| 1 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 <135 lm/Watt) Supplying of Street light LED fixture powder coated pressure die cast aluminium body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage rotection, EMIEMC As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of nitial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 m/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- harge as per requirement. (Thermal management: heat sink of luminium housing such that LED junction temperature shall ot rise above 90°C). |
| 2 | 120 watt |
| 3 | 150 Watt |
| 4 | 200 Watt |
| 5 | LED Flood Light, powder coated pressure die cast aluminium System lumen efficacy ≥120 and <135 lm/Watt).Supplying of Flood light, powder coated pressure die cast aluminium body with uilt in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, nternal surge protection of 5 KV L,N,E as per IEC 61000-4-5, river efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage rotection, EMI-EMC as per CISPR-15, lenses for beam angle 30 eg-120deg as per the application and the project requirement, uitable tilt able fitting, life time (LED, Driver & electrical ircuitry) of minimum 50000 Burning Hours with 70% of nitial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation olour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant IS standard complete in all respect i/c external connections ith 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing equired for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 6 | 200 Watt |
| 7 | 250 Watt |
| 8 | Supplying & Fixing of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required.3 output(1output per phase) and suitable for three phase supply |
| 9 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required. |
| 10 | 100 A,30KA, FPMCCB |
| 11 | 125 A,36KA, FPMCCB |
| 12 | Providing and fixing 4 pole 105 Amp Power Contactor of 105 Amp with conforms to IS/IES-60947-4-1 and IEC 60947-4-1 i/c wiring testing commissioning etc. as required. |
| 13 | Supplying of one Number Following size. XLPE insulated PVC outer sheathed armoured with standard copper conductor suitable for rated voltage of 1.1 KV grade ISI marked confirming to IS 7098 / (Pt.-I)/88 with ammendment No. 1 in following manners. |
| 14 | 3 x 10 Sq. mm |
| 15 | 4 x 16 Sq. mm |
| 16 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. onforming to IS 14930, Part II complete with fitting and cutting, jointing tc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required |
| 17 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 18 | Supplying of one Number Following size XLPE insulated PVC outer sheathed unarmoured with standard Copper conductor suitable for rated voltage of 1.1 KV grade ISI marked confirming to IS 7098 / (Pt.-I)/88 with ammendment No. 1 in following manners. |
| 19 | 3 x 1.5 Sq. mm |
| 20 | Supply and Fixing of Winch motorized Gear Box (750kg single gear double drum) for existing 30 mtr high mast complete etc. as reqd. i/c 6 mm dia SS rope length of 150 mtr. |
| 21 | Servicing and minor repairing of High Mast (12.5 m / 16 m / 30 m height) complete, including checking, lubrication and operation of motorized raising & lowering system, inspection of wire rope, pulleys, winch, control panel, etc. as required.” |
| 22 | Supplying of Driver with efficiency >85% THD < 10% as per IEC 61000-3-2, P. F.≥0.95 for street light/Flood light etc. complete as required. |
| 23 | 50 Watt |
| 24 | 100 Watt |
| 25 | 150 Watt Please Enable Macros to View BoQ information |