| 1 | (Supply Part) - 2X400 KVA 11/0.4KV Sub-Station |
| 2 | Distribution Transformer 11/0.4 kV, 400 KVA |
| 3 | Steel Tubular Poles (13 m) |
| 4 | Muffs with concerete filling |
| 5 | X-Arm: [Channel Iron (100x50x6 mm), Length : 2800mm X 2 Nos] for incommer line |
| 6 | MS Angle Iron (50X50x6 mm), Length: (2800 mm) x1 Nos for LA's |
| 7 | X-Arm: [Channel Iron (75x40x6 mm), Length :(2800mm) X 4 Nos] for supporting DO fuse unit & GO switch |
| 8 | X-Arm: [Channel Iron (100x50x6 mm), Length : 2800 mm X 2 Nos] for Transformer Bed |
| 9 | X-Arm [Channel Iron (100x50x6 mm), Length : 460 mm x 2 Nos for supporting Main Channel of Transformer] |
| 10 | MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos for Bed Knee Bracing |
| 11 | MS Angle Iron (50X50x6 mm), Length : (2800 mm) x 2 Nos |
| 12 | MS Angle Iron (50X50x6 mm), Length : (450 mm) x 1 Nos |
| 13 | GO Switch Handle Supporting: [Channel Iron (75x40x5 mm), Length : 460 mm |
| 14 | GO AB Switch Unit (11kV, 400A, 25 KA ) Tripple pole O/D type |
| 15 | D.O Fuse Unit |
| 16 | Surge Arrester, 9 kV Station Class (Porcelain Type) |
| 17 | Discs insulator sets (comprising 1 No. Disc: ^^(Porcelain, BS, 12 kV, 90 kN) including Dead End Clamps etc.) |
| 18 | Stay set complete |
| 19 | Stay Wire (7/3.15 mm) (6.0 kg Per Stay Set) |
| 20 | Pipe Earthing Set |
| 21 | LT Distribution Panel Box of 400 kVA DTR |
| 22 | Half Clamp (M.S. Flat 50X6 mm) |
| 23 | Full Clamps (M.S. Flat 50X6 mm) |
| 24 | Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)] |
| 25 | Aluminium Thimble |
| 26 | Aluminium Thimble |
| 27 | Danger Plate |
| 28 | Barbed Wire |
| 29 | LT Cable (3.5 Core) 400 mm² X 2 incommer |
| 30 | 11 KV CT/Pt unit, PT (1 unit, 15kv/110V); 200/5A |
| 31 | 11 KV HT meter 3-ɸ, 3/4 wire CT-PT operated Static Tri-Vector meter.(PT ratio-/ 110 V, CT ratio-/5 A) |
| 32 | Aluminium Paint. |
| 33 | Red oxide |
| 34 | LT switched capacitor 135KVAr for 400 kva DTR |
| 35 | Transportation charges |
| 36 | (Supply Part) of 11 KV H.T. Line |
| 37 | HT XLPE cable 3x120 sq m |
| 38 | Steel tubular pole 9 mtr long (working load > 200 kgf/m2) |
| 39 | Muffs with concrete muffing |
| 40 | Messenger wire/Stay wire 7/3.15mm for holding cable |
| 41 | Cable clamps with nuts & bolts |
| 42 | X-Arm (Horizontal) - MS Channel Iron: 75X40x6, Length:2800mm x 2 Nos |
| 43 | X-Arm (Horizontal) - MS Channel Iron: 100X50x6, Length:2800mm x 1 Nos |
| 44 | X-Arm (Horizontal) - MS Channel Iron: 100X50x6, Length:1500mm x 1 Nos |
| 45 | X-Arm - MS Channel Iron: 50X50x6, Length:750mm x 2 Nos |
| 46 | GO AB s/w unit (11 KV, 400 A, 25 KA) |
| 47 | DO Fuse Unit |
| 48 | 11 kV Pin Insulators (Porcelain, 12 kV, 10 kN): 6 No per Structure |
| 49 | Disc insulator sets(comprising 1 no disc:(porcelain BS, 12 KV,, 90KN i/c deadend clampsetc) |
| 50 | stay set complete |
| 51 | Stay wire 7/3.15mm (@ 10 kg per stay set ). |
| 52 | Earthing set |
| 53 | Termination kit |
| 54 | Half clamp (M S Flat 50x6mm). |
| 55 | Full clamp (M S Flat 50x6mm). |
| 56 | façade hooks |
| 57 | Anchoring assembly for HT |
| 58 | Suspension assembly |
| 59 | Prov. Nuts and bolts off size (galvanised/coated) with flat and spiral washers. |
| 60 | Prov. Danger notice plate |
| 61 | Prov. Barbed wire. |
| 62 | Aluminium Paint |
| 63 | Transportation charges |
| 64 | (Supply Part) Re-conductoring of existing 11 KV H.T. Line |
| 65 | AAAC 7/3.81 mm (80 mm2) {Includes 3 conductor lengths for 3Φ and Additional 1% (Sag, Jumpering and wastage} |
| 66 | Steel Tubular Poles (10 m, Working Load > 227 kgf/m²) (with Ruling Span 90 m, 8 No. Run thro' and 3 No. Double Pole Dead End Structures) |
| 67 | Muffs with concerete filling |
| 68 | 11 kV Pin Insulators (Porcelain, 12 kV, 10 KN): 3 No per pole structure |
| 69 | Discs insulator sets on Dead End structures (comprising 1 No. Disc: ^^(Porcelain, BS, 12 kV, 90 kN) including Dead End Clamps etc.) x (3 No. conductors) x (2 No. sides) |
| 70 | Stay set complete in all respect i/c Stay clamp (1No. / Single Pole , 4 No. / Double Pole Structures) |
| 71 | Stay Wire (7/3.15 mm) (10.0 kg Per Stay Set) |
| 72 | HT Earthing set complete (REC Constr. Stand. J-1) |
| 73 | GO switch unit (11 KV, 400 A, 25 KA) |
| 74 | Nuts and Bolts of Various Sizes (Galvanised / Coated) [Preferably 16 mm Φ or more (with flat and spring washers)] |
| 75 | Transportation charges |
| 76 | (Supply Part) of L T . Line |
| 77 | LT AB Cable [Size: ( 4X70+1X70+1X16mm² ) x 2 Cables |
| 78 | Steel Tubular Poles (9 m, Working Load > 200 kgf/m²) |
| 79 | Muffs with concerete filling |
| 80 | Stay Set Complete |
| 81 | Stay Wire (7/3.15 mm) (6.0 kg Per Stay Set) |
| 82 | Full Clamp |
| 83 | Anchoring Assembly |
| 84 | Suspension Assembly |
| 85 | Facade Hooks |
| 86 | Lugs for the connection in the Distribution boxes |
| 87 | Pre Insulated connector(jointing sleevs) for AB Cable |
| 88 | LT Earthing set complete (preferbly coil earthing) |
| 89 | Nut and Bolts |
| 90 | Red Oxide |
| 91 | Aluminium paint |
| 92 | Transportation charges |
| 93 | (Supply Part) - 33 KV and 11 KV CTs |
| 94 | Prov. 33 KV CT 200-100/1Amps |
| 95 | Prov. 11 KV CT 200-100/ 5-5 Amps (For Mohin Feeder) |
| 96 | (Erection Part ) - 400KVA 11/0.4KV Sub-Station |
| 97 | Erection of 2x400 KVA,11/0.4KV Transformer, LT Box, MCCB Switch, Cable , service Cableand Energy Meter completed in all respect. |
| 98 | Loading Unloading of 400 KVA Dtrs with Hydra |
| 99 | (Erection Part) ) of 11 KV H.T. Line |
| 100 | Erection of H T steel tubular Poles complete in all respect |
| 101 | Erection of H T Stay set complete in all respect |
| 102 | Erection of H T Earthing set complete in all respect |
| 103 | Erection of XLPE Cable 3*120 mm2 HT Line (Including laying of cable ,installation of suspension and tension assembly etc,sagging of cable with cable clamps on messenger wire ,heat shrinkable cable jointing /termination /t-joint ) complete in all respect. |
| 104 | (Erection Part) ) Re-conductoring of existing 11 KV H.T. Line |
| 105 | Erection of Double Pole str. Steel tubular pole complete in all respect. |
| 106 | Erection of Double Pole str. Steel tubular pole complete in all respect. |
| 107 | Erection of AAAC 7/3.81 mm2Add. Erection charges for conductor AAAC |
| 108 | Erection charges for stay set |
| 109 | Erection charges for earthing set |
| 110 | Dismentalling Charges for 1 km of HT Line Conductor ACSR 6/1/2.11 |
| 111 | (Erection Part) ) of L TLine |
| 112 | Erection of L T steel tubular Poles complete in all respect |
| 113 | Erection of L T Stay set complete in all respect |
| 114 | Erection of L T Earthing set complete in all respect |
| 115 | Erection of LT AB Cable for LT Line (Including laying of cable ,installation of suspension and tension assembly etc,sagging of cable with cable clamps on messenger wire ) complete in all respect. |
| 116 | (Erection Part ) - 33 and 11 KV C Ts |
| 117 | Erection of 33 KV & 11 KV CT completed in all respect |
| 118 | CIVIL PART (DTR foundation & chain link fencing of 400 KVA Distribution Transformer |
| 119 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 120 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:3:6 (1 Cement : 3 coarse sand): 6 graded stone aggregate 20 mm nominal size) |
| 121 | Centering and shuttering including strutting, propping etc. and removal of form for: Foundations, footings, bases of columns, etc. for mass concrete. |
| 122 | Centering and shuttering including strutting, propping etc. and removal of form for: Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 123 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level 1:1.5:3 (1 cement : 1.5 coarse sand): 3 graded stone aggregate 20 mm nominal size) |
| 124 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 125 | Fencing of DTR Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 126 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6 (1 Cement : 3 coarse sand) : 6 graded stone aggregate 20 mm nominal size) |
| 127 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 Cement: 2 coarse sand) : 3 graded stone aggregate 20 mm nominal size) |
| 128 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 129 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. Made of G.I. wire of dia 4 mm |
| 130 | Providing and fixing ISI marked M.S. pressed butt hinges bright finished with necessary screws etc. complete :125x65x2.12 mm |
| 131 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete :250x16 mm |
| 132 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/ 10 sqm over an under coat of primer applied @ 0.80 Ltr./ 10 sqm of approved brand and manufacture |
| 133 | Supplying, filling, spreading & leveling gravels of approved size in required thickness, for all leads & lifts, all complete as per direction of Engineer-incharge. |
| 134 | Centering and shuttering including strutting, propping etc. and removal of form for:Retaining walls, return walls, walls (anythickness) including attached pilasters,buttresses, plinth and string courses fillets, kerbs and steps etc. |
| 135 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 75 mm diameter Please Enable Macros to View BoQ information |