| 1 | DSR Item No 1.17 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 2 | 5 x 4 sq. mm |
| 3 | 5 x 6 sq. mm |
| 4 | DSR Item No. 1.21 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 5 | 40 mm |
| 6 | DSR item No.1.24 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 7 | 5/6 amps switch |
| 8 | 3 Pin 5/6 A. socket outlet |
| 9 | DSR item No.1.28 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. |
| 10 | 12 Module |
| 11 | DSR Item No. 2.10 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 12 | Single pole |
| 13 | Triple pole |
| 14 | DSR item no.8.16LEDFlood powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt)Supplying,installation,Testing&CommissioningofFlood Light,powdercoatedpressuredie cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%,Input voltage., (As per Complete Item No. 6 of the DNIT) |
| 15 | 100 Watt |
| 16 | 250 Watt |
| 17 | DSR item No.15.16 SupplyingandlayingoffollowingsizeDWCHDPEpipeISI markedalongwithallaccessorieslikesocket,bend,couplers etc.conforming toIS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioningandprotectivecoveringetc.,completeasrequired. |
| 18 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 19 | DSR Item No.2.5 Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required). |
| 20 | 4 way (4 + 12) Double door |
| 21 | 8 way (4 + 24) Double door |
| 22 | DSR item No.2.2 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 23 | 100A,30KA,FPMCCB |
| 24 | 200A,36KA,FPMCCB |
| 25 | 400A,35KA,TPMCCB |
| 26 | Supply and erection of sheet metal bus-bar chamber on existing surface with required No. of bus-bar strips of suitable length and cross-sectional area, made of copper strips of suitable length and cross-sectional area enclosure made of M.S. sheet 1.6mm thick with detachable cover fitted with dust excluding gasket and secured with sufficient No. ,(As per Complete Item No. 10 of the DNIT) |
| 27 | Sheet metal bus-bar chamber suitable for 200 Amp. 415 Volts capacity with 4 copper strip Bus-bars each of length 600 mm & cross-sectional area (40mm x 5mm) enclosure having overall dimensions (680mm x 450 mm x 150 mm) nominal. |
| 28 | Sheet metal bus-bar chamber suitable for 400 Amp. 415 Volts capacity with 4 copper strip Bus-bars each of length 600 mm & cross-sectional area (60mm x 6.6 mm) enclosure having overall dimensions (680mm x 450mm x 150mm) nominal. |
| 29 | S/E of enclosure for MCCB 200/400 Amp 4 pole made out of 16 Gauge M.S. sheet. The enclosure is to be painted after one coat of primer including its erection in existing angle iron board with nut bolts/ screws etc. to complete the job to the entire satisfaction of Engineer In Charge. |
| 30 | Supply and erection of sheet metal cubical pedestal of suitable dimensions made from 50 mm X 50 mm X 6 mm thick M.S angle iron frame, covered with 1.6 mm thick M.S. sheet duly welded on five sides and front side hinged complete with locking arrangement with 4 Nos. switchgear supporting members each of M.S. f(As per Complete Item No. 12 of the DNIT) |
| 31 | Cubical size 900 mm X 600 mm X 350 mm |
| 32 | Supply and laying of XLPE insulated PVC sheathed Aluminum conductor cable of 1.1 KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid in existing RCC/Hume/DWC/ Metal pipe. (As per Complete Item No. 13 of the DNIT) |
| 33 | Size 25 Sq.mm 3.5 Core XLPE Al. Arm. Cond. Cable Please Enable Macros to View BoQ information |