| 1 | Removing / Dismantling the existing DG Sets alongwith alternator complete including Diesel tank, panel boards, cables, silencer pipe etc and transporting the entire plant machineries to MES store yard approx 3 Km complete. The existing DG Sets, panel board and plinth / foundations shall be totally demolished to ground level and the debris shall be removed to a distance of 500 mtrs and to make good the disturbed floor to match with the existing floor finish complete all as specified and as directed. |
| 2 | Supply, installing, testing and commissioning, factory assembled silent Diesel Engine driven Generator set conforming ISO-8528, fully wired alternator AC, to give an out put of 180 kVA continuously rating at a power factor 0.8 lagging, 3 phase 4 wire, 415 volts 50 Hz ± 1% supply, 1500 RPM, CPCB IV+ regulation, directly coupled with diesel engine liquid cooled mounted on common base frame complete with floor mounting fuel tank (Min 3mm thickness) & accessories, vibration damper pads, Standard Control Panel With Controller DSE 6120 MK III, Engine Safeties & Protections Battery With Leads, as per OEM etcincluding Exhaust gas piping of 125 mm dia MS black Class-B pipe welded including all necessary fitting reducer, flange, bend etc support & clamps with 50X50X3 mm equal angle and anti vibration mounting insulation of exhaust system with 50 mm thick mineral wool coverd with wire mesh and aluminium cladding (from DG set to out side of the building and comprising of following :- |
| 3 | Ser. Item No. 2.00 Contd....(A) Diesel Engine : Liquid cooled turbo charged with after cooler to deliver suitable BHP at 1500 RPM under NTP conditions of BS 5514 and conforming to ISO 3046, with an overload capacity of 10% for one hour in any 12 hours continuous operation with the following accessories, Diesel engine of rated speed at full load electric start developing with system with radiator and including electronic governor control of class G-3, engine control panel, lub oil pump, water pump, fuel tank, exhaust pipe with silencer and suitable for electric start with batteries of adequate capacity and suitable for alternator of specified capacity complete with fly wheel direct/ flexible coupling and coupling guard complete.(a) Radiator with blower fan or heat exchanger with guard.(b) Pipe coupling for engine cooling system piping.(c) Corrosion inhibitor coolant |
| 4 | Ser. Item No. 2.00 Contd....(d) Paper element filters (i) Fuel filter (ii) Lube oil filter (iii) By pass(e) Fly wheel housing and fly wheel to suit alternator.(f) Engine bearing mechanism in fly wheel housing.(g) Shut off coil with safety for LLOP/HWT/over speed.(h) Dry type air cleaners and vacuum indicators.(j) Residential silencers.(k) Stainless steel exhaust flexible bellows.(l) BLANK(m) Battery charging alternator. |
| 5 | Ser. Item No. 2.00 Contd....(o) Electronic instrument panel, complete with all accessories as per manufacturer's specifications displaying the following:- (i) Battery as per OEM specified (ii) Water temperature. (iii) Lubricating oil pressure. (iv) Engine speed -1500 Rpm (v) Engine hours (vi) Frequency. (vii) Voltage.(p) Safety control (Trip and indication). (i) High water temperature (ii) Low lube oil temperature (iii) Overspeed stop |
| 6 | Ser. Item No. 2.00 Contd....(q) Base frame : Sturdy, fabricated welded construction, channel iron base frame (duly painted) for mounting engine and alternator as per manufacturer's design alonwith Anti vibration material pads.(q) Battery : as per OEM specified, maintenance free battery conforming to IS:14257 with leads & terminals.(B) Alternator : Suitable rated 180 kVA, 0.8 PF, 415 Volts, 3 Phase, 4 Wire, 50 Hz at 1500 RPM, self excited and self regulated with AVR brushles, screen protected, drip proof, insulation class-H, IP -23, voltage regulation Automatic self ventilated and conforming to IS- 13364 Part-II suitable for engine as mentioned here-in before.(C) Acoustic Enclosure : M&L for acoustic enclosure for the above180 kVA DG set to reduce noise level to 75 dB measured at 1.0 meter distance for audiable frequencies as per guide of Central Pollution Control Board and manufacturer's specification and comprising of following from authorised GOEMs of Gen Set manufacturer's specification(D) Contractors shall satisfactorily conduct load test of each DG set for 12 hours including run on 10% overload for 1 hour, Testing eqpt (load bank) and fuel will be arranged by the Contractor under his own arrngement and cost. |
| 7 | Supply and installation, testing of AMF Panel outdoor type suitable for AMF 180 KVA with factory made type panel weather proof, vermin proof, fully ventilated both side opening and fabricated out of 3.00 mm thick CRCA sheet & mounting channel 75 mm having bus bar of aluminum 300 Amps cap, Three phase and One Neutral fixed on insulator and bus bar insulated by colored heat shrinkable sleeve & housed in specified compartment both side openable including powder coating internally / externally the entire steel surfaces. All the cover shall have with suitable locking arrangements, fully internally wired with suitable size of thimbles. Incoming/outgoing internal connection with PVC insulated PVC sheathed multi stranded copper wire of suitable size all as directed The panel shall be provided with 04 Nos 25mmx25mmx3mm thick angle iron suppons of not less than each 0.6 mtr height duly painted with anti corrosive black paint and grouted on floor/well atc and suitable fixing amanament as per she requirement connection to the existing earthing., including PCC 1:3:6 & termination of incoming and outgoing cable with lugs, gland complete & comprising of following :- |
| 8 | Ser. Item No. 3.00 Contd....Under voltage relay 415v AC for main - 1 NoUnder voltage relay 415 v AC for DG - 1 NoAC timer 230 volt, 2 No. +2 NC 1 NoDC timer 14 V - 1 NoControl MCB SP 16 A - As requiredControl MCB SP 6 A - As requiredAutomatic battery charger 24 volts- 1 NoLED indicating light for Main & DG - 6 Nos.LED indicating light for Main & Gen. On - 2 NosLED indicating light for battery charger - 1 NoVAF Meter - 2 NosAMF Controler 3 Phase 4 wire - 1 NoVolt meter selector switch - 1 NoAmp meter selector switch - 3 Nos.CT 500/5 Amp - 1 NoDC volt meter 15/30 V - 1 NoDC amp meter 0 - 15 A - 1 NoTrickle / boost switch - 1 NoAuto / manual switch - 1 NoPush button start & stop with elements-2 NosPower contactor 250 A, 4 Pole - 2 NosMCCB 315 Amp 35 ka 3 pole for main & DG supply - 2 NosControl relay -1 setOver load relay 2.5-4A - 1 NoBus bar 500 A 3 strips & N/L 250 A, Aluminium - 1 Set |
| 9 | All as per Ser. Item No. 2.00 above but Diesel Engine driven generator set conforming ISO-8528, fully wired alternator AC, to give an out put of 160 kVA continuously rating complete all as specified and as directed. |
| 10 | All as per Ser. Item No. 3.00 above but suitable for AMF 160 KVA with factory made type panel complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 11 | All as per Ser. Item No. 3.00 above but suitable for AMF 160 KVA with factory made type panel complete all as specified and as directed. Please Enable Macros to View BoQ information |