| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Certain Repair/Replacement of LT Switch gear system at CHNC under GE (Utilities) Udhampur Contract No: GE/U-30/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Supply and fixing in replacement of MCCB, 4 pole, 415 volt of capacity 630 amp,Ics=50%Icu short circuit, breaking capacity not less than 50 KA , thermal setting 80 to 100 % confirming to IEC-947, IS-13947 , including thimbles, nuts, bolts ,washers etc disconnecting and making incoming , out going connections complete all as specified and directed by Engineer-in-Charge. |
| 3 | Supply and fixing in replacement of MCCB, 3 phase, 4 pole, 415 volts of capacity 400 Amps, breaking capacity not less than 35/36 KA, thermal setting 80-100%, Ics=100% Icu conforming to IEC-947, IS-13947 including thimbles, nuts, bolts, washers etc disconnecting and making incoming, outgoing connections complete all as specified and directed by Engineer-in-Charge. |
| 4 | Description all as per Ser item No 2.00 here-in-before, but capacity of MCCB 250 Amps 25 KA |
| 5 | Description all as per Ser item No 2.00 here-in-before, but capacity of MCCB 200 Amps 25 KA |
| 6 | Description all as per Ser item No 2.00 here-in-before, but capacity of MCCB 160 Amps 25 KA |
| 7 | Description all as per Ser item No 2.00 here-in-before, but capacity of MCCB 100 Amps 25 KA |
| 8 | Description all as per Ser item No 2.00 here-in-before, but capacity of MCCB 63 Amps 25 KA |
| 9 | Supply and fix MCB TPN 415 volts 63 amps with 10KA breaking capacity complete all as specified and directed by Engineer-in-Charge. |
| 10 | Supply and fixing in replacement of Air Circuit Breaker 415V Microprocessor based SR18G release of capacity 2000A 4P 50K MDO rated current at 50°C conformance to IS/IEC 60947-2 & IEC 60947-2. ACB should have High short time withstand capacity, Icu = Ics = Icw for 1 sec for total selectivity and Having Electromechanical operation not less than 20000. ACB Should have overload phase protection, overload Neutral, short circuit, instantaneous,earth fault & individual fault LED indication complete all as specified and directed by Engineer-in-Charge. |
| 11 | Supply and fixing in replacement of Air Circuit Breaker 415V Microprocessor based SR18G release of capacity 1600A 4P 50K MDO rated current at 50°C conformance to IS/IEC 60947-2 & IEC 60947-2. ACB should have High short time withstand capacity, Icu = Ics = Icw for 1 sec for total selectivity and Having Electromechanical operation not less than 20000. ACB Should have overload phase protection, overload Neutral, short circuit, instantaneous, earth fault & individual fault LED indication complete all as specified and directed by Engineer-in-Charge. |
| 12 | Supply and fixing in replacement of Air Circuit Breaker 415V Microprocessor based SR18G release of capacity 1250A 4P 50K MDO rated current at 50°C conformance to IS/IEC 60947-2 & IEC 60947-2. ACB should have High short time withstand capacity, Icu = Ics = Icw for 1 sec for total selectivity and Having Electromechanical operation not less than 20000. ACB Should have overload phase protection, overload Neutral, short circuit, instantaneous, earth fault & individual fault LED indication complete all as specified and directed by Engineer-in-Charge. |
| 13 | Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick steel sheet duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming/ outgoing feeders CTS contactors for remote control operation, complete all as specified and directed by Engineer-in-Charge, fitted with following accessories. (i) 1 No. 100 Amps MCCB incoming.(ii) 1 Set 100 Amps MCCB TPN and neutral copper conductor bus bars duly sleeved. (iii) 1 No. 100 Amps TPN MCCB outgoing for 40/35/25/20 kw strip heater.(iv) 1 No. 32 Amps TPN MCCB outgoing alongwith 1 No. star delta starter for 11.0/7.5/5.5 kw motor.(v) 1 No. 16 Amps MCB outgoing |
| 14 | Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick steel sheet duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming/ outgoing feeders CTS contactors for remote control operation, complete all as specified and directed by Engineer-in-Charge. fitted with following accessories. (For F.M. AHU's).(i) 1 No. 32 Amps MCCB incoming.(ii) 1 No. 32 Amps MCCB outgoing along with 1 No. star delta starter for 11.5/7.5/5.5 kw motor. |
| 15 | Supplying, installing, testing and commissioning of main panel board cubical compartmentalised, floor mounted made of 2.0 mm thick steel sheet duly painted complete with voltmeter, ammeter, indicating lights for selector switch, incoming/ outgoing feeders CTS contactors for remote control operation, complete all as specified fitted with following accessories. (For C.S. AHU's).(i) 1 No. 16 Amps MCB incoming. (ii) 1 No. 16 Amps MCB outgoing along with 1 No. DOL starter for 3.7/2.2/1.1 kw motor. |
| 16 | Supply, Installation , testing and commissioing outdoor type, weather proof, cubicle panel board made out of 3.15 mm thick CRCA steel sheet mounted on 60 cm long legs made out of 40 x 40 x 6 mm equal angle, embedded in PCC 1:2:4 type B-1 blocks of size 15 x 15 x 15 cm front and back openable, double door openable up to minimum 150 degree & removable type having magnetic catche system, lockable/ openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flow suitable foamed in PU gasket to make it dust/vermin proof, IP 54 protection, powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliset for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produced to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels complete suitable cable glands for cable entry. The panel shall accomodate the following equipments, complete all as specified and directed by Engineer-in-Charge:-(a) Aluminium Bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 1250 Amps for phases and neutral - 01 set . |
| 17 | (b) Digital multifunction meter of size 96x96mm to measure current, voltage, freequency and power factor with built in selector switch and programmable CT of appropriate ratio - 01 Nos.(c) Panel indicating lamp neon/LED type (Red, Yellow & Blue) with lamp holders - 03 Nos.(d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 Sqmm copper wire single core - 01 Job. INCOMING(a) MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 630 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos. OUT GOING(a) MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 320 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos. (b) MCCB 4 Pole, Ics = 100% Icu,25/26KA, 415 Volts, 200 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 03 Nos. (c) MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 125 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 03 Nos.(d)MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 250 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos. |
| 18 | Supply and fixing in On load change over switch with Sheet Steel Enclosure 415 V, 4 pole, 1000 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cables from LT panels to change over switches complete all as specified and directed by Engineer-in-Charge. |
| 19 | Supplying and install Heavy Duty cable tray ,hot-dip galvanised mild steel , with size 450MMX50MM and 2mm thick ness. , complete with bends, tees, reducers, cross members, couplers, and all necessary accessories.The tray shall be hot dip galvanized after fabrication with zinc coating not less than 120 microns (or as specified), fixed on walls/ceiling with M.S. angle iron supports, threaded rods, clamps, anchor fasteners, including painting of supports with one coat of red oxide primer and two coats of synthetic enamel paint of approved shade complete all as specified and directed by Engineer-in-Charge.Note :- (a) Drilling, cutting and welding as required Fixing with dash fasteners / anchor bolts Earthing of cable tray with 25x3 mm GI strip along with cable tray is included in the quoted rate of the items.(b) Cost is included for L supports for wall with all accessories such as nut ,bolt ,washers etc.(c) All major and minor spares are required in laying of cables and fixing of cable trays which are not mention above are included in the quoted rates.c) All meterial such as cement ,concerete,tiles etc to make wall/roof /ground in its original shape after fixing of cable trays shall include in the quoted rates of the items. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |