| 1 | DESCRIPTION OF ITEMS |
| 2 | Cleaning and preparation of old painted surface of 9m LT/street light pole complete and painting with one coat of aluminium paint including channels/ brackets, street light brackets, cross arms and making Red & white strips with synthetic enamelled paint of 30 cm height, each alternative strip upto 1.5 mtr height and writing pole numbers with yellow synthetic enamelled paint after making circular base with black synthetic enamelled paint and applying two coats of white wash on PCC coping complete all as specified and directed. |
| 3 | Supply and fixing only PVC flat cable twin core PVC insulated and unsheathed solid aluminium conductor of size 6.00 Sqmm complete all as specified and directed. |
| 4 | S & F 1x60 watt LED building security light fitting , PDC housing,IP-65 with 4 KV inbuilt surg protection driver, pressure die-cast aluminium including fixing the same on GI pipe 25 mm dia bore light grade bracket, 1.5 mtr long including necessary cutting / bending /welding and fixed the same with two Nos FI clamps of 40x 4mm duly painted and suitable size of nut & bolts etc. and making electric connection with PVC three core copper flexible wire complete all as specified and directed. |
| 5 | S & F 1x70 watt LED building security light fitting , PDC housing,IP-65 with 4 KV inbuilt surg protection driver, pressure die-cast aluminium including fixing the same on GI pipe 25 mm dia bore light grade bracket, 1.5 mtr long including necessary cutting / bending /welding and fixed the same with two Nos FI clamps of 40x 4mm duly painted and suitable size of nut & bolts etc. and making electric connection with PVC three core copper flexible wire complete all as specified and directed. |
| 6 | Supply and fixing street light bracket made out of 25 mm dia GI pipe light grade of length upto 1.5 mtr bent to shape required with and including 2 Nos, 50 x 6 mm MS flat iron clamps with nuts, bolts, washer etc and applying one coat of aluminium paint to clamps including dismantling of old brackets complete all as specified and directed. |
| 7 | Excavation in trenches n. exc. 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of underground cable and getting out in soft/loose soil complete all as specified and directed. |
| 8 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed. |
| 9 | Removing of excavated soil to a distance not exceeding 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 10 | M&L local sand dry, filling in trenches around under ground cable complete all as specified and directed. |
| 11 | M&L for providing of new sub class 'B' bricks, old size, well burnt laid flat dry for protection of under ground cable complete all as specified and directed. |
| 12 | S & F in replacement GI pipe light grade 40 mm bore for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallaha etc complete all as specified & directed. |
| 13 | Supply laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric cables (heavy duty) with stranded aluminium copper conductor , 1100 volts grade of size 3.5 core 35 Sqmm complete including cutting of existing bituminous Road/payment/ footpath upto 0.75 metre in depth, 0.45m in width and getting out excavated material and making good the damaged portion after laying the pipe by providing PCC 1:2:4 type B2 upto top of the road all as directed by Engineer-in-Charge. |
| 14 | Supply laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric cables (heavy duty) with stranded aluminium copper conductor , 1100 volts grade of size 4 core 16 Sqmm including cutting of existing bituminous Road/payment/ footpath upto 0.75 metre in depth, 0.45m in width and getting out excavated material and making good the damaged portion after laying the pipe by providing PCC 1:2:4 type B2 upto top of the road all as directed by Engineer-in-Charge. |
| 15 | Supply laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric cables (heavy duty) with stranded aluminium copper conductor , 1100 volts grade of size 3.5 core 25 Sqmm complete including cutting of existing bituminous Road/payment/ footpath upto 0.75 metre in depth, 0.45m in width and getting out excavated material and making good the damaged portion after laying the pipe by providing PCC 1:2:4 type B2 upto top of the road all as directed by Engineer-in-Charge. |
| 16 | Supply and erection (in repair) in truly vertical position in replacement LT Steel tublar swaged pole complete with cast iron base plate finial taper plug, bolt , nut and screwed type 410 SP 31 09 mtrs long Class -10 including painting of poles with two coats of synthatic enamel paint in black and white strips upto 1.5 mtr height from coping over a coat of red oxide primer including numbering of poles including PCC 1:3:6 type C-2,using stone aggregate 40mm graded as incoping and for PCC 1:4:8 type D-2, using stone aggregate 40mm graded as in foundation for electric poles all as specified and directed by Engineer-in-charge. |
| 17 | M&L for earthing in replacement complete with galvanised or steel earth plate electrode of size 60cm x60cmx6mm thick burried directly in ground vertically ( to a depth not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to strip 32x 6 mm size with nuts, bolts , check nuts , washers, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick all around, top & bottom watering pipe 20mm bore of GI medium grade with funnel and wiremesh all as shown in electrical plate No. 5 of SSR -1991 Part I and connecting to arthing test point,main switch board and testing on completion including PCC chamber concrete 1:3:6 type C-2 and RCC cover 75mm thick with MS TMT bar 8mm dia @ 150mm c/c both ways in cement concrete(1:2:4) type B-1 all asshown in electrical plate in No 5 of SSR(Pt-I)1991 complete all as specified and dirfected by Engineer-in-charge. |
| 18 | M & L for junction box hot press moulded SMC of inside dimension size 250 x200x 100 mm and outside dimention 295 x 255 x 120 mm with locking arrangements consisting of necessary suitable arrangements for incoming & out going cables with cable glands & having aluminium bus bar 4 strips of 20x3mm for TPN on necessary epoxy base insulator and fixing of 6 Amp MCB SPN, including necessary 25x3mm flat iron clamps with nuts, bolts & washers all as specified and directed. |
| 19 | Supply and fixing in replacement of danger notice plate of 1.6mm thick, MS sheet, vitreous enamelled white, with letters, figuers and conventional skull and bones in signal red colour and fixed with MS clamps made out of flat iron 25x3 mm, nuts-bolts, of approved size for LT 20 x 15 cm all as specified and directed. |
| 20 | S&F MCCB 4 pole 250 Amps with breaking capacity 36 KA 415 volt & elect connection etc completeall as specrfied and directed. |
| 21 | S&F MCCB 4 pole 160 Amps with breaking capacity 36 KA 415 volt & elect connection etc completeall as specrfied and directed. |
| 22 | Supply and Fix MCCB 4 pole 200 Amps with breaking capacity 36 KA 415 volt & elect connection etc completeall as specrfied and directed. |
| 23 | S&F earth test point terminal block made of gun metal or phosphorus bronze of size 75x75x25mm, drilled and screwed including 3 Nos 8 mm dia, 25mm long, hex head screw complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 24 | S&F earth test point terminal block made of gun metal or phosphorus bronze of size 75x75x25mm, drilled and screwed including 3 Nos 8 mm dia, 25mm long, hex head screw complete all as specified and as directed. Please Enable Macros to View BoQ information |