| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Repair /Maint to Low Tension Power distribution system at A Mess, HQNC, Command Camp and other locations under GE (Utilities) Udhampur Contract No: GE/U-23/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Supplying and laying in replacement of GI tubing medium grade for cable protection in trenches/duct/fixing to pole/wall or in such similar position of following size complete all as specified and directed by Engineer-in-Charge:- |
| 3 | 100 mm dia |
| 4 | 80 mm dia |
| 5 | 50 mm dia |
| 6 | 40 mm dia |
| 7 | Taking up old unserviceable LT UG cables from trench/poles/wall etc of following size complete all as specified and directed by Engineer-in-Charge:- |
| 8 | 25 Sqmm 3.5 core |
| 9 | 35 Sqmm 3.5 core |
| 10 | 95 Sqmm 3.5 core |
| 11 | 120 Sqmm 3.5 core |
| 12 | 185 Sqmm 3.5 core |
| 13 | 240 Sqmm 3.5 core |
| 14 | 300 Sqmm 3.5 core |
| 15 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of following sizes all as specified and directed :- |
| 16 | 25 Sqmm 3.5 core |
| 17 | 35 Sqmm 3.5 core |
| 18 | 95 Sqmm 3.5 core |
| 19 | 120 Sqmm 3.5 core |
| 20 | 185 Sqmm 3.5 core |
| 21 | 240 Sqmm 3.5 core |
| 22 | 300 Sqmm 3.5 core |
| 23 | Excavation in soft / loose soil not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out incl forming of bottom for laying cable complete all as specified and directed by Engineer-in-Charge. |
| 24 | Excavation in hard / dense soil Including road cutting etc not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out incl forming of bottom for laying cable complete all as specified and directed by Engineer-in-Charge. |
| 25 | Returning filling using excavated soil including spreading leveling, watering and well ramming in layers n exc 25 cms complete all as specified and directed by Engineer-in-Charge. |
| 26 | Removal of surplus excavated material n.exc 50 mtrs and depositing where directed at a level n.exc 1.5 mtrs above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 27 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 160A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 28 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 200A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 29 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 250A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 30 | Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 320A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 31 | Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 400A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 32 | Supply and fix in replacement MCB, 415 volts, 4 pole 36 KA, 630A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 33 | Supply and fix in replacement MCCB, 415 volts, 3 pole 10 KA, 63 A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 34 | Supply and fix in replacement MCCB, 415 volts, 3 pole 16 KA, 100 A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 35 | Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 125A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 36 | Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 160A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 37 | Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 200A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 38 | Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 250A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 39 | Supply and fix in replacement MCCB, 415 volts, 3 pole 36 KA, 320A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 40 | M&L for straight through jointing kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed and making the disturbed surface after relaying the cable and making joints suitable for aluminium conductor of size 16 to 25 Sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge.Note : Taking down the fault cable, excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this sch. |
| 41 | Description all as per Ser item No-21.00 here-in-before, but size of 35 to 70 Sqmm 3.5 core |
| 42 | Description all as per Ser item No-21.00 here-in-before, but size of 95 to 150 Sqmm 3.5 core |
| 43 | Description all as per Ser item No-21.00 here-in-before, but size of 185 to 240 Sqmm 3.5 core |
| 44 | Description all as per Ser item No-21.00 here-in-before, but size of 300 to 400 Sqmm 3.5 core |
| 45 | Supply & laying in replacement DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 50 mm and inner dia 38 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed by Engineer-in-Charge. |
| 46 | Description all as per Ser item No-26.00 here-in-before, but outer dia of 63 mm and inner dia 50 mm. |
| 47 | Description all as per Ser item No-26.00 here-in-before, but outer dia of 90 mm and inner dia 76 mm . |
| 48 | Description all as per Ser item No-26.00 here-in-before, but outer dia of 110 mm and inner dia 95 mm. |
| 49 | Description all as per Ser item No-26.00 here-in-before, but outer dia of 120 mm and inner dia 103.5 mm. |
| 50 | M&L for disconnecting LT supply and taking out defective LT draw out EDO type ACB 440 V suitable for 800 Amps to 1250Amps and servicing by OEM .i.e Auth dealer cleaning the fixed and moving all parts, removing dust particles by using high speed blower applying grease/jelly to moving mechanism and moving parts, tightening nut bolts of all the components of ACB and complete testing and putting on full load complete all as specified and directed by Engineer-in-Charge. |
| 51 | S&F in replacement of isolating JAW contacts suitable for 800 Amps to 1250Amps LT draw out EDO type ACB complete all as specified and directed by Engineer-in-Charge. |
| 52 | S&F in replacement of polyester resin cast CT 800 / 5A suitable for 800 Amps to 1250Amps LT draw out EDO type ACB as per existing make and model complete all as specified and directed by Engineer-in-Charge at site. |
| 53 | S&F in replacement of ARC Chutes for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site |
| 54 | S&F in replacement of Pole Unit for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site |
| 55 | S&F in replacement of Draw out terminals for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site |
| 56 | S&F in replacement of Lower terminals for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site |
| 57 | S&F in replacement of Upper terminals for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site |
| 58 | S&F in replacement of Charging motor for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as directed at site. |
| 59 | S&F in replacement of shunt trip and closing coil for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps complete all as specified and directed by Engineer-in-Charge. |
| 60 | S&F in replacement of manual Charging handle for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site. |
| 61 | S&F in replacement of under voltage trip device compact with UVT coil for Air circuit brekers EDO type suitable for 800Amp/ 630Amp as per existing make and model complete all as specified and directed by Engineer-in-Charge at site |
| 62 | S&F in replacement of Safety shutter assembly for Air circuit brekers EDO type suitable for 800Amp/630Amp as per existing make and model complete all as specified and directed by Engineer-in-Charge at site. |
| 63 | S&F in replacement of Earth fault relay with NCT for Air circuit brekers EDO type suitable for 800/630 Amp as per existing make and model complete all as specified and directed by Engineer-in-Charge at site |
| 64 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet of Min size 1.5MX1.2MX0.75M with digital Volt meter, Ammeter, with CTs ,Led lamps RYBN busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete all as specified and directed by Engineer-in-Charge with following :-Incoming(a) MCCB 630A 4 pole 50A, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No. |
| 65 | Outgoing (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 1200 Amp,4 pole, not less than 1 MTR long mounted on insulators - 01 setNote- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level(iii) Outgoing MCCBs shall be fed with solid busbar connectors(iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately. |
| 66 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet of Min size 1.5MX1.2MX0.75M with digital Volt meter, Ammeter, with CTs ,Led lamps RYBN busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete all as specified and directed by Engineer-in-Charge with following :-Incoming(a) ACB 1000 AMPS 4 pole 50A, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No. Outgoing(b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 1500 Amp,4 pole, not less than 1 MTR long mounted on insulators - 01 set |
| 67 | Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level(iii) Outgoing MCCBs shall be fed with solid busbar connectors(iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately. |
| 68 | Supply and pasting of stickers on transformer/Panel body using industrial-grade adhesive of custom-designed glue-based weatherproof stickers for transformers, size 6\\"x4\\", UV & water-resistant with the Following Details. Material: Vinyl or equivalent high-grade sticker with lamination. Note: 1) Sticker will be full-color digital print with lamination for UV protection. (surface to be cleaned before pasting). 2) Words (in English) for printing will be given by Engineer-in-charge during Execution. |
| 69 | Supply and installation of heat shrinkable/PVC cable sleeves with color-coded as per phase identification (Red, Yellow, Blue, Black, Green), suitable for LT Aluminium/aluminum cables of sizes ranging from 16 mm² to 300 mm², with thickness not less than 1.2 mm and temperature rating ≥ 90°C. The scope includes cutting, cleaning of cables, and proper application of sleeves with hot air gun or flame torch to ensure tight adhesion without air pockets. Work shall conform to IS: 7098/IS: 13592 and standard electrical practices complete all as specified and directed by Engineer-in-Charge. |
| 70 | M&L for aluminium thimble cable (Lugs) suitable for Cable of size 25 sqmm to 70 Sqmm complete all as specified and directed by Engineer-in-Charge. |
| 71 | Description all as per Ser item No 49.00 here-in-before, but size 95 Sqmm to 120 Sqmm |
| 72 | Description all as per Ser item No 49.00 here-in-before, but size 150 Sqmm to 240 Sqmm |
| 73 | Description all as per Ser item No 49.00 here-in-before, but size 300 Sqmm to 400 Sqmm |
| 74 | Supply, install, 200 amp copper Bus bar with enclouser wall mounted size 800 mmX600 mmX300mm ,suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system with 160 Amps 4 pole 25KA MCCB , dust and vermin proof, made of 2 mm CRCA MS sheet for cable entry and locking arrangement complete all as specifiled and directed by Engineer-in-charge. |
| 75 | M&L Plain cement concrete 1:3:6 type C-2 as in foundations filling and mass concrete using 40 mm graded stone aggregate for repair of copping of poles, LT Panels foundation etc complete all as specifiled and directed by Engineer-in-charge. |
| 76 | Earthing complete with GI earth electrode of size 60cmx60cmx6mm buried directly in ground vertically at a depth not less than 2.25 meter below normal ground level with top edge of earth plate at a depth not less than 1.5 meter below normal ground surrounded from all sides by 15 CM thick and packed layer of charcoal dust and common salt filling in alternate layers cleaned connected to and including GI earth strip 32X6 mm size up to 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected light grade 20 mm bore for watering and including funnel wire mesh, RCC pit cover 50 mm thick and PCC chamber pit with PCC 1:3:6 type C-2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 meter) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 all as specified and directed.Note :- Contractor Shall provide earth pit chamber board of 3.15mm thick mild steel sheet of size 45cmX30cm fixed with12mm thick MS rod two nos up to 90 cm height by nuts/bolts including spray painting with two coats of synthetic enamel black paint complete MS sheet both side including writing letters 6cm height i.e Eart pit No, Location, Earthing test Value and date complete all as specified and directed by Engineer-in-Charge. |
| 77 | Taking down/Dismantling of old unserviceable/corroded ACSR Conductor of any size from existing over head lines completed and supply, lay and fix aerial bunched cable 1.1KV grade stranded and compact aluminium phase conductor of size 4 x120sqmm + 1x95 sqmm (bare messenger with steel wire) with Aluminium alloy and Junction box The phase conductor shall be insulated with XLPE (Sioplas) compound Aluminium as per IS-14225-1995 including all fittings such as anchor clamp, suspension clamp, line connector, service clamp, Including End joints insulator piercing connectors, for taps from bare line etc, complete all as specified and directed by Engineer-in-Charge. Make : Grandlay/ Havells/ SCI/ Plycab |
| 78 | Taking down/Dismantling of old unserviceable/corroded ACSR Conductor of any size from existing over head lines completed and supply, lay and fix aerial bunched cable 1.1KV grade stranded and compact aluminium phase conductor of size 4 x 150sqmm + 1x120 sqmm (bare messenger with steel wire) with Aluminium alloy and Junction box The phase conductor shall be insulated with XLPE (Sioplas) compound Aluminium as per IS-14225-1995 including all fittings such as anchor clamp, suspension clamp, line connector, service clamp, Including End joints insulator piercing connectors, for taps from bare line etc, complete all as specified and directed by Engineer-in-Charge. Make : Grandlay/ Havells/ SCI/ Plycab |
| 79 | Taking down/Dismantling of old unserviceable/corroded ACSR Conductor of any size from existing over head lines completed and supply, lay and fix aerial bunched cable 1.1KV grade stranded and compact aluminium phase conductor of size 3.5 x 35 sqmm + 1x25 sqmm (bare messenger with steel wire) with Aluminium alloy and Junction box The phase conductor shall be insulated with XLPE (Sioplas) compound Aluminium as per IS-14225-1995 including all fittings such as anchor clamp, suspension clamp, line connector, service clamp, Including End joints insulator piercing connectors, for taps from bare line etc, complete all as specified and directed by Engineer-in-Charge. Make : Grandlay/ Havells/ SCI/ Plycab |
| 80 | Taking down/Dismantling of old unserviceable/corroded ACSR Conductor of any size from existing over head lines completed and supply, lay and fix aerial bunched cable 1.1KV grade stranded and compact aluminium phase conductor of size 3.5 x 50 sqmm + 1x25 sqmm (bare messenger with steel wire) with Aluminium alloy and Junction box The phase conductor shall be insulated with XLPE (Sioplas) compound Aluminium as per IS-14225-1995 including all fittings such as anchor clamp, suspension clamp, line connector, service clamp, Including End joints insulator piercing connectors, for taps from bare line etc, complete all as specified and directed by Engineer-in-Charge. Make : Grandlay/ Havells/ SCI/ Plycab |
| 81 | Supply and erect in position steel tubular swaged poles complete with cast iron base plate ,finial taper plug,bolts,nuts & screws as specified type 410 SP-31(9.00 metres long) complete all as specified and directed by Engineer-in-Charge. |
| 82 | M & L plain cement concrete 1:4:8 type D2 using 40 mm graded stone aggregate for foundation of poles complete all as specified and directed by Engineer-in-Charge. |
| 83 | M & L plain cement concrete 1:3:6 type C1 using 20 mm graded stone aggregate for poles complete all as specified and directed by Engineer-in-Charge. |
| 84 | S & F stay assembly for LT steel tubular poles comprising of 7/10 SWG galvanized MS stranded stay wire of required length, minimum tensile strength 70 Kg/mm (grade-2 quality) fixed to pole with and including FI clamps bolts, nuts, washers, galvanized steel stay rod 16mm dia 180 cm long bow 400x14mm nuts/bolts, washers all galvanized and two nos thimble, loop insulator of size 65x90mm vitreous, clearance dia of hole 16mm, stayplate of size 230x230x6mm including necessary excavation and earth work PCC 1:3:6 type C-2 using 40mm graded crushed stone aggregate in foundation and disposal of surplus spoil, upto 50 M all as specified and shown in plate No 1 of MES SSR Pt -I, complete all as specified and directed by Engineer-in-Charge. |
| 85 | Repair/Maint LT Panel board / Feeder pillar boxes , removing the carbon deposited inside the panel, cleaning the panel with cotton waste, applying two coat of synthetic enamel paint , checking the faults inside the panel board complete all as specified and directed by Engineer-in-Charge. Note : (a) Proper shut down shall be taken prior the commencement of work . (b) Fabrication of LT Panels for broken hinges shall be rectified. (c) LT Panel shall be painted with two coats of synthetic enamel paint over a coat of red oxide primer.(d) Marking on LT panels shall be done as per sources of power supply (1100 volts) and outgoing area by 10cm glow sign/paint all as directions of Engr-in-Charge. |
| 86 | Supply and fixing PVC insulation tape red,yellow, blue colour 25 mm 25 mtr length tape Roll Lall complete all as specified and directed by Engineer-in-Charge. |
| 87 | Terminal box made out of SMC with hinged door and locking arrangements of size 500 × 500 × 250 mm with 1000 Amps 4 Nos Bus bar connector,M.S. Clamps suitable for pole ,PCC/MS/GI/rail etc. with bolt, nut and washer ,electrical connections including MCB SP 6-32 Amps complete all as specified and directed by Engineer-in-Charge. Make - Sintex product or equivalent in Havells/CG/Polycab/Bajaj. |
| 88 | Terminal box made out of SMC with hinged door and locking arrangements of size 400 × 400 × 200 mm with 500 Amps 4 Nos Bus bar connector,M.S. Clamps suitable for pole ,PCC/MS/GI/rail etc. with bolt, nut and washer ,electrical connections including MCB SP 6-32 Amps complete all as specified and directed by Engineer-in-Charge. Make - Sintex product or equivalent in Havells/CG/Polycab/Bajaj. |
| 89 | Terminal box made out of SMC with hinged door and locking arrangements of size 300 × 300 × 150 mm with 500 Amps 4 Nos Bus bar connector,M.S. Clamps suitable for pole ,PCC/MS/GI/rail etc. with bolt, nut and washer ,electrical connections including MCB SP 6-32 Amps complete all as specified and directed by Engineer-in-Charge. Make - Sintex product or equivalent in Havells/CG/Polycab/Bajaj. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |