| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Repair /Maint to LT network system in AOR of Central Power House under GE (Utilities) Udhampur Contract No: GE/U-22/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Supply and fix in replacement of on load change over switch 415 V, 4 pole, 100 A open execution as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 3 | Supply and fix in replacement of on load change over switch 415 V, 4 pole, 125 A open execution as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 4 | Supply and fix in replacement on load change over switch 415 V, 4 pole, 160 A open execution as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 5 | Supply and fix in replacement on load change over switch 415 V, 4 pole,200 A open execution as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 6 | Supply and fix in replacement on load change over switch 415 V, 4 pole, 250 A open execution as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 7 | Supply and fix in replacement on load changeover switch 415 V, 4 pole, 320A open execution as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 8 | Supply and fix in replacement on load changeover switch 415 V, 4 pole, 400A open execution as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 9 | Supply and fix in replacement on load changeover switch 415 V, 4 pole, 630A open execution as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 10 | Supply and fix in replacement on load changeover switch 415 V, 4 pole, 1000A open execution as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 11 | Supply and fix in replacement of on load change over switch 415 V, 4 pole, 100 A with enclosure as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed. |
| 12 | Supply and fix in replacement of on load change over switch 415 V, 4 pole, 125 A with enclosure as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 13 | Supply and fix in replacement on load change over switch 415 V, 4 pole, 160 A with enclosure as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 14 | Supply and fix in replacement on load change over switch 415 V, 4 pole,200 A with enclosure as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 15 | Supply and fix in replacement on load change over switch 415 V, 4 pole, 250 A with enclosure as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 16 | Supply and fix in replacement on load changeover switch 415 V, 4 pole, 320A with enclosure as per existing make and model suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 17 | Supply and fix in replacement on load changeover switch 415 V, 4 pole, 400A with enclosure as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 18 | Supply and fix in replacement on load changeover switch 415 V, 4 pole, 630A with enclosure open execution as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 19 | Supply and fix in replacement MCCB, 415 volts, 4 pole 16 KA, 63A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 20 | Supply and fix in replacement MCCB, 415 volts, 4 pole 16 KA, 100 A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 21 | Supply and fix in replacement MCCB, 415 volts, 4 pole 16 KA, 125A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 22 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 160A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 23 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 200A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 24 | Supply and fix in replacement MCCB, 415 volts, 4 pole 25 KA, 250A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 25 | Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 320A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 26 | Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 400A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 27 | Supply and fix in replacement MCCB, 415 volts, 4 pole 36 KA, 630A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed. |
| 28 | Supply and fix in replacement MCCB, 415 volts, 3 pole 16 KA, 63 A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 29 | Supply and fix in replacement MCCB, 415 volts, 3 pole 16 KA, 100 A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 30 | Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 125A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 31 | Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 160A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 32 | Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 200A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 33 | Supply and fix in replacement MCCB, 415 volts, 3 pole 25 KA, 250A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 34 | Supply and fix in replacement MCCB, 415 volts, 3 pole 36 KA, 320A as per existing make and model or suitable equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 35 | Supply and fix in replacement MCCB, 415 volts, 3 pole 36 KA, 400A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 36 | Supply and fix in replacement MCCB, 415 volts, 3 pole 36 KA, 630A as per existing make and model suitable or equivalent make as per list of make at PS complete all as specified and directed by Engineer-in-Charge. |
| 37 | M&L for straight through jointing kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed and making the disturbed surface after relaying the cable and making joints suitable for aluminium conductor of size 16 to 25 Sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge.Note : Taking down the fault cable, excavation, returning filling, removal of surplus soil shall be measured and paid under relevant of this sch. |
| 38 | Description all as per Ser item no-36.00 here-in-before, but size of 35 to 70 Sqmm 3.5 core. |
| 39 | Description all as per Ser item no-36.00 here-in-before, but size of 95 to 150 Sqmm 3.5 core |
| 40 | Description all as per Ser item no-36.00 here-in-before, but size of 185 to 240 Sqmm 3.5 core |
| 41 | Description all as per Ser item no-36.00 here-in-before, but size of 300 to 400 Sqmm 3.5 core |
| 42 | Supply & laying in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 50 mm and inner dia 38 mm polyethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed by Engineer-in-Charge. |
| 43 | Description all as per Ser item No-41.00 here-in-before, but outer dia of 63 mm and inner dia 50 mm. |
| 44 | Description all as per Ser item No-41.00 here-in-before, but outer dia of 77 mm and inner dia 63 mm. |
| 45 | Description all as per Ser item No-41.00 here-in-before, but outer dia of 90 mm and inner dia 76 mm . |
| 46 | Description all as per Ser item No-41.00 here-in-before, but outer dia of 110 mm and inner dia 95 mm. |
| 47 | Description all as per Ser item No-41.00 here-in-before, but outer dia of 120 mm and inner dia 103.5 mm. |
| 48 | All as per item No-41 above but outer dia of 160mm and inner dia 126 mm. |
| 49 | M&L for disconnecting LT supply and taking out defective LT draw out EDO type ACB 440 V suitable for 800 Amps to 1250Amps and servicing by OEM .i.e Auth dealer cleaning the fixed and moving all parts, removing dust particles by using high speed blower applying grease/jelly to moving mechanism and moving parts, tightening nut bolts of all the components of ACB and complete testing and putting on full load complete all as specified and directed by Engineer-in-Charge. |
| 50 | S&F in replacement of isolating JAW contacts suitable for 800 Amps to 1250Amps LT draw out EDO type ACB complete all as specified and directed by Engineer-in-Charge. |
| 51 | S&F in replacement of polyester resin cast CT 800 / 5A suitable for 800 Amps to 1250Amps LT draw out EDO type ACB as per existing make and model complete all as specified and directed by Engineer-in-Charge. |
| 52 | S&F in replacement of ARC Chutes for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site. |
| 53 | S&F in replacement of Pole Unit for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Chargeat site. |
| 54 | S&F in replacement of Draw out terminals for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site. |
| 55 | S&F in replacement of Lower terminals for Air circuit brekers EDO type suitable for 800 Amps to 1250 Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site. |
| 56 | S&F in replacement of Upper terminals for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site. |
| 57 | S&F in replacement of Charging motor for Air circuit brekers EDO type suitable for 800 Amps to 1250 Amps as per existing make and model complete all as directed at site. |
| 58 | S&F in replacement of shunt trip and closing coil for Air circuit brekers EDO type suitable for 800 Amps to 1250 Amps complete all as specified and directed by Engineer-in-Charge. |
| 59 | S&F in replacement of manual Charging handle for Air circuit brekers EDO type suitable for 800 Amps to 1250Amps as per existing make and model complete all as specified and directed by Engineer-in-Charge at site. |
| 60 | S&F in replacement of under voltage trip device compact with UVT coil for Air circuit brekers EDO type suitable for 800Amp/ 630Amp as per existing make and model complete all as specified and directed by Engineer-in-Charge at site. |
| 61 | S&F in replacement of Safety shutter assembly for Air circuit brekers EDO type suitable for 800Amp/630Amp as per existing make and model complete all as specified and directed by Engineer-in-Charge at site. |
| 62 | S&F in replacement of Earth fault relay with NCT for Air circuit brekers EDO type suitable for 800/630 Amp as per existing make and model complete all as specified and directed by Engineer-in-Charge at site |
| 63 | Supplying and laying in replacement of GI tubing medium grade for cable protection in trenches/duct/fixing to pole/wall or in such similar position of following size complete all as specified and directed by Engineer-in-Charge:- |
| 64 | 100 mm dia |
| 65 | 80 mm dia |
| 66 | 50 mm dia |
| 67 | 40 mm dia |
| 68 | Taking up old unserviceable LT UG cables from trench/poles/wall etc of following size all as specified and directed:- |
| 69 | 16 Sqmm 4 core |
| 70 | 25 Sqmm 3.5 core |
| 71 | 35 Sqmm 3.5 core |
| 72 | 50 Sqmm 3.5 core |
| 73 | 70 Sqmm 3.5 core |
| 74 | 95 Sqmm 3.5 core |
| 75 | 120 Sqmm 3.5 core |
| 76 | 185 Sqmm 3.5 core |
| 77 | 240 Sqmm 3.5 core |
| 78 | 300 Sqmm 3.5 core |
| 79 | 400 Sqmm 3.5 core |
| 80 | Supply and laying LT UG cable XLPE insulated armoured and PVC sheathed 1100 volts grade with aluminium conductor stranded of following sizes all as specified and directed :- |
| 81 | 16 Sqmm 4 core |
| 82 | 25 Sqmm 3.5 core |
| 83 | 35 Sqmm 3.5 core |
| 84 | 50 Sqmm 3.5 core |
| 85 | 70 Sqmm 3.5 core |
| 86 | 95 Sqmm 3.5 core |
| 87 | 120 Sqmm 3.5 core |
| 88 | 185 Sqmm 3.5 core |
| 89 | 240 Sqmm 3.5 core |
| 90 | 300 Sqmm 3.5 core |
| 91 | 400 Sqmm 3.5 core |
| 92 | Excavation in soft / loose soil not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out incl forming of bottom for laying cable complete all as specified and directed by Engineer-in-Charge. |
| 93 | Excavation in hard / dense soil Including road cutting etc not exceeding 1.5 mtr wide and n exc 1.5 mtr depth and getting out incl forming of bottom for laying cable complete all as specified and directed by Engineer-in-Charge. |
| 94 | Returning filling using excavated soil including spreading leveling, watering and well ramming in layers n exc 25 cms complete all as specified and directed by Engineer-in-Charge. |
| 95 | Removal of surplus excavated material n.exc 50 mtrs and depositing where directed at a level n.exc 1.5 mtrs above the starting point all as specified and directed |
| 96 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming(a) MCCB 250 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-02 No.(b) C/O switch 250Amps 4 pole 50 KA-01 No (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 500 Amp,4 pole, not less than 1 MTR long mounted on insulators - 01 set |
| 97 | Outgoing (a) MCCB 160 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25 KA-03 No, (b) MCCB 100 Amps 4 pole , Ics=100%Icu-25/26 KA, 415 Volts,, with thermal adjustable and fixed magnetic setting with extended terminals -01 No. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level(iii) Outgoing MCCBs shall be fed with solid busbar connectors(iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately. |
| 98 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming(a) MCCB 400 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA- 1 No, (b) Change Over 400 A with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No, (c) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 1000 Amp,4 pole, not less than 1 MTR long mounted on insulators 01 set |
| 99 | Outgoing (a) MCCB 250 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-02No, (b) MCCB 160 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25 KA-02 No, Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level(iii) Outgoing MCCBs shall be fed with solid busbar connectors(iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately. |
| 100 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming(a) MCCB 630 A 4 pole 36 KA, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA- 2 No, C/O switch 630 Amps 50KA-01 No(b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 1000 Amp,4 pole, not less than 1 MTR long mounted on insulators 01 set |
| 101 | Outgoing (a) MCCB 250A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50 Hz, 415V with rupturing capacity 35 KA-04 Nos,(b) MCCB 160 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25 KA-02 No, Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level (iii) Outgoing MCCBs shall be fed with solid busbar connectors(iv) Cables shall be terminated using gun metal /SS glands. (v) including suitable thimbles/ lugs, nut bolts, washers fitted the cables.(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately. |
| 102 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming(a) MCCB 630 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA- 1 No, (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 1000 Amp,4 pole, not less than 1 MTR long mounted on insulators 01 set |
| 103 | Outgoing (a) MCCB 400A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-02 No, (b) MCCB 250 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-03 No, (c) MCCB 160 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25 KA-01No, Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level(iii) Outgoing MCCBs shall be fed with solid busbar connectors (iv) Cables shall be terminated using gun metal /SS glands.(v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately. |
| 104 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron,powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :-Incoming(a) MCCB 630 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA- 1 No, |
| 105 | Outgoing(b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 1000 Amp,4 pole, not less than 1 MTR long mounted on insulators 01 setNote- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level(iii) Outgoing MCCBs shall be fed with solid busbar connectors(iv) Cables shall be terminated using gun metal /SS glands. (v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables(vi) cable glands for incoming and out going suitable cables is including rate quoted by vendover(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately.(vii) 02 No's of Earhing connecting the same panel will be measured and paid separately. |
| 106 | Supply and pasting of stickers on transformer/Panel body using industrial-grade adhesive of custom-designed glue-based weatherproof stickers for transformers, size 6\\"x4\\", UV & water-resistant with the Following Details. Material: Vinyl or equivalent high-grade sticker with lamination. Note: 1) Sticker will be full-color digital print with lamination for UV protection. (surface to be cleaned before pasting). 2) Words (in English) for printing will be given by Engineer-in-charge during Execution. |
| 107 | Supply and installation of heat shrinkable/PVC cable sleeves with color-coded as per phase identification (Red, Yellow, Blue, Black, Green), suitable for LT Aluminium/aluminum cables of sizes ranging from 16 mm² to 300 mm², with thickness not less than 1.2 mm and temperature rating ≥ 90°C. The scope includes cutting, cleaning of cables, and proper application of sleeves with hot air gun or flame torch to ensure tight adhesion without air pockets. Work shall conform to IS: 7098/IS: 13592 and standard electrical practices complete all as specified and directed by Engineer-in-Charge. |
| 108 | M&L for aluminium thimble cable (Lugs) suitable for Cable of following sizes complete all as specified and directed by Engineer-in-Charge. |
| 109 | Description all as per Ser Item No 76.00 here-in-before, but for size 25 sqmm to 70 Sqmm |
| 110 | Description all as per Ser Item No 76.00 here-in-before, but for size 95 Sqmm to 120 Sqmm |
| 111 | Description all as per Ser Item No 76.00 here-in-before, but for size 150 Sqmm to 240 Sqmm |
| 112 | Description all as per Ser Item No 76.00 here-in-before, but for size 300 Sqmm to 400 Sqmm |
| 113 | Supply, install, 200 amp copper Bus bar with enclouser wall mounted size 800 mmX600 mmX300mm ,suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system with 160 Amps 4 pole 25KA MCCB , dust and vermin proof, made of 2 mm CRCA MS sheet for cable entry and locking arrangement complete all as directed and specified by Engineer-in-charge. |
| 114 | M&L Plain cement concrete 1:3:6 type C-2 as in foundations filling and mass concrete using 40 mm graded stone aggregate for repair of copping of poles, LT Panels foundation etccomplete all as directed and specified by Engineer-in-charge. |
| 115 | Earthing complete with GI earth electrode of size 60cmx60cmx6mm buried directly in ground vertically at a depth not less than 2.25 meter below normal ground level with top edge of earth plate at a depth not less than 1.5 meter below normal ground surrounded from all sides by 15 CM thick and packed layer of charcoal dust and common salt filling in alternate layers cleaned connected to and including GI earth strip 32X6 mm size up to 7.5 mtr by means of bolts, nuts, check nuts and washers made of galvanised iron and protected light grade 20 mm bore for watering and including funnel wire mesh, RCC pit cover 50 mm thick and PCC chamber pit with PCC 1:3:6 type C-2 (including excavation and earth work disposal of surplus soil to a distance not exceeding 50 meter) and testing after completion all as specified and shown on plate No 3 of SSR Part-I 2009 complete all as directed and specified by Engineer-in-charge.Note :- Contractor Shall provide earth pit chamber board of 3.15mm thick mild steel sheet of size 45cmX30cm fixed with12mm thick MS rod two nos up to 90 cm height by nuts/bolts including spray painting with two coats of synthetic enamel black paint complete MS sheet both side including writing letters 6cm height i.e Eart pit No, Location, Earthing test Value and date complete all as directed and specified by Engineer-in-charge. |
| 116 | Material and labour for Design, Composition, Supply & Installation of 4 inch thick ACP Box of size 12 feet X4 feet with MS pipe structure fix inside with 3mm Acrylic sheet with digitally printed 3M backlit vinyl on HP Latex Printer, Display both side, LED Modules complete upto 100 letters as specified size directed by Engr-in-Charge with Andaman and Nicobar command and MES logo fixed with four nos of MS pipe Heavy duty(C) 50mm bore up to 6Mtr height height by nuts/bolts and welding as required at site, spray painting with two coat synthetic enamel paint complete MS pipe including necessary excavation and PCC work for foundation of MS poles as directed at site, complete all as directed and specified by Engineer-in-charge. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |