| 1 | DSR item No. 3.13Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated (Please refer DNIT for complete specification of item no.1) |
| 2 | 1600 A, Isc= 50kA for 1 sec |
| 3 | DSR item 4.1Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers MS/GI Suspenders i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastneretc as required. |
| 4 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 5 | 600 mm width X 62.5 mm depth X 2.0 mm thickness |
| 6 | DSR item No. 5.6 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 7 | DSR item No.5.8Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 8 | DSR item No. 5.14 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 9 | DSR item No.11.1 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPEaluminium conductor cable of 1.1 KV grade as required. |
| 10 | 3 ½ x 95 Sq mm (45 mm) |
| 11 | 3 ½ x 185 Sq mm (57 mm) |
| 12 | 3 ½ x 400 Sq mm (82 mm) |
| 13 | 4 x 16 Sq mm (28 mm) |
| 14 | DSR Item No. 23.4 supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPEaluminium conductor cable of 11 KV grade as required : |
| 15 | 120 sq. mm |
| 16 | DSR item No.15.15Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
| 17 | 120 mm dia (OD-120 mm & ID-103 mm nominal) |
| 18 | DSR item No.2.22Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 19 | DSR item No. 24.4Supply, installation, testing and commissioning of following capacity (continuous loading) BEE 3 Star rated (Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433 KV step down, 3 Phase, 50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH (Please refer DNIT for complete specification of item no.10) |
| 20 | 1000KVA |
| 21 | DSR item No. 25.2HYBRID Power Factor Correction SystemSupply, Installation, testing and commissioning of HYBRID APFC Panel, 3 phase 4 wire, 415 V, 50 Hz AC System for Ambient temperature -5°C to +40°C of following capacity with passive solution of 60% capacity and active solution of 40% capacity, 3Phase 4 wire Hybrid Power Factor Correction Solution (with arrangment for neutral current balance) to achieve >0.99 lag and TDDI/THDV values within IEEE recommended limits. (Please refer DNIT for complete specification of item no.11) |
| 22 | 300 KVAR |
| 23 | Supply, installation, testing & commissioning of 3 phase, 50Hz, 11KV, 800 Amp, 26.3KA/3Sec. incoming VCB panel with copper busbar for indoor substations. The VCB should be floor mounted trolley type horizontal isolation, horizontal draw out, type Breaker confirming to IEC-62271-100 & Panel as per IEC- 6227I-200, & IEC-60694 as amended up to date. The panel shall be compartmentalized consisting of Bus bars compartment, Breaker compartment, Cable and CT compartment, LV compartment for Relays, indications and controls. Each compartment shall be segregated from other by metallic partition. The shutters shall also be metallic for safety of operation staff.(Please refer DNIT for complete specification of item no.12) |
| 24 | Supply, installation, testing & commissioning of 3 Phase, 50Hz, 11KV, 800 Amp, 26.3KA/3Sec. outgoing VCB panel with copper busbar for indoor sub stations. The VCB should be floor mounted trolley type horizontal isolation, horizontal draw out, type Breaker as per IEC-62271-100 & Panel as per IEC- 6227I-200, as amended up to date. The panel shall be compartmentalized consisting of Bus bars compartment, Breaker compartment, Cable and CT compartment, LV compartment for Relays, indications and controls. Each compartment shall be segregated from other by metallic partition. The shutters shall also be metallic for safety of operation staff.(Please refer DNIT for complete specification of item no.13) |
| 25 | S/I/T/C of power pack with 220 Volt AC supply input and 24 Volt DC continuous output, suitable for closing/tripping/ indication of HT VCB breakers, provided with 2 Nos. 12 Volt each, SMF batteries of 100 AH capacity of make Exide/ Amaron/ Luminous only, Charging unit and suitable capacity of multifunction meter for current and voltage including connection with 2.5 Sq.mm FRLS insulated copper conductor cable etc. duly houses in cabinet of size (L x W x D) 36”x24”18” made of 14 gauge CRCE sheet having 4 Nos. legs of 8” length made of MS angle of size 50 x 50 x 6mm. The complete cabinet inner and outer side is powder coated of approved shade. The cabinet should have openable door on front side with locking arrangement complete be suitable for boost mode and trickle mode with display of input and output voltage and current and provided with suitable rating Miniature circuit breaker for protection at input supply and output of the battery charger. |
| 26 | MAIN PANEL (NORMAL SUPPLY) Supplying, Installation, Testing & Commissioning of Modular, Sectionalized (Form-4B Construction) Low Voltage Panel suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply system as per standard IEC 61439 Part-1 & Part-2 as Totally Type Tested Assembly and of suitable size fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers & doors of 1.6mm thick sheet, 3 mm thick for gland plates with stiffeners wherever required, having vibration free structure .(Please refer DNIT for complete specification of item no.15) |
| 27 | S/E of 4 nos. sand buckets of 10 ltr. Capacity each made out of 24 Gauge G.I sheet. The buckets with sand shall be hanged on Suitable size of angle iron stand fabricated out of 1 ¼ x 1 ¼ x1/8” angle iron having hooks for hanging the buckets in two rows. The job includes the cost of painting with two coats of red paint of superior quality after one coat of primer on buckets and stands to complete the job up to the entire satisfaction of the Engineer–in–charge. |
| 28 | Supply of Erection of medium size first aid box made of 16 gauge MS sheet of size 14”x7”x5” with 6 wound dressings, 3 burn dressings, 13 gms absorbent cotton wool, one dressing scissors, one bottle of spirit of sal volatile, 1 tube of burn ointment (Burnol) tablets of aspiring, 1 No. artificial respirator. |
| 29 | Supply and Erection of shock treatment chart written in Hindi and English and local language duly framed in wood frame with glass complete as required as per India Electricity Act. (Safety rules). |
| 30 | Supply and Erection of Fire Extinguishers ISI marked duly erected/ hung on wall with hooks including the cost of hooks with all material &labour required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of work. |
| 31 | CO2 type of 9 Kg capacity fire extinguishers conforming to IS. |
| 32 | S/E rubber mat of size 6’x3’x 12 mm thick (ISI mark) Wide of superior quality and of approved make as approved by the Engineer –in- Charger /EC to be laid on floor in HT room in Front of panels and transformers. |
| 33 | Supply and erection of CT/PT operated tri-vector meter of accuracy class 0.5 suitable for voltage rating 11 KV/110 Volt, current rating 100/5Amp. (As decided by DISCOM) for energy measurement and maximum demand etc. as per the specification of Chandigarh Electrical Department (CED). The three phase HT CT meter should be of Lauritz Knudsen / Secure / Genus/Saraf make only. The meter is to be got tested from the M&P Sub Division laboratory of the CED at the stake of contractor. The meter is to be installed in the existing metering compartment of the CT&PT unit on a wooden plank (on S/E basis) of suitable size including. The job also includes the cost of supply erection of 11 KV test terminal block for connecting secondary connection of 11KV CT/PT unit &Trivector meter as per site requirement. The job includes labour, taxes and duties etc. |
| 34 | Supply, Fabrication and Erection of cubical type dust and vermin proof metering panel, free standing floor mounting, made out of 14 Gauge M.S. sheet with channel for base frame to accommodate CT & PT dry type unit and set of Trivector Meter including fixing of MS angle /flat where ever required. The cubical panel should have two compartments, with double door having locking & reeling arrangements. (Please refer DNIT for complete specification of item no.22) |
| 35 | Supply and erection of HT XLPE insulated armoured power cable stranded aluminum conductor sheathed with extruded semi-conducting compound cross linked polyethylene insulated laid up inner sheathed of extruded PVC single layer of galvanized steel flat strip armoured and PVC sheathed over all suitable for 11 KV (earthed) cable to IS: 7098 (Part-ii) 2011 with up to date amendments and laying in the existing cable trey/ RCC pipe cable duct/ sand & brick for underground after the digging the trench. The XLPE cable shall be of Polycab / Havells / KEI / RR Kabel/ Finolex make only. |
| 36 | Size 95 sq. mm 3 core (in pipe) |
| 37 | Supply and laying of XLPE insulated PVC sheathed Aluminum conductor armoured cable of 1.1 KV grade as per IS 7098 (Part-I) 1988 (amended up to date) of the following sizes to be laid in existing Trench/Ducts/Cable Tray/ RCC/ HUME/ METAL/ DWC pipe / on surface with the help of MS clamps of suitable size/ as required at site to the entire satisfaction of Engineer-in-Charge. The job includes labour charges of laying the cable and making connections with suitable size aluminum lugs/thimbles etc.The cable shall be of Polycab / Havells / R.R. Kabel/ KEI/ Finolex make only. |
| 38 | Size 400 sq.mm 3.5 core |
| 39 | Size 185 sq.mm 3.5 core |
| 40 | Size 95 sq.mm 3.5 core |
| 41 | Size 16 sq.mm 4 core Please Enable Macros to View BoQ information |