| 1 | Supply , Installation , testing and commissioning of Eco friendly for emmission and noice (CPCB IV+ norms Complience), generating set Diesel Engine driven 82.5 KVA / 66 KW at 0.8 power factor or nearest higher size , 415 volts AC , 3 Phase 50 Hz , 4 wire directly coupled alternator and Engine water cooled common base platform with in built fuel tank and including all excavation PCC foundation , anti vibration pads / dampers as per manufacturer instructions and as directed by manufacturer. The DG set shall be factory assembled by the OEM of the engine manufacturer and all components shall be accommodated in enclosure and other accessories comprising of the following:- |
| 2 | A ) ENGINE : Eco friendly for emmission and noice (CPCB IV+ norms Complience) Diesel Engine confirming to BS/IS standard devoloping suitable HP @ 1500 RPM water cooled complete under NTP condition, with a provision for 10% over load for one hour on 12 hours running with the following:- |
| 3 | a) Radiator / Heat exchanger cooling system. |
| 4 | b) Spider coupling guard. C) Fy wheel |
| 5 | d) Fly wheel housing complete with starter gear ring & Coupling |
| 6 | e) Fuel pipes f) Air cleaner g) Fuel & Lub oil filter |
| 7 | h) by pass filter j) Fuel pump k) Water pump l) Lub oil pump |
| 8 | m) Self starter 12 volts DC n) Residential silencer |
| 9 | o) Extension joint p) Digital DC volt meter 0-30 volts for battery |
| 10 | q) Disply for fault r) Lead acid DC battery 12 volts 88 AH |
| 11 | s) Battery lead copper conductor stranded with terminals |
| 12 | t) battery charging generator ( DC Alternator) |
| 13 | B) ALTERNATOR :- |
| 14 | Syncronous alternator 82.5 KVA , 1500 RPM 415 volts 50 Hz 3 Phase system self excited self regulated confirming to IS 13364 |
| 15 | C) Fuel tank of suitable capacity for contineous 8 Hrs of operation including all connection etc |
| 16 | D) Base frame made out off suitable channel mounted on AVM pads as recommended by manufacture. |
| 17 | E) Provn of DG set foundation as recommended by manufacturer |
| 18 | F) Accoustic enclosure meeting stringer MOEF/CPCB norms of 75 dBA @ 1 mtr at 75% load under free field condition with air inlet louvers poweder coated. Use of stainless steel hard ware and insulating materials shall meeting IS 8183 insulating materiala. Acoustic enclosure shall be as per manufacturer design. |
| 19 | (G) AMF Panel:-Supply install testing and commissioning of AMF panel indoor type suitable for 82.5 KVA Generating set totally enclosed with sheet metal enclosure with sheet CRCA duly powder coated, dust and vermin proof enclosurecv made out of 2.0 mm thick sheet . MS angle frame , front door with locking arrangement & two earth points by the side of he box , floor mounted cubical type with cable glands , sockets etc with provision of cable entry from bottom all pre wired and connected complete with comprising the following:- |
| 20 | a) PLC - 01 No b) Contactor heavy duty of capacity 160 Amps four pole - 2 Nos c) AC coil 220 volts - 01 No d) LED Type Indicator 150 Vots -10 Nos e) Aux block consist of 2 Nos NC contact & 2 Nos NO contact . F) Push button 4 Nos g) Selector switch - 2 Nos h) hooter =01 No j) Incoming MCCB, Adjustable type 125 Amps 25 KA , 4 pole, Icu=Ics=100% -02 Nos k) Digital type volt meter with selector switch - 02 Nos Ammeter with selector switch including neccessary CTs of reqruired ratio- 02 Nos l) Battery charger - 12 Volts Auto - 01 No m) Over load relay -01 No n) Control relay-01 No o) Under voltage & Over voltage unit p) Digital Amps meter 0-100 Amps for DC supply - 01 NO , Digital frequenc6y meter complete with accessories q) Interlocking system r) Lead acid battery 12 Volts with two years gurantee- 01 No. Note : Testing & commissioning of DG set will be carried out in presence of rep of OEM to avail the company guarantee. |
| 21 | M & L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick burried directly in ground vertically to a depth not less than 3.0 mtr deep below GL with top edge of the plate not less than 2.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to earth lead of GI strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel and thimbles and other end of the earth strip connected to LT panel / including path strip / down conductor and protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20 mm bore GI medium grade with funnel and wire mesh, including required excavation for making the pit perfect to size and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 and also including making test point for testing of earthing complete. |
| 22 | S & F in replacement off Load Change over switch 4 pole 415 Volt 50 HZ ,side operated 100 Amp in SS enclosure with side handle Make :-Havells /INDO ASIAN/L&T |
| 23 | S & F in replacement off Load Change over switch 4 pole 415 Volt 50 HZ ,side operated 160 Amp in SS enclosure with side handle Make :-Havells /INDO ASIAN/L&T |
| 24 | Supply and laying or fixing or passing through HDPE pipe, 1100 volts grade heavy duty cable with XLPE insulated stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel or strip and overall PVC sheathed, 95 sq mm 4 core ISI Marked as per IS 7098(Part 1) including connecting on LT OH line / LT panel /DB with suitable lugs, glands, binding wire etc complete all as specified and directed. |
| 25 | Supply and laying or fixing or passing through HDPE pipe, 1100 volts grade heavy duty cable with XLPE insulated stranded aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel or strip and overall PVC sheathed, 120 sq mm 4 core ISI Marked as per IS 7098(Part 1) including connecting on LT OH line / LT panel /DB with suitable lugs, glands, binding wire etc complete all as specified and directed. |
| 26 | Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts complete all as specified and directed by Engineer-in-Charge. |
| 27 | Excavation in trenches in any type of soil not exe 1.5 mtrs wide and not exe 1.5 mtr in depth for laying of pipe/cables etc and getting out incl forming bottom surface to the required level/slope etc complete all as specified and directed . |
| 28 | Returning fitting in soft/loose soil, including spreading levelling watering and well ramming in layers n.exc 25 cm complete all as directed |
| 29 | Removing excavated soils to a distance n.exc. 50 mtrs and depsiting where directed at a level n.exc. 1.5 above the starting point complee all as specified and directed |
| 30 | M&L pipe galvanised iron of size 50 mm dia, light grade ISI marked, complete with fittings laid in trenches/ fixed with poles etc as protection to cables complete as ditrected by Engineer in Charge |
| 31 | M&L Providing and laying 60mm thick factory made chamfered edge cement concrete paver block of M-35 grade with approved colour, design & pattern as in footparth, parks, lawns, drive ways or light traffic parking etc., of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over and including 50 mm thick compacted bed of fine sand, compacting and proper embedding/ laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sandt complete all as specified and directed. |
| 32 | Demolition of cement concrete(un Reinforced) of any description in any position not otherwise specifically provided for etc. complete all as specified and directed. |
| 33 | M&L PCC 1:4:8 type D2 using 40mm graded stone agg as in filling and mass concrete, Sub base/flooring complete all as specified and directed. |
| 34 | Supply , Installation , testing and commissioning of Eco friendly for emmission and noice (CPCB IV+ norms Complience), generating set Diesel Engine driven 30 KVA /24 KW at 0.8 power factor or nearest higher size , 415 volts AC , 3 Phase 50 Hz , 4 wire directly coupled alternator and Engine water cooled common base platform with in built fuel tank and including all excavation PCC foundation , anti vibration pads / dampers as per manufacturer instructions and as directed by manufacturer. The DG set shall be factory assembled by the OEM of the engine manufacturer and all components shall be accommodated in enclosure and other accessories comprising of the following:- |
| 35 | A ) ENGINE : Eco friendly for emmission and noice (CPCB IV+ norms Complience) Diesel Engine confirming to BS/IS standard devoloping suitable HP @ 1500 RPM water cooled complete under NTP condition, with a provision for 10% over load for one hour on 12 hours running with the following:- |
| 36 | a) Radiator / Heat exchanger cooling system. |
| 37 | b) Spider coupling guard. C) Fy wheel |
| 38 | d) Fly wheel housing complete with starter gear ring & Coupling |
| 39 | e) Fuel pipes f) Air cleaner g) Fuel & Lub oil filter |
| 40 | h) by pass filter j) Fuel pump k) Water pump l) Lub oil pump |
| 41 | m) Self starter 12 volts DC n) Residential silencer |
| 42 | o) Extension joint p) Digital DC volt meter 0-30 volts for battery |
| 43 | q) Disply for fault r) Lead acid DC battery 12 volts 88 AH |
| 44 | s) Battery lead copper conductor stranded with terminals |
| 45 | t) battery charging generator ( DC Alternator) |
| 46 | B) ALTERNATOR :- |
| 47 | Syncronous alternator 30 KVA , 1500 RPM 415 volts 50 Hz 3 Phase system self excited self regulated confirming to IS 13364 |
| 48 | C) Fuel tank of suitable capacity for contineous 8 Hrs of operation including all connection etc |
| 49 | D) Base frame made out off suitable channel mounted on AVM pads as recommended by manufacture. |
| 50 | E) Provn of DG set foundation as recommended by manufacturer |
| 51 | F) Accoustic enclosure meeting stringer MOEF/CPCB norms of 75 dBA @ 1 mtr at 75% load under free field condition with air inlet louvers poweder coated. Use of stainless steel hard ware and insulating materials shall meeting IS 8183 insulating materiala. Acoustic enclosure shall be as per manufacturer design. |
| 52 | (G) AMF Panel:-Supply install testing and commissioning of AMF panel indoor type suitable for 30 KVA Generating set totally enclosed with sheet metal enclosure with sheet CRCA duly powder coated, dust and vermin proof enclosurecv made out of 2.0 mm thick sheet . MS angle frame , front door with locking arrangement & two earth points by the side of he box , floor mounted cubical type with cable glands , sockets etc with provision of cable entry from bottom all pre wired and connected complete with comprising the following:- |
| 53 | a) PLC - 01 No b) Contactor heavy duty of capacity 80 Amps four pole - 2 Nos c) AC coil 220 volts - 01 No d) LED Type Indicator 150 Vots -10 Nos e) Aux block consist of 2 Nos NC contact & 2 Nos NO contact . F) Push button 4 Nos g) Selector switch - 2 Nos h) hooter =01 No j) Incoming MCCB, Adjustable type 125 Amps 25 KA , 4 pole, Icu=Ics=100% -02 Nos k) Digital type volt meter with selector switch - 02 Nos Ammeter with selector switch including neccessary CTs of reqruired ratio- 02 Nos l) Battery charger - 12 Volts Auto - 01 No m) Over load relay -01 No n) Control relay-01 No o) Under voltage & Over voltage unit p) Digital Amps meter 0-100 Amps for DC supply - 01 NO , Digital frequenc6y meter complete with accessories q) Interlocking system r) Lead acid battery 12 Volts with two years gurantee- 01 No. Note : Testing & commissioning of DG set will be carried out in presence of rep of OEM to avail the company guarantee. |
| 54 | Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) |
| 55 | Supply and Fixing Exhaust fans AC single phase 230/240V of size 300 mm sweep, 1250-1350 RPM with louvre complete including with all arrangement of making holes on wall, making good and finishing of disturbed surfaces matching with the existing surfaces, necessary fixing arrangement such as fastener bolts, nuts, washers etc, of appropriate size all as specified and as directed |
| 56 | Supply and Fixing Exhaust fans AC single phase 230/240V of size 450 mm sweep, 1250-1350 RPM with louvre complete including with all arrangement of making holes on wall, making good and finishing of disturbed surfaces matching with the existing surfaces, necessary fixing arrangement such as fastener bolts, nuts, washers etc, of appropriate size all as specified and as directed |
| 57 | S&F storage type water heater (Geyser),5 star BEE rating, 230 Volt AC, 25 Ltrs capacity comprising Stainless steel inner tank,suitable heatng element, thermostate with adjustable temperature setting , indication lamps provision for inlet outlet and air vent connections & NRV,inclucluding all fixing arrangement such s faster bolts, nuts washers etc complete including making good disturbed wall surfaces matching with the existing surfaces and finishing all as specified and as directed. |
| 58 | S&F storage type water heater (Geyser),5 star BEE rating, 230 Volt AC, 50 Ltrs capacity comprising Stainless steel inner tank,suitable heatng element, thermostate with adjustable temperature setting , indication lamps provision for inlet outlet and air vent connections & NRV,inclucluding all fixing arrangement such s faster bolts, nuts washers etc complete including making good disturbed wall surfaces matching with the existing surfaces and finishing all as specified and as directed. |
| 59 | S&F PVC connection 15 mm size suitable for geyser/hot water, heavy duty with brass nuts, 450 mm long complete all as specified and as directed. |
| 60 | S&F Bib taps, cast copper alloy with crutch or butter fly handle, screwed down, screwed for iron pipe and fixed of size 15 mm dia complete all as specified and as directed. |
| 61 | S&F angle cock, cast copper alloy, srewed down , high pressure, with cruntch or butter fly handle, screwed both ends for iron pipe or for unions and fixed of size 15 mm dia complete all as specified and as directed. |
| 62 | S&F MCB protected power socket unit with sheet steel enclosure include power socket , mini MCB SP 20 A ,240V,50 Hz complete all as specified and directed Please Enable Macros to View BoQ information |