| 1 | SITC of ISO certified company made air cooled ducted split type airconditioning machine with each having a capacity and details asmentioned below suitable for operation on R-32/R-410A R-407Green refrigerant comprising of single/twin Scroll / Rotary /Reciprocating type compressor hermatically sealed complete withautomatic capacity, safety switches, lubrication system,with min 5year OEM warranty both compressor and PCB , Suitable capacitysquirrel cage induction motor with class 'B' insulation suitable foroperation on 415 + 10% volts, 50 Hz, A.C. supply for Blower motor,Necessary drive arrangement for blower motor, Matching Air cooledcondenser with necessary fittings for refrigerant piping connections,necessary structural support for mounting condensers,Microprocessor based control panel complete with accessories,machine isolation / disconnect switch, valves and accessories tointer connect compressor and condender including pressure testing,vacuum. Necessary starters suitable for Indoor & outdoor unitcomplete with O/L , U/V, phase reversal protection, single phasepreventors etc complete as required. NABL accredeated as perIS/ISO/IEC 17025 standards / CPRI/ ERDA lab testing reports asper IS 1391 with OEM certificate must submitted to engineer incharge.All as per pre approved by Engineer in-charge. All as perpre approved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \\"A\\" attached with thisBSR .Ductable Split type |
| 2 | 11 TR |
| 3 | 5.5 TR |
| 4 | Supply and installation of copper refrigerant piping of required sizesduly insulated with closed cell elastomeric insulation thickness asspecified by manufacturer,as per pipe size and cabling betweenindoor and outdoor complete with proper supports etc for followingcapacity unit. All related civil work such as making hole, chasing inwall, shall be inclusive in the quoted price. |
| 5 | 1.8 TR WALL MOUNTED UNIT (3-Star Rated), R-32 Gas Inverter/Non Inverter |
| 6 | 11.0 TR DUCTABLE UNIT, R-22 gas, Non Inverter type |
| 7 | 5.5 TR DUCTABLE UNIT, R -22 gas, Non Inverter type |
| 8 | Communication cable between IDU & ODU |
| 9 | For Split AC (2.5 Sq mm X 4 C) |
| 10 | For Ducted AC (1.5 sq mm X 8 C) |
| 11 | To supply, install, test and commission PVC drain pipes dulyinsulated with 6 mm thick nitrile rubber and 'U ' traps from indoorunits to nearest drain point. |
| 12 | 32 mm dia |
| 13 | 25mm dia. |
| 14 | Out door stand for Split Ac (pre fabricated) |
| 15 | Out door stand MS frame for ducted AC |
| 16 | Supply , Installation, Testing and Comissioning of ducting made fromGSS of class VIII & fabricated as per IS:655 and as per approveddrawings & designs including the cost of hangers, supports, angle,expansion fasteners , closed cell neoprene gasket T&P etc. asrequired of following gauge:- All as per pre approved by Engineerin-charge. For additional technical parameters of products/ work ,refer Annexure \\"A\\" attached with this BSR .SITE FABRICATED GI SHEET DUCT |
| 17 | 0.63mm (24 G) |
| 18 | 0.80mm (22 G) |
| 19 | Supply, installation, testing and commissioning of terminal airdistribution equipment as per approved shop drawings, colour andspecifications. |
| 20 | Powder Coated aluminium linear grille with aluminium damper. |
| 21 | Powder Coated aluminium linear/square grille without damper. |
| 22 | Supply , Installation, Testing and Comissioning of site fabricated ducting made from GI sheet metal conforming to IS:277 with a zinc coating grade not less than 120 GSM (both side inclusive) & fabricated as per IS:655 and as per approved drawings & designs including the cost of hangers, supports, angle, expansion fasteners , closed cell neoprene gasket T&P etc. as required of following thickness. Test Certificate for Galavanizing with lot no. to be submitted. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 23 | 0.60 mm |
| 24 | 0.80mm |
| 25 | 1.00mm |
| 26 | 1.25mm |
| 27 | Supply , Installation, Testing and Comissioning of site fabricatedducting made from aluminium sheet conforming to IS:737, Grade31000 fabricated as per IS:655 and as per approved drawings &designs including the cost of hangers, supports , angle , expansionfasteners , closed cell neoprene gasket T&P etc. as required offollowing thickness. All as per pre approved by Engineer in-charge.For additional technical parameters of products/ work , referAnnexure \\"A\\" attached with this BSR . |
| 28 | 0.60 mm |
| 29 | 0.80mm |
| 30 | 1.00mm |
| 31 | 1.20mm |
| 32 | Supplying, installing, testing and balancing of extruded Aluminium Powder coated supply/return Grilles with fixed bars at front having 0 / 15 / 30 / 45 degrees deflection as required. with Flange size 20 mm with rounded edges including fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 33 | Supplying, installing, testing and balancing of double louvered ofextruded Aluminium Powder coated supply/return air grills of varioussizes, Each grill shall be with fixed aerofoil shaped horizontal frontbar at 0 deflection and back adjustable vertical louvers, airdistribution grid for straightening the air flow through the collar andregister including fixing with steel screws etc. complete in all respect.All as per pre approved by Engineer in-charge. For additionaltechnical parameters of products/ work , refer Annexure \\"A\\"attached with this BSR . |
| 34 | Supply air grill with key operated volume control damper |
| 35 | Return air grill without volume control damper |
| 36 | Supplying, installing and balancing of extruded Aluminium powder coated fresh air inlet louvers with bird screen & volume control damper fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 37 | Supply , installation, testing & balancing of 20 Gauge G I Damper with brass bushes and 6\\" pitch multiblade box type galvanised sheet steel construction volume control damper for Ducting and air washers to be provided with suitable links and quadrants for control of volume of air as per specifications complete as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 38 | Supply and fixing of acoustic lining of ducts with chemically cross link Oxide accetate foam open cell structure Acoustic Insulation with density 30 Kg / Sqm, UV protected and Class O Fire propperty Water Vapour absorption 0.002 gm / Sqcm, including cost of adhesive etc. complete in all respect. All as per pre approved by Engineer in-charge. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 39 | 10 mm thick |
| 40 | 15 mm thick |
| 41 | 25 mm thick |
| 42 | Supply and fixing duct insulation with 50 mm thick ExpandedPolystyrene Thermocol (ESP) sheet of density 24 kg/cu.m afterapplying two coats of cold setting adhesive (CPRX Compound) andbinding sheet with chicken wire mesh and applying cement mortarplaster (1:4) including primer & painting (suitable for outdooraplication) matching with building colour or as per direction ofEngineer incharge as required. All as per pre approved by Engineerin-charge. For additional technical parameters of products/ work ,refer Annexure \\"A\\" attached with this BSR . |
| 43 | Supply and fixing aluminium foil faced 50 mm thick Rock woolinsulation of density 36 kg/cu.m after applying two coats of coldsetting adhesive (CPRX Compound) sealing all joints with selfadhesive tape & finished with 26 G Aluminium cladding. complete inall respect. (For Outdoor applications-air conditioning ducts) All asper pre approved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \\"A\\" attached withthis BSR . |
| 44 | Supply & fixing of external thermal closed-cell Nitrile rubber Insulation material FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 in form of sheet on duct including cost of adhesive (CPRX Compound) complete as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 45 | 9mm thick for indoor Application |
| 46 | 13mm thick for indoor Application |
| 47 | 13mm thick for Outdoor Application with 26 SWG Aluminium Cladding |
| 48 | 19mm thick for Outdoor Application with 26 SWG Aluminium Cladding |
| 49 | Supplying, installing of external thermal closed cell cross linkedPolyethylene (XLPE) foam insulation made out from non-fibrous, fireretardant (FR), closed cell, tri-dimensional chemically crosslinkedpolyethylene foam. should be certified 'Class O' in Fire Propagationand 'Class 1' in Surface Spread of Flame as per BS 476 Part 6 &Part 7 respectively in the form of sheet on ducts including cost ofadhesive, tape complete as required. All as per pre approved byEngineer in-charge. For additional technical parameters of products/work , refer Annexure \\"A\\" attached with this BSR . |
| 50 | 9mm thick |
| 51 | 13mm thick |
| 52 | 25 mm thick |
| 53 | Supply and fixing duct insulation with 50 mm thick Expanded Polystyrene Thermocol (ESP) sheet of density 24 kg/cu.m after applying two coats of cold setting adhesive (CPRX Compound) and binding sheet with chicken wire mesh and applying 26 G aluminium cladding complete as required. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 54 | Supply, Installation, Testing & Commissioning of modulartype Variable Refrigerant Flow/Variable Refrigerant Volume aircooled Outdoor units suitable for cooling and heating, having100% hermetically sealed inverter type Scroll Compressor(s) withand minimum two compressors along with two Condensing fan,above 14/18 HP modules, microprocessor based Controller, Side /top discharge type condensing unit(s), with R-410 ARefrigerant, vibration isolators, with suitable foundationetc. complete as required. The unit shall deliver the ratedcapacity at AHRI Conditions and work even at 50°Cambient temperature without tripping. The unit shall be suitable towork on 400V +/- 10%, 3 Phase, 50Hz AC power supply. Theunit shall be filled with first charge of the refrigerant and ready foruse as required. The EER at 100% load with AHRI conditions shallnot be less than 3.5 and Including OEM supplied Piping connectionKit etc. as required. All as per pre approved by Engineer in-charge.For additional technical parameters of products/ work , referAnnexure \\"A\\" attached with this BSR . |
| 55 | Supplying and installation of high-pressure grade required size OEMmake copper connection Y or T Joints / refnet for liquid and suctionline complete erected on wall/ceiling with supports/raceways, Nitrilerubber insulation, painting etc. with brazing and testing for leakagesconfirming the normal operation of the VRV / VRF air conditioningsystem. All as per pre approved by Engineer in-charge. Foradditional technical parameters of products/ work , refer Annexure\\"A\\" attached with this BSR . |
| 56 | Gas charging of VRF/VRV system with R410A refrigerant gas.Before gas charging system shall be flushed with high purityNitrogen Gas to remove carbon content, dirt particles to make surethat there is no chance of mixing any impurity with Refrigerant Gas.Thereafter System shall be tested with Nitrogen Gas at 1.5 Times ofworking pressure of R410 Refrigerant Gas to ensure leakproofsystem. Whole system shall be Vacuumed up to 500-micron levelwhich ensures the zero-moisture content level in piping to ensurebetter cooling efficiency and long life of the system. All as per preapproved by Engineer in-charge. For additional technicalparameters of products/ work , refer Annexure \\"A\\" attached withthis BSR . |
| 57 | Supply & Fixing of FR PVC insulated & sheathed 3 core flexible copper conductor as per PWD specification for electrical Works confirming to IS:694 and as per IS 8130 : 2013 of 1.1 kV grade .Wire should be made from 99.99% purity copper, class 5 stranding in acc. to IEC 60228 for lower watt loss , oxygen free (<10 ppm) forless chances of oxidization and higher silver content for gives betterconductivity , insulation PVC type A ,flame retardant as per IS10810-53, better amperage rating as per VDE 0298 part 4 includingmaking connection etc. as required. OEM Must have its own inhouse NABL lab setup for all testing facilities for wires. All as per preapproved by Engineer in charge, making connections. Foradditional technical parameters of products/ work , refer Annexure\\"A\\" attached with this BSR . |
| 58 | 4 core x 2.5 Sq.mm |
| 59 | Supply, installation, testing and comissioning of interconnecting copper refrigerant piping of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. duly insulated with tubular elastomeric nitrile rubber FM/UL approved with high water vapor diffusion resistance and low thermal conductivity should be certified 'Class O' in Fire Propagation as per BS 476 Part 6 including chase cutting andfilling with mortar, Slotted channel supports mounted on 10 mm threaded rod at suitable spacing the exposed piping shall be wrapped with glass woven cloth and lag coating for vapour barrier and weather protection. Joints shall be covered with nitrile rubber tape of 3 mm thick complete as required of following sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 60 | 25 mm O.D., wall thinkness ≥ 1.2mm (insulation – 19 mm thick) |
| 61 | 19.1 mm O.D., wall thinkness ≥ 1.0mm (insulation – 13 mm thick) |
| 62 | 12.7 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick) |
| 63 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 64 | 20 mm |
| 65 | 25 mm |
| 66 | 40 mm |
| 67 | Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrial plug top making connection etc complete in all respect. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 68 | 3 KVA |
| 69 | 4 KVA |
| 70 | 5 KVA |
| 71 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 72 | 50 mm dia per running inch length |
| 73 | 100 mm dia per running inch length |
| 74 | 150 mm dia per running inch length |
| 75 | 200 mm dia per running inch length |
| 76 | Providing and making wall openings in existing stone masonary wall complete with all requited T & P , Scafolding and providing lintel of required size and strength, repairing ,plastering and cleaning the site debrises as required. |
| 77 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 78 | P & F of trap door for AHU / FCU's in existing false ceiling dulymade from 12 mm thick laminated board, hinged with wooden frameof cheed wood size 50mm x 80mm, Frame suspended with MS strip25 x 3 mm with ancor fastner min 8 supports from ceiling, Hinges,Locking arrangement etc as required. All as per pre approved byEngineer in-charge. For additional technical parameters of products/work , refer Annexure \\"A\\" attached with this BSR . |
| 79 | Supply and Installation of Box type EU13 Hepa Filter of 99.997% efficiency down to 0.3 micron particle size installed in zero leakage Aluminium frame as per ISO 14644-1 clean room including sealing and packing material cost like silicon and hardware cost and Labour cost for the dismantling of existing worn out filters & shifting the same to the store as required as under. All as per pre approved by Engineer in-charge. For additional technical parameters of products/ work , refer Annexure \\"A\\" attached with this BSR . |
| 80 | 305 mm Thick |
| 81 | 150 mm thick |
| 82 | Dismantling of split air conditioner of any capacity/any type including existing indoor unit & outdoor unit , refrigerant piping , connecting cables , drain pipe etc. including shifting of dismentaled material to store complete as required |
| 83 | Supplying and charging of fresh refrigerant and testing of performance of air conditioner/ fridge/ water cooler of following capacity including capillary and strainer/ filter. |
| 84 | 1.0 TR Window/ Split A.C. |
| 85 | 1.5 TR Window/ Split A.C. |
| 86 | 2.0 TR Window/ Split A.C. |
| 87 | 25/50 / 40/80 Ltr. Water cooler |
| 88 | 150/150 Ltr. Water cooler |
| 89 | 165 Ltr Refrigerator |
| 90 | Replacement of defective compressor by company repaired compressor as per OEM recommendations of following gadgets including testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 91 | 1.0 TR A.C. |
| 92 | 1.5 TR A.C. |
| 93 | 2.0 TR A.C. |
| 94 | 25/50 / 40/80 Ltr. Water cooler |
| 95 | 60/120 Ltr. Water cooler |
| 96 | 150/150 Ltr. Water cooler |
| 97 | 165 Ltr Refrigerator |
| 98 | 200/210 Ltr Refrigerator |
| 99 | 280/310 Ltr Refrigerator |
| 100 | P & Replacement of condensing/ cooling coil of copper fins for following capacity A.C./ Water cooler/ Fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 101 | 1.0 TR A.C. |
| 102 | 1.5 TR A.C. |
| 103 | 2.0 TR A.C. |
| 104 | 25/50/40/80 Ltr. |
| 105 | 150/150 Ltr. Water cooler |
| 106 | 165 Ltr Refrigerator |
| 107 | Servicing of 1.0/1.5/2.0 TR capacity Split/ Window type air conditioner |
| 108 | P & Replacement of overload protection of A.C./ Water cooler as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 109 | P & Replacement of thermostat of A.C./ Water cooler/fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor |
| 110 | P & Replacement of selector switch of 1.0/1.5/2.0 TR A.C Fan as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 111 | P & Replacement of starting relay of A.C/water cooler/fridge compressor as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 112 | P & Replacement of door liner of 165/200 Ltr. Fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 113 | P & Replacement of door gasket of 165/200 Ltr. Fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 114 | S & F of capacitor of 230V/ 275V, 50Hz rating of plastic casing and terminals -Lugs or copper wire. |
| 115 | Running capacitor |
| 116 | 40-60 micro farad |
| 117 | 60-80 micro farad |
| 118 | 80-100 micro farad |
| 119 | 120-150 micro farad Please Enable Macros to View BoQ information |