| 1 | Taking out old rusted LT Panel/Feeder box/bus bar box complete all as specified and directed. |
| 2 | Design, fabricate, supply ,install, testing and commissioning of LT panel indoor type 415 Volts, 50 Hz, 3 phase, 4 wire totally enclosed self supporting structure fully compartmentalized suitable for indoor use with bottom cable entry with suitable cable glands, made out of CRCA sheet 2mm thick with angle iron frame works with suitable legs of ISA 50x50x5mm with four legs grouted PCC (1:2:4) type B1 foundation block, pedestal of 30cm height from ground level with suitable nuts, bolts and washers etc. detachable plate shall be provided at the bottom of the panel with necessary holes suitable for termination of various sizes of cables with glands and suitable mounting arrangement for aluminium bus bars 600 Amps capacity, suitable size copper wire for internal power and control wiring, hinged door at front with suitable locking arrangement, provision of air vent at both sides, both side openable, CPRI approved, dust and vermin proof, powder coated for accommodating the following accessories and incoming/outgoing switchgears complete all as specified and directed (Location : BD-I) :- Incoming : (a) MCCB 400 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 36 KA,-01 NoOutgoing :(b) MCCB 250 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 25 KA,-02 Nos(c) MCCB 100 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 16 KA,-04 Nos(d) MCCB 63 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 16 KA,-03 Nos(e) Automatic Transfer Switch/Automatic On Load Change Over Switch, 250 Amps, 4 Pole, 415 V, 50 Hz -01 No(f) Digital Volt meter with selector switch (0-500 V)-01 No(g) Digital Ammeter with selector switch-01 No(h) CT's 600/5- set of 3 No(j) LED Indication lamps (RYB)-one set |
| 3 | Design, fabricate, supply , install, testing and commissioning of LT panel indoor type 415 Volts, 50 Hz, 3 phase, 4 wire totally enclosed self supporting structure fully compartmentalized suitable for indoor use with bottom cable entry with suitable cable glands, made out of CRCA sheet 2mm thick with angle iron frame works with suitable legs of ISA 50x50x5mm with four legs grouted PCC (1:2:4) type B1 foundation block, pedestal of 30cm height from ground level with suitable nuts, bolts and washers etc. detachable plate shall be provided at the bottom of the panel with necessary holes suitable for termination of various sizes of cables with glands and suitable mounting arrangement for aluminium bus bars 600 Amps capacity, suitable size copper wire for internal power and control wiring, hinged door at front with suitable locking arrangement, provision of air vent at both sides, both side openable, CPRI approved, dust and vermin proof, powder coated for accommodating the following accessories and incoming/outgoing switchgears complete all as specified and directed (Location : BD-II) :-Incoming :(a) MCCB 400 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 36 KA,-01 NoOutgoing :(b) MCCB 250 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 25 KA,-02 Nos(c) MCCB 100 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 16 KA,-03 Nos(d) Digital Volt meter with selector switch (0-500 V)-01 No(e) Digital Ammeter with selector switch-01 No(f) CT's 600/5- set of 3 No(g) LED Indication lamps (RYB)-one set |
| 4 | Design, fabricate, supply , install, testing and commissioning of LT panel outdoor type 415 Volts, 50 Hz, 3 phase, 4 wire totally enclosed self supporting structure fully compartmentalized, with sloping canopy, suitable for outdoor use with bottom cable entry with suitable cable glands, made out of CRCA sheet 3.15mm thick with angle iron frame works with suitable legs of ISA 50x50x5mm with four legs grouted PCC (1:2:4) type B1 foundation block pedestal of 30cm height from ground level with suitable nuts, bolts and washers etc. detachable plate shall be provided at the bottom of the panel with necessary holes suitable for termination of various sizes of cables with glands, with suitable mounting arrangement for aluminium bus bars 400 Amps capacity, suitable size copper wire for internal power and control wiring, hinged door at front with suitable locking arrangement, provision of air vent at both sides, both side openable CPRI approved, dust and vermin proof, powder coated for accommodating the following accessories and incoming/outgoing switchgears complete all as specified and directed :-Incoming(a) MCCB 400 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 36 KA,-01 NoOutgoing(b) MCCB 250 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 25 KA,-02 Nos(c) MCCB 63 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 16 KA,-03 Nos(d) Digital Volt meter with selector switch (0-500 V)-01 No(e) Digital Ammeter with selector switch-01 No(f) CT's 400/5- set of 3 No(g) LED Indication lamps (RYB)-one set |
| 5 | All as per item No 4 hereinbefore but with the following switchgears:Incomer :(c) MCCB 200 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 25 KA,- 01 Nos(d) MCCB 100 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 16 KA,- 03 Nos(e) MCCB 63 Amp, 4 Pole, 415 V, 50 Hz with rupturing capacity 16 KA,- 01 Nos(f) Digital Volt meter with selector switch (0-500 V)-01 No(g) Digital Ammeter with selector switch-01 No(h) CT's 400/5- set of 3 No(j) LED Indication lamps (RYB)-one set |
| 6 | Design, Supply, installation, testing and commissioning of LT out door loop in loop out panel board (feeder box) with sloping canopy of size 1000mmx500mmx300mm made out of 3.15 mm thick CRCA sheet duly painted with two coat of powder coated paint over a coat of red oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 40x 10mm for three phase and neutral 200mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 200 Amps, 4 pole, 415 Amps, 50 Hz of breaking capacity 36 KA as incomer complete all as specified and directed by Engineer-in-Charge. |
| 7 | Design, Supply, installation, testing and commissioning of LT out door loop in loop out panel board (feeder box) with sloping canopy of size 1000mmx500mmx300mm made out of 3.15 mm thick CRCA sheet duly painted with two coat of powder coated paint over a coat of red oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 40x 10mm for three phase and neutral 200mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 125 Amps, 4 pole, 415 Amps, 50 Hz of breaking capacity 16 KA as incomer complete all as specified and directed by Engineer-in-Charge. |
| 8 | Design, Supply, installation, testing and commissioning of LT out door loop in loop out panel board (feeder box) with sloping canopy of size 1000mmx500mmx300mm made out of 3.15 mm thick CRCA sheet duly painted with two coat of powder coated paint over a coat of red oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 40x 10mm for three phase and neutral 200mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 63Amps, 4 pole, 415 Amps, 50 Hz of breaking capacity 16 KA as incomer complete all as specified and directed by Engineer-in-Charge. |
| 9 | Supply, installation, testing and commissioning of Bus Bar Box (junction box) with sloping canopy of size 1000mmx500mmx300mm made out of 3.15 mm thick CRCA sheet duly painted with two coat of powder coated paint over a coat of red oxide, front and rear hinged doors mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4;8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 40x 10mm for three phase and neutral 200mm length respectively mounted on insulators and terminating with suitable cable with glands complete all as specified and directed by Engineer-in-Charge. |
| 10 | M & L for Earthing complete with galvanised steel earth plate electrode 600mmx600mmx6mm size buried directly in ground vertically to a depth not less than 2.25 mm below ground level with top edge of the plate not less than 1.5 metre below normal ground level, connected to galvanised earth strip 25x4 mm size protected by 40 mm light grade pipe upto 7.5 m length by means of bolts, nuts, check nuts and washers made out of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part-1 including necessary excavation earth work, drilling of holes for electrode, PCC 1:3:6 type C1, RCC cover slab, 50 mm thick with 1:2:4 type B1, using 8 mm CTD bars 140 mm C/C both- way with suitable handle, watering pipe 20 mm dia light grade GI, funnel, charcoal, salt all as specified and as directed by Engineer in charge including taking down old u/s earthing assembly complete all as specified and directed. |
| 11 | Supply and fixing in repair MCCB 4 pole 63/100 Amps 415 volts of breaking capacity 16 KA fixed type complete all as specified and directed. |
| 12 | Supply and fixing in repair MCCB 4 pole 160 Amps 415 volts of breaking capacity 36 KA fixed type complete all as specified and directed. |
| 13 | Supply and fixing in repair MCCB 4 pole 200 Amps 415 volts of breaking capacity 36 KA fixed type complete all as specified and directed. |
| 14 | Supply and fixing in repair MCCB 4 pole 250 Amps 415 volts of breaking capacity 36 KA fixed type complete all as specified and directed. |
| 15 | Supply and fixing in repair MCCB 4 pole 400 Amps, 50Hz 415 volts of breaking capacity 36 KA fixed type complete all as specified and directed. |
| 16 | Supply and fixing in repair MCCB 4 pole 630 Amps, 50Hz 415 volts of breaking capacity 50 KA fixed type complete all as specified and directed. |
| 17 | M & L for preparing to old painted steel/metal surface of any description over 10 CM in width or girth of LT panel/Feeder box/bus bar box of indoor/Outdoor type at various locations and applying two coats of synthetic enamel paint with fine quality with suitable spray gun including writing of panel details complete all as specified and directed. Note:-(i) Writing includes SL No, details of Incoming and outgoing, area indication as directed by Engineer- in-Charge |
| 18 | Taking shutdown from MES, disconnecting all electric connections and opening of LT panel of any description for repair etc., reassembling of the same after all necessary repair, refixing, replacement of unserviceable components, reconnecting, commissioning and testing to the entire satisfaction of Engineer-in-Charge.NOTE: Supply only spares/components will be measured and paid for separately under respective items of BoQ. |
| 19 | Supply only analogue Ammeter 0-300 Amp of size 96 x 96 mm with selector switch complete all as specified and directed. |
| 20 | Supply only analogue Voltmeter 30-600 Volt of size 96 x 96 mm with selector switch complete all as specified and directed. |
| 21 | Supply only LED lamp, RYB indication complete all as specified and directed. |
| 22 | Cutting out existing worn out/ damaged CRCA sheet of LT panel board and providing new CRCA sheet of thickness not less than 3 mm including necessary welding, sheet metal repair work and applying two coats of synthetic enamel paint over a coat of red oxide primer after preparation of surfaces complete all as directed. |
| 23 | M&L for making LT panel doors operateable to the entire satisfaction of Engineer-in-Charge by providing new hinges of existing size & pattern including necessary welding, sheet metal repair work and applying two coats of synthetic enamel paint after preparation of surfaces and filling the undulation with ready made putty for MS/steel surfaces, complete all as directed. |
| 24 | Note : Amount of credit for retrieved materials is mentioned in Sch 'A' Section-II of tender documents in pdf form which will be deducted while acceptance of tender offline. Please Enable Macros to View BoQ information |