| 1 | Taking out unserviceable cable any type/size from trenches, pole road, duct etc including necessary joints, unserviceable fittings, cable protection cover and pipes etc complete. Note: Excavation and earthwork shall be measured & paid for seperatly under respective item of this schedule of work. |
| 2 | Supply, laying, commissioning and testing in repairs of XLPE insulated, seceened, PVC bedded, galvanised steel wire armoured heavy duty electric power cable with aluminium conductor, 6.35/11 KV suitable for 11000 volts grade, cross-sectional area 95 sqmm 3 core complete all as specified and directed. |
| 3 | Excavating in trenches not exc. 1.5m wide and not exc. 1.5 metre deep and getting out in soft/loose soil complete all as specified and directed.Note: (i) During the excavation damage of Road, Electric cable,Signal cable and Sewage line should be repaired by the contractor without any extra coast and surface should be matched as existing surface. |
| 4 | Returning, filling in including spreading, watering and well ramming in layers not exc 25cm in soft/loose soil. Complete all as specified and directed. |
| 5 | Removing surplus soil to a distance not exc 50m and depositing where directed at a level not exc. 1.5m above the starting point. |
| 6 | M & L for sand cushioning for under ground cable with locally available clean sand for protection of cable 8cm before laying cable and 15cm deep over the cable including spreading and onsolidations, complete all as specified and directed. (Note-Punned thickness ie 18 mm will be measured and paid) |
| 7 | Supplying and laying unreinforced precast concrete cable cover, class HV, type 2, flat size 450mm x 180mm x 40mm |
| 8 | S&F pipe galvanised iron light grade ( ISI marked )with all fittings laid in trenches or on pole, crossing of road,fixed on wall for protection of cables complete all as specified and directed of 80mm dia |
| 9 | Dismantling and taking down of End termination/ Straight through cable joint of any size,any type |
| 10 | M & L for replacement of cable jointing kit for 11 kV grade (Earthed) HT cable for indoor termination Cold shrinkable type complete with jointing material and accessories suitable for 3 core x 95 Sqmm XLPE armoured aluminium conductor cable of following sizes complete all as specified and directed by EIC. |
| 11 | All as per item No 10 Above but 95 Sqmm out door type. |
| 12 | All as per item No 10 above but for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm, straight through type. |
| 13 | Supply, jointing and testing in repair cable jointing kit for 11KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 - 185 Sqmm all as per manufacturer’s recommendations complete all as specified and directed. |
| 14 | Supply, jointing and testing in repair cable jointing kit for 11KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 - 185 Sqmm all as per manufacturer’s recommendations complete all as specified and directed. |
| 15 | M&L for rubber mat of size 2.5 mm thick 2mtrx1mtr suitable for 11KV sub station complete all as specified. |
| 16 | Supply only electric hand gloves rubber suitable for 11 KV line complete all as specified. |
| 17 | Supply only safety Helmet with slide-strap adjustment yellow complete all as specified. |
| 18 | Detecting of fault of HT UG cable (any place any length any type /size) with help of vehicle mounted cable fault locator including detecting exact location of cable fault and remove of cable for rectification. Note:-Cable fault locator shall be aggranged within 2 days from of inimation by Engineer-in-charge otherwise Penalty of RS 2000/day will be levised for each day of delay for for every segment of cable . If fault not located no payment shall be made to contractor. |
| 19 | Disconnecting and taking out existing HT 11 KV (VCB) from housing and cleaning, rubbing and overhauling the mechanical parts including greasing, oiling, replacement of unserviceable Trip coil, Breaker charging motor, gear pinion, roller switch, big gear checking of SF6 quality of vacuum interrupter, insulation resistances, static contact resistance etc and re-assembling the same after requir and made the VCB serviceable including making all electrical connection and testing (IR value, Ratio test, polarity test) and connection verification of 11 KV current transformer (set of three) by PRIMARY INJECTION KIT and testing and calibration of relay (set of two over current and one earth fualt) by SECONDARY INJECTION KIT including all other functional tests of the VCB, C&R panel and CTs, PTs. complete all specified and directed. Note :- (i) All spares parts of VCB panel shall be measured and paid for separately under relevent item as supply only. (ii) The repair work and testing of VCB shall be carried out by the representative of OEM only.(iii) Relay test record shall be submitted with signature of Engineer in charge,JE and Contractor. |
| 20 | Supply only breaker charging motor including gear assembly 220 volt AC of 11 KV VCB panel. |
| 21 | Supply install, testing and commissioning of Closing coil suitable for 11 KV HT VCB of make L & T 110V DC complete all as sspecified and directed. |
| 22 | Supply install, testing and commissioning of Triping coil suitable for 11 KV HT VCB of make L & T 110V DC complete all as sspecified and directed. |
| 23 | Supply install, testing and commissioning of Power Pack , 230V AC input, 110V DC output, 100VA suitable for 11 KV HT VCB of make L & T 110V DC complete all as sspecified and directed. |
| 24 | Supply install, testing and commissioning of 11 KV, indoor CT 100 A/50A+1A ACC Class 5P ratio suitable for VCB |
| 25 | Supply install, testing and commissioning of 11 KV, indoor PT 110 V suitable for SF6 VCB |
| 26 | S&F in repair 11 KV panel indicating lamp fitting RYB LED type suitable for 12/24 volt DC complete with base complete all as specified ad directed. |
| 27 | S&F in repair 11 KV VCB panel volt ampere frequency meter digital type suitable for 12/24 volt DC complete with base complete all as specified ad directed. |
| 28 | Supply, fixing and testing 11 KV bus insulator suitable for 11 KV SF6 VCB Panel complete. |
| 29 | Supply ,installation and testing of Bus bar Spout Please Enable Macros to View BoQ information |
| 30 | Supply ,installation and testing of Bus bar Spout Please Enable Macros to View BoQ information |