/l 300 A . Aluminium - 1 set |
| 6 | Supplying, installing, testing and commissioning, factory assembled silent Diesel Engine driven generator set, fully wired alternator AC, to give an out put of 160 kVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz ± 1% supply, 1500 RPM,CPCB IV+ regulation, directly coupled with diesel engine liquid cooled mounted on common base frame complete with floor mounting fuel tank (service tank) of minimum capacity 385 ltrs with fuel line & accessories, vibration damper pads, Standard Control Panel With Controller PS0602, Engine Safeties & Protections Battery With Leads With dept tank capacity 60 Ltrs, including termination of cable with gland and lugs and comprising of following :- |
| 7 | (A) Diesel Engine : Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500 RPM 4 stroke, 6 cylinderunder NTP conditions of BS 5514 and conforming to IS 10002, DIN 6271 & ISO 3046 with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories, Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class A1, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/ flexible coupling and coupling guard complete.(a) Radiator with blower fan or heat exchanger with guard.(b) Pipe coupling for engine cooling system piping.(c) Corrosion inhibitor coolant(d) Paper element filters (i) Fuel filter (ii) Lube oil filter (iii) By pass(e) Fly wheel housing and fly wheel to suit alternator.(f) Engine bearing mechanism in fly wheel housing.(g) Shut off coil with safety for LLOP/HWT/over speed.(h) Dry type air cleaners and vacuum indicators.(j) Residential silencers.(k) Stainless steel exhaust flexible bellows.(l) BLANK.(m) Battery charging alternator. |
| 8 | (B) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:-(i) Battery as per manufacturer specified.(ii) Water temperature.(iii) Lubricating oil pressure.(iv) Engine speed -1500 Rpm(v) Engine hours(vi) Frequency.(vii) Voltage.(w) Safety control (Trip and indication).(i) High water temperature(ii) Low lube oil temperature(iii) Overspeed stop(C) Base frame : Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design alonwith AVM pads.(D) Battery : as per manufacturer specified with leads & terminals. |
| 9 | (E) Alternator : Suitable rated 160 kVA, 0.8 PF, 415 Volts, 3 Phase, 4 Wire, 50 Hz at 1500 RPM, self excited and self regulated with AVR brushles, screen protected, drip proof, insulation class-H, IP -23, voltage regulation grade - VG 3 self ventilated and conforming to BS : 5000 / IS : 4722 suitable for engine as mentioned here-in before, conformig to IS: 13364 (Part-1)(F) Acoustic Enclosure : M&L for acoustic enclosure for the above 160 kVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audiable frequencies as per guide of Central Pollution Control Board and manufacturer's specification and comprising of following from authorised GOEMs of Gen Set manufacturer's specified. |
| 10 | Supplying, installing, testing and commissioning imdoor CPRI approved AMF Control panel of capcity 160 KVA factory fabricated cubical type, free standing, floor mounted, outdoor type, IP-52, with rotary handle, provided with removable rear panels & hinged front panel for easy accessibility, fabricated out of not less than 2.0 mm thick CRCA sheet with partition and switch enclosure door 1.6 mm including two coats of powder coated paint over a coat of red oxide primer with MS angle stand of size 50x50x6mm and shall be mounted on including necessary grouting in PCC 1:3:6 type C-1 by using 20 mm graded stone aggregate completed with legs 30 cm in ground in PCC and 40 cm above ground and termination of cable with gland and lugs comprising of following :-LOCATION : MAINT PUMP HOUSE AT AICTS PUNE - 01 No. |
| 11 | (a) AMF control circuit with 3 Pole MCCB 320 Amps - 01 No, with ultimate breaking capacity Icu-36 KA at 415 volts and microprocessor release conforming to IEC 60947 Part-I, aluminium busbar OF capacity 450 Amps- 01 Set, digital timer 6 Amp-02 Nos, Battery charger 24 V 10 A -02 Nos, Relay with base 11 pin type 220 V - 01 No, MCB SP 6 A 10 kA -04 Nos, Rotary switch 6 A auto manual type - 02 Nos, Connectors DMC type 20 A 4 Way 2p, Indication lamp LED type 220 V - 05 Nos, VAF meter digital type -01 No, Add on Block type 2 NO 2 NC - 02 Nos, VMR 3 Phase digital type - 01 No, Contactor 4 Pole for Main & Gen Set Mc type 300 A -02 Nos, spreader terminal 3 Pole type - 01 Set etc and thermal overload setting 70% to 100%, short circuit setting 5 to 10 times-02 Nos for main supply & DG set supply with HRC back up fuse complete with all DC control relays/ Line voltage monitor (LVM) as per OEM specifications incorporating motorised stored energy operating Engine start, stop, three attempt starting facility and failure to start etc.(b) Digital load manager : Three Phase 4 wire indicating V, I, PF, KVA, KW, F with serial communication port with class 1.0, per Phase- 03 Nos.(c) Bottom gland plate for incoming and outgoing cables.(d) Circuit diagram plate. |
| 12 | Supply laying and testing LT cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric cable (Heavy duty) 1100 Volts grade with stranded aluminum conductor of size 300 Sqmm X 3.5 Core including termination of cable witjh gland lugs etc complete all as specified and directed. |
| 13 | Supply laying and testing LT cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric cable (Heavy duty) 1100 Volts grade with stranded aluminum conductor of size 150 Sqmm X 3.5 Core complete all as specified and directed. |
| 14 | Supply, laying, jointing and testing of XLPE insulated screened PVC bedded, armoured heavy duty electric circular cable with stranded aluminium conductor, 1100 volts grade of cross-sectional area 185 Sqmm 3.5 core, conforming to IS-7098 (Part-I) of 1988 laid in trenches/wall/floors/ducts etc fixed with saddle and clamps or passing through pipes complete with cable and connection with proper thimbles, nuts, bolts and washers complete all as specified and directed by Engr-in-Charge. |
| 15 | Supply, laying, jointing and testing of XLPE insulated screened PVC bedded, armoured heavy duty electric circular cable with stranded aluminium conductor, 1100 volts grade of cross-sectional area 240 Sqmm 3.5 core, conforming to IS-7098 (Part-I) of 1988 laid in trenches/wall/floors/ducts etc fixed with saddle and clamps or passing through pipes complete with cable and connection with proper thimbles, nuts, bolts and washers complete all as specified and directed by Engr-in-Charge. |
| 16 | Supply, laying, jointing and testing of XLPE insulated screened PVC bedded, armoured heavy duty electric circular cable with stranded aluminium conductor, 1100 volts grade of cross-sectional area 70 Sqmm 3.5 core, conforming to IS-7098 (Part-I) of 1988 laid in trenches/wall/floors/ducts etc fixed with saddle and clamps or passing through pipes complete with cable and connection with proper thimbles, nuts, bolts and washers complete all as specified and directed by Engr-in-Charge. |
| 17 | Dismantle Locking tile /and paving block care fully and refixing the same after PCC complete all as specified and directed. |
| 18 | Surface Excavation not exceeding 30 Cm deep and getting out in soft loose soil complete all as specified and directed. |
| 19 | Excavation in trenches not exceeding 1.5 m wide and not exc. 1.5 m depth for laying cables, foundation for pole etc and getting out in soft/loose soil complete all as specified and directed. |
| 20 | Excavation in trenches not exceeding 1.5 m wide and not exc. 1.5 m depth for laying cables, foundation for pole etc and getting out in hard /dense soil complete all as specified and directed. |
| 21 | Excavation in trenches not exceeding 1.5 m wide and not exc. 1.5 m depth for laying cables, foundation for pole etc and getting out in hard rock complete all as specified and directed. |
| 22 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed. |
| 23 | Removal of excavated material (soil /rock) to a distance not exceeding 500m and depositing where directed complete all as specified and as directed |
| 24 | Supplying and laying DWC pipe IS -16205 outer dia 160 mm with coupler for protection of underground cable laid along pole/along wall/in PCC on GL and including all fittings as required at site complete all as specified and directed. Make -IS Approved. |
| 25 | M&L for Road cutting by road cutting machine not less than 0.6 mtr wide and not less then .45 mtr depth for laying GI Pipe for the the LT cable and making good surface with PCC 1:4:8 type D-2 using 40 mm graded stone aggergate complete all as specified and directed.(Note :- PCC shall be measured and paid saparately.) |
| 26 | Supply and lay GI tubing medium grade including necessary fittings as cable protection laid in trenches/ fixed to wall/pole including MS clamps of size 150 mm etc complete all as specified and directed. |
| 27 | M&L for plain cement concrere 1:4:8 type D-2 using 40 mm graded stone aggergate for foundation and mass filling including form work complete all as specified and directed. |
| 28 | Supply, installation, commisioning of double door outdoor CPRI ApprovedLT pannel of minimum size (1 X 1.5 X 0.4)m suitable for AC 440 V , 50 HZ supply, fabricated with 3 mm Steel sheet duly pre-treated and pure polyester thick powder coated using Siemens grey colour The LT Panel shall be double door in cubical formation, compartmentalized in form with front open able doors. The door shall be provided with concealed hinges and with brazing wherever required to avoid deformation and shall be earthed. All the door shall have heavy duty door locks, and shall be sealed with neoprene gaskets. The LT panel shall be IP 55, outdoor type weather , dust and vermin proof having canopy type tapered roof self-standing type as per approved GA diagram. Panels shall have lifting hooks and base channel of size 40 X40 X5 mm The feeder pillar shall be complete with bus bars, wiring, cabling of proper ratings (not less than 1.5 times the rating of respective switchgears, control gear etc.) for inter connection between switch gear, control gear, metering , safety relays, indicators etc. as per the approved single line diagram. |
| 29 | The LT panel shall have proper arrangement for termination of all incoming and out goings cables. All the bus bars shall be supported on epoxy supports and The feeder pillar shall be insulated with colour coded heat shrinkable sleeves. LT Panel shall be as per the space available at site. It shall have earthing bolts at both sides inter connected with 50x5 mm earthing bus along the width of LT panel. The LT panel shall be provided with MS angle iron frame 40 X 40 X5 mm welded in shape and including necessary grouting in PCC 1:3:6 type C-1 by using 20 mm graded stone aggregate completed with legs 30 cm in ground in PCC and 40 cm above ground including connecting to cable with cable gland, lugs etc complete(Note:-The drawing for panel should be approved by engineer in charge before fabrication. The LT Panel shall have space and proper arrangements for installation of incoming and outgoing MCCBs with R,Y,B LED type indicating lamps.) |
| 30 | The LT Panel comprising of following Parts :-INCOMER :- (a) Sleaved Aluminium bus bar 1000 A - 4 NOS switchgears, control gear etcinsulator,nuts & bolts complete.(b) MCCB 630 Amp braking capacity 50 KA, 4 pole- 01 Nos as incomerOUTGOING :-(a) MCCB 630 Amp, Thermal magenetic release braking capacity 36 KA 4 pole- 01 NosMCCB 400 Amp, Thermal magenetic release braking capacity 36 KA 4 pole- 01 Nos(b) Control panel wiring with multistranded, pvc insulated copper conductor cable between voltmeter, CTs of ratio 500/5 Amps- 3 nos, Multi function VAF meter 96x96mm -1 No Each,& indicator Lamp(c) Power panel wiring between bus bar to MCCB with Al strip duly sleved & using suitable insulation complete all as directed.Arrangement of cable ally for outgoing cable |
| 31 | M&L for earthing with Glavanised steel earth plate electrode 60cmx60cmx6 mm buried directly in ground earth pit not less 2.25 deep below normal ground level with top edge of the plate vertically to depth of not less than 1.5 m below ground level connected to & including GI strip of size 32x6mm as earthing lead by means of GI bolts & nuts etc. connecting to equipment with provision of char-coal and salt etc. all as per electrical plate No.3 of SSR Part I 2009 including RCC cover and MS angle iron frame watering arrangement with GI pipe 20 mm dia (medium grade), GI protection pipe 15 mm dia light grade & MS funnel, concrete pit including excavation and earthwork in any type of strata soft/ loose / hard / dense soil /Rock and testing on completion etc complete all as specified and as directed by Enginer - in charge. Complete all as specified & directed.(Note : GI strip and earth protection pipe upto and including 7.5 m length shall be deemed to be included in unit rate quoted by contractor) |
| 32 | M&L for Galvanised iron strip 32mm x 6mm with fixing of pole by mean of nut bolt and waher etc of suitable size for Loop earthing purpose etc complete all as specified and directed. |
| 33 | S&F earthing marker made out of 3mm thick MS sheet of size 300mm X 300mm (as approved by Engr-in-charge) duly painted with two coats black paint over a coat of red oxide primer, writing ( type of earthing) and mentioned the Nos of earthing and mounted on angle iron 40x40x3mm, angle height 45 cm, ( 30 cm below ground level ) with PCC 20 cm x 20cm x 20 cm complete all as specified and directed. |
| 34 | S & F of Exhaust gas piping of 125 mm dia MS black class -B pipe welded incl. all necessary fitting reduce , flange, bend etc support & clamps with 50X 50X 3 mm equal angle and anti vibration mounting insulation of exhaust system with 50 mm thick mineral wool coverd with wire mesh and aluminium cladding (from DG set to out side of the building complete all as specified an directed. |
| 35 | M&L for dismantling Concrete in ground and pavings exc 15 cm thickness below ground level complete all as specified and directed. |
| 36 | Supply and lay GI tubing Light grade including necessary fittings as cable protection laid in trenches/ fixed to wall including MS clamps of size 100 mm dia etc complete all as specified and directed. |
| 37 | Supply and installation and commisioning of chemical earthing with Earthing Electrode 17.2mm Copper Bonded Earthing Electrode 3mtr in length Copper bonding thickness will be minimum 250microns Electrode must be tested for Short Circuit Test of minimum 40kA at CPRI / NABL. Bore will be fill with BFC Compound , The BFC is carbide based having very high electrical conductivity.BFC having high moisture retaining capacity. BFC is hygroscopic, nonmagnetic and non-corrosive in nature and is ROHS Compliant, The Earthing electrode will be placed in the ground after a bore is drilled 120mm dia to the depth of 3.5mtr. The Bore drilling will be done with the help of Pneumatic boring machine. 50KG BFC will be placed in the bore to cover the Earthing rod from all sides. BFC will be poured in Slurry form in properly mixed condition including fixing Earth Pit Cover Square 300X300X240mm to be provided to cover the Earth Pit, The Earth pit Cover shall be made of Reinforced FRP and should be capable of carrying the weight of 5 tons complete all as specified and directed. |
| 38 | M&L for Brick work with fly ash brick, straight or curved on plan, exc 6m mean radius built in Cement mortar with 1:4 ratio complete all as specified and directed. |
| 39 | M&L for Rendering 15mm thick on fair faces of brick work or concrete surfaces with ratio 1:4 cement plaster complete all as specified and directed. |
| 40 | M & L for Mild steel plates, Fe 410-W (Gde-E- 250) quality plain or chequered, 5mm thick or over in thickness for cable duct complete all as specified and directed |
| 41 | S&F DWC high density polyethelene pipes having 90/75 outer dia mm, inner as per site requirement having corrugation on the wall and plain surface on the inner wall conforming to IS: 16098(Part I 2013) for protection of underground cable laid along pole/along wall/in PCC on GL and including all fittings as required at site complete all as specified and directed. Make -IS Approved Please Enable Macros to View BoQ information |
| 42 | S&F DWC high density polyethelene pipes having 90/75 outer dia mm, inner as per site requirement having corrugation on the wall and plain surface on the inner wall conforming to IS: 16098(Part I 2013) for protection of underground cable laid along pole/along wall/in PCC on GL and including all fittings as required at site complete all as specified and directed. Make -IS Approved Please Enable Macros to View BoQ information |