| 1 | Taking down carefully copper/aluminium point wiring complete (light, fan, plug point & power complete alongwith fittings (switches, ceiling roses, tube light fittings, bulk head fitting regulator, sockets , removing materials to store and offering credit & making good of disturb surfaces of wall/floors etc complete all as specified and directed. |
| 2 | M& L for Point wiring with 1.5 Sqmm (22/0.30mm) PVC insulated and unsheathed multistranded copper conductor cable, 1100 volts grade, ISI marked, FRLS type drawn through and including PVC concealed conduit (ISI marked) of adequate size and its accessories with sunk cast iron/pressed steel terminal boxes of size 1.6mm thick, with 3mm thick plastic laminated sheet cover of adequate size for one light or one fan point controlled by one switch incl 1.5 Sqmm (nominal area) copper conductor cable (multistrand), FRLS type, PVC insulated and unsheathed with colour code earth wire connected to common earth dolly at one end and metallic bodies of luminaires/ fan at other end complete as per site requirement and complete all as specified and directed for the following:- (a) One light point or one fan point controlled by one switch with cables 1.5 sq. mm size Note:- Unit rate include for cutting chases for conduits and sinking for boxes and making good to wall, floors etc. |
| 3 | All as per ser item No. 2 above, but for One 5 Amp 5 pin socket outlet point on same board with other switches including earth wire complete all as specified and directed. |
| 4 | All as per ser item No. 2 here in before, but for One 5 Amp 5 pin socket outlet point on independent board complete all as specified and directed. |
| 5 | All as per ser item No. 2 here in before, but with 4.0 Sqmm (36/0.30mm) PVC copper stranded cable FRLS type for one 15 Amp 5 pin socket outlet point including PVC cable 4 Sqmm FRLS type copper stranded conductor as earth wire as specified & connected to common earth & earth terminals including boards for mounting purposes complete all as specified and directed. |
| 6 | All as per ser item No. 2 here in before, but one light point controlled by 2 way switches complete all as specified and directed. |
| 7 | All as per ser item No. 2 here in before, but one bell/buzzer point controlled by one push button on the same board with other switches or independent complete all as specified and directed. |
| 8 | M & L for Point wiring with 1.5 Sqmm (22/0.30mm) PVC insulated and unsheathed multistranded copper conductor cable, 1100 volts grade, ISI marked, FR type drawn through and including PVC casing caping/ PVC Conduit (ISI marked) and its accessories such as Tee, elbow, jointer, elbow corner etc. fixed on surface of walls, columns/ beams alongwith 1.5 Sqmm (nominal area) copper conductor cable (multistranded) PVC insulated and unsheathed as earth wire connected to common earth dolly at one end and metallic bodies of luminaire/ fan at other end including PVC folding boards with sunmica top for mounting switches, sockets, fan Regulators, accessories etc as per site requirement and complete all as specified and directed. for the following:- (a) One light point or one fan point controlled by one switch with cables 1.5 sq. mm size. |
| 9 | All as per ser item No. 8 above, but for One 5 Amp 5 pin socket outlet point on same board with other switches including earth wire complete all as specified and directed. |
| 10 | All as per ser item No. 8 here in before, but for One 5 Amp 5 pin socket outlet point on independent board complete all as specified and directed. |
| 11 | All as per ser item No. 8 here in before, but with 4.0 Sqmm (36/0.30mm) PVC copper stranded cable FRLS type for one 15 Amp 5 pin socket outlet point including PVC cable 4 Sqmm FRLS type copper stranded conductor as earth wire as specified & connected to common earth & earth terminals including boards for mounting purposes complete all as specified and directed. |
| 12 | All as per ser item No. 8 above here in before, but one bell/buzzer point controlled by one push button on the same board with other switches or independent complete all as specified and directed. |
| 13 | All as per ser item No. 8 here in before, but one light point controlled by 2 way switches complete all as specified and directed. |
| 14 | S&F bell push, flush type, 5 Amp single pole, 230 volts white finish complete all as specified and directed. |
| 15 | S&F switch piano flush button 5 Amp single pole 2 way 230 volts white finish complete all as specified and directed. |
| 16 | S&F in replacement switch piano flush button 5 Amp single pole one way 230 volts white finish complete all as specified and directed. |
| 17 | S&F in replacement of socket outlet flush type 5 pin 5 Amp multipurpose 230 volts single pole one way suitable for 3 pin/2pin 5 Amp plug top white/ivory finish complete all as specified and directed. |
| 18 | S&F in replacement switch socket combination flush type 5 pin 5 Amp multipurpose 230 volts single pole one way suitable for 3 pin/2pin 5 Amp plug top white/ivory finish complete all as specified and directed. |
| 19 | S&F in replacement of switch socket combination multipurpose flush type 2 in 1 type (3 and 5 pin) 5/15 Amps, 230V, AC complete all as specified and directed. |
| 20 | S&F in replacement ceiling rose surface PVC 50mm dia 3 terminals including PVC mounting block white/ivory finish complete all as specified and directed. |
| 21 | S&F in replacement surface and wall mounted LED batten 20 watt - 4Ft White with Aluminium housing & integrated electronic driver, high performance batten and efficacy should not less than100 lumen/watt and complete all as specified and directed. |
| 22 | S&F in replacement surface and wall mounted LED batten 10 watt - 2Ft White with Aluminium housing & integrated electronic driver, high performance batten and efficacy should not less than 100 lumen/watt and complete all as specified and directed. |
| 23 | S&F in replacement LED light fitting 1x9W/ 1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size as per site requirement and complete all as specified and directed. |
| 24 | S&F in replacement energy efficient Street/ Roadway/Building Security Luminaire LED fitting upto 35 Watt 230 V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete, including brackets and all accessories needed to fixed to the wall or pole all as per site requirement and complete all as specified and directed. |
| 25 | S&F in replacement Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fitting complete all as specified and directed. |
| 26 | S&F in replacement stepped type electronic fan regulator Socket type on the existing phenolic laminated sheet etc. complete all as specified and directed. |
| 27 | S&F in replacement exhaust fan, steel body AC single Phase. 230V of size 300mm sweep with, blades, and frame and louvers complete as per site requirement and complete all as specified and directed. |
| 28 | Taking down carefully copper/aluminium sub main wiring complete alongwith all connected accessories etc complete all as specified and directed. |
| 29 | S&F of submain wiring with two single core PVC insulated unsheathed, multistranded flexible copper conductor 1100Volts grade, FRLS type, cables 6 Sqmm drawn through in and including rigid PVC heavy duty concealed conduits including 6 Sqmm 1100Volts grade, FRLS type, PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified and directed. Note:- (i) Two runs of cables and one run of continuous earthing cable drawn in conduit/ casing and caping will be measured as one length of sub main with colour code Red Black and Green. (ii) PVC conduit / casing caping and its accessories is deem to be included in this item rates. (iii) Unit rate include for cutting chases for conduits and sinking for boxes and making good to wall, floors etc. |
| 30 | S&F of submain wiring with two single core PVC insulated unsheathed, multistranded flexible copper conductor 1100Volts grade, FRLS type, cables 10 Sqmm drawn through in and including rigid PVC heavy duty concealed conduits including 10 Sqmm 1100Volts grade, FRLS type, PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified and directed. Note:- (i) Two runs of cables and one run of continuous earthing cable drawn in conduit/ casing and caping will be measured as one length of sub main with colour code Red Black and Green. (ii) PVC conduit / casing caping and its accessories is deem to be included in this item rates. (iii) Unit rate include for cutting chases for conduits and sinking for boxes and making good to wall, floors etc. |
| 31 | S&F of submain wiring with two single core PVC insulated unsheathed, multistranded flexible copper conductor 1100Volts grade, FRLS type, cables 6 Sqmm drawn through in and including rigid PVC heavy duty PVC casing caping upto 32mm or PVC conduit upto 25mm on wall surface/ recessed as required at site including 6 Sqmm 1100Volts grade, FRLS type, PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified and directed. Note:- (i) Two runs of cables and one run of continuous earthing cable drawn in conduit/ casing and caping will be measured as one length of sub main. (ii) PVC conduit / casing caping and its accessories is deem to be included in this item rates. |
| 32 | S&F of submain wiring with two single core PVC insulated unsheathed, multistranded flexible copper conductor 1100Volts grade, FRLS type, cables 4 Sqmm drawn through in and including rigid PVC heavy duty PVC Conduit/casing caping upto 32mm or PVC conduit upto 25mm on wall surface/ recessed as required at site including 4 Sqmm 1100Volts grade, FRLS type, PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified and directed. Note:- (i) Two runs of cables and one run of continuous earthing cable drawn in conduit/ casing and caping will be measured as one length of sub main. (ii) PVC conduit / casing caping and its accessories is deem to be included in this item rates. |
| 33 | Taking down carefully DB/ Sheet Metal Enclosure with existing MCBs complete & making good of disturb surfaces of wall/floors etc complete all as specified and directed. |
| 34 | S&F distribution board sheet metal enclosure double door shutter type factory made fixed flush with wall or outside on wall surface suitable for mounting isolators & MCB's 415 volts, 200 Amp rated bus bar with front openable cover suitable for TP & N 4 ways complete all as specified and directed. |
| 35 | S&F distribution board sheet metal enclosure double door shutter type factory made fixed flush with wall or outside on wall surface suitable for mounting isolators & MCB's 240volts, 200 Amp rated bus bar with front openable cover suitable for SP & N 4 ways complete all as specified and directed. |
| 36 | S&F distribution board sheet metal enclosure double door shutter type factory made fixed flush with wall or outside on wall surface suitable for mounting isolators & MCB's 240volts, 200 Amp rated bus bar with front openable cover suitable for SP & N 8 ways complete all as specified and directed. |
| 37 | S&F sheet metal enclosure (factory made), VTPN Vertical Distribution Boards, IP-43 & IP-44 protection suitable for MCCB's upto 125A as as incomer, Double Door, 8 way with 250 Amps rated copper busbar complete all as specified and directed. |
| 38 | S&F sheet metal enclosure (factory made), VTPN Vertical Distribution Boards, IP43 protection suitable for MCCB's upto 125A as as incomer, Double Door, 4 way with 250 Amps rated copper busbar complete all as specified and directed. |
| 39 | S&F sheet metal enclosures with plug socket single pole and neutral with two pin and earth plug and with one MCB of 20 Amps (SP) complete all as specified and directed. |
| 40 | S&F in replacement MCB SP 5 to 32 Amp rating 240V, 10KA 'C' curve complete with connection testing and commissioning complete all as specified and directed. |
| 41 | S&F in replacement MCB SPN 32 Amp rating 240V, 10KA 'C' curve complete with connection testing and commissioning complete all as specified and directed. |
| 42 | S&F in replacement MCB SPN 40 to 63 Amp rating 240V, 10KA 'C' curve complete with connection testing and commissioning complete all as specified and directed. |
| 43 | S&F in replacement of MCB TP 25 to 63 Amps, 415 Volts, 50 Hz with 10 KA 'C' curve complete with connection testing and commissioning complete all as specified and directed. |
| 44 | S&F in replacement of MCB TPN 16 to 32 Amps, 415 Volts, 50 Hz with 10 KA 'C' curve complete with connection testing and commissioning complete all as specified and directed. |
| 45 | S&F in replacement of MCB TPN 40 to 100 Amps, 415 Volts, 50 Hz with 10 KA 'C' curve complete with connection testing and commissioning all complete all as specified and directed. |
| 46 | M&L in replacement of Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thickness buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to and incl galvanised earth lead wire of 4.00mm dia by means of nuts & bolts, check nuts and washers of galvanised incl PCC pit of 1:2:4 type B-1, cover reinforced with XPM weight not less than 4 Kg/Sqm and 6mm dia bar handle, earth pit angle iron frame of size 25mm x 25mm, excavation and earth work in any type of soil, charcoal dust, salt, light grade GI watering pipe 20mm dia with funnel and wire -mesh and medium grade GI protection pipe of 15mm bore from top edge of earth plate upto main distribution board complete all to as shown in electrical plate No 3 of MES Sch 2009 (Part I) connected main switch board complete all as specified and directed and testing on completion. |
| 47 | S&F in replacement of modular type fan regulator, AC 230 Volts complete all as specified and directed. |
| 48 | S&F in replacement of switch modular type 6 Amps one way AC 230 Volts complete all as specified and directed. |
| 49 | S&F in replacement of switch modular type 16 Amps one way AC 230 Volts complete all as specified and directed. |
| 50 | S&F in replacement of modular type bell push 6 Amps, AC 230 Volts complete all as specified and directed. |
| 51 | S&F in replacement of modular type socket 6 Amps 2/3 pin combined, AC 230 Volts complete all as specified and directed. |
| 52 | S&F in replacement of modular type socket 6/16 Amps 2/3 pin combined, AC 230 Volts complete all as specified and directed. |
| 53 | S&F in replacement of modular white cover plate with frame, 2 module complete all as specified and directed. |
| 54 | S&F in replacement of modular white cover plate with frame, 4 module complete all as specified and directed. |
| 55 | S&F in replacement of modular white cover plate with frame, 8 module complete all as specified and directed. |
| 56 | Taking down, strip opening, cleaning all parts and packing of ceiling fan of any make and size and greasing ball bearing with specified quality grease and re-assembling the ceiling fan as a one unit, complete all as specified and directed. Note : Replacement of spare parts such as rewinding, painting, cable for connection etc., to be measured and paid separately under relevant items. |
| 57 | Hanging only ceiling fan in position after necessary repairs and re-commissioning the same including making electric connection complete all as specified and directed. |
| 58 | All as per srl No 57 above, but of exhaust fan any make and any size complete all as specified and directed. |
| 59 | Hanging only exhaust fan in position after necessary repairs and re-commissioning the same including making electric connection complete all as specified and directed. |
| 60 | M&L for rewinding of ceiling fan of 1200 mm size complete with super enamelled insulated copper wire of suitable size/gauge and varnishing including oiling, greasing, and replacement of old unsv or weak capacitor of suitable capacity as per manufacturer and testing complete in MES store yard complete all as specified and directed. |
| 61 | All as per item No. 60 above, but for ceiling fan of 1400mm sweep complete all as specified and directed. |
| 62 | M&L for rewinding of exhaust fan of upto 350mm sweep with super enamelled insulated copper wire of suitable size/gauge and varnishing including oiling, greasing, and replacement of old unsv or weak capacitor of suitable capacity as per manufacturer and testing complete in MES store yard complete all as specified and directed. |
| 63 | All as per item No. 62 above, but for Exhaust fan of 380mm to 450mm sweep complete all as specified and directed. Please Enable Macros to View BoQ information |
| 64 | All as per item No. 62 above, but for Exhaust fan of 380mm to 450mm sweep complete all as specified and directed. Please Enable Macros to View BoQ information |