| 1 | M&L for repair/overhauling of existing APFC panel 50 KVAR TO 75 KVAR capacity/rating incl cleaning with compressed air, tightening of all electric connections, replacement of wornout/ unserviceable cable of suitable capacity/rating with suppy & replacement of lugs, re-fixing of panel door with proper fixing/locking arrangement, glands to be provided as required at cable entries incl any work not included above but considered necessary for efficient performance of APFC panel and testing on completion complete all as specified and as directed by Engr-in-charge. Note: contractor should be be quote the rate including required neccessary material. |
| 2 | All as per item No 01 above but capacity 100-150 KVAR |
| 3 | Supply , Installation, testing and commissioning of in replacement of Power factor improvement panel of capacity 75 KVAR size 1100 mm x 700 mm x 250 mm, fully type test according to IEC 61439-1&2,IEC 61921 including interconnection with LT panel with appropriate size of electric cable for Main panel factory made, weather proof , dust and vermin proof (IP 65) suitable for Humidity: up to 95%,Average daily temperature: +35°C max,Ambient temperature: -5°C to 45°C, 1100 V/660 V grade 3 phase 50 HZ AC supply floor mounted , fabricated out of 14 SWG MS sheet welded on 40 x 40 x 3 mm angle iron frame / base of appropriate size and having four Nos angle iron legs made out of 40 x 40 x 6mm 60 cm long angle iron below frame with front door and back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles , lugs duly painted with grey epoxy powder coating after suitable chemical treatment , legs duly embedded in ground in PCC 1:3:6 of suitable size including locking arrangement suitable for mounting , with required sheet metal enclosures, thimbles , all as specified and directed by Engr-in-Charge and all other electric incoming and outgoing connections with PVC insulated multi stranded flexible copper NYVIN cable of suitable size and PVC flexible conduit medium quality as required , comprising of the following:- |
| 4 | (A) Insulated Bus bar of aluminium of 250 Amps capacity for three phase, fixed on insulators, Busbar should be PVC sleeved with Red, Yellow & Blue Colour, Bus bar support should be of SMC/DMC, Rated Impulse Withstand Voltage 8KV -01 Set |
| 5 | ( B) Incommer MCCB 160 Amp , four pole, short circuit breaking capacity 36 KA Icu at 415 V (KA rms), Ics =100% , IEC 60947-2 Adjustable thermal and fixed magnetic setting ,frame LS type, Front Face, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barrier.Make:- Schneider/ Siemens / ABB/L&T/Havells -1 No. |
| 6 | (C) Capacitor 75 KVAR (2 KVAR x 01 No, 3 KVAR x 01 No, 5 KVAR x 02 Nos, 10 KVAR x 02 Nos, 20 KVAR x 02 Nos) , square type capacitor heavy duty rated, capacitor bank of rated 440 volt , 3 phase, Maximum over current: 1.8 In,Overpressure protection,Discharge resistance 50 V - 1 min, Capacitance Tolerance -5%, +10%,Maximum permissible over current(with thermal protection included)1.43 In ,Maximum permissible over voltage 1.1 x Un, 8 h every 24 h,of rated 480 volt with detuned Reactor of de-tuning factor (P) 7% and suitable output of 75 KVAr at 440 volt suitable output , Overheating protection by thermostat confirming to IS-13340-1993/, 13341-1992 & IEC -60831-1+2. .Make:- Schneider/ Siemens / ABB/L&T/Havells |
| 7 | (D) Intelligent Power factor controller relay 8 steps, seven segment LED Display, Augiliary power factor, Algotitham, Dual password protection 4 digit display, Alarm Indication on Display switching time programmable 1 s to 1809 s, 90V - 550V 50/60Hz 1A/5A with RS485 Make:- Schneider/ Siemens / ABB/L&T/Havells -01 No |
| 8 | (G) SP MCB ,C-Curve, 240 volt, 10 KA, Control Circuit, .Make:- Schneider/ Siemens / ABB/L&T/Havells |
| 9 | (H) CT 250/5A , 10 V.A,CL:1.0,Resin Cast , CT Secondary wire Size should be 2.5 Sq mm.Make : Kalpa /AE/ L&T/Kappa -03 Nos |
| 10 | (L) Accessories for 75 KVAR capacitor Bank :- |
| 11 | (1) Capacitor Duty Contactor (3 KVAR x 02 Nos, 5 KVAR x 02 Nos, 12.5 KVAR x 02 Nos, 25 KVAR x 02 Nos ) 440 volt with damping resistors which limit inrush Current,440 volt ,3ph,50 Hz, Coil-220 Vac, .Make:- Schneider/ Siemens / ABB/L&T/Havells |
| 12 | (2) MCB, TPN, 10 Amp, 10 KA, 240 Volt, Make : Siemens/ ABB/Schneider/L&T/Havells -04 Nos |
| 13 | (3) MCB, TPN, 16 to 25 Amp, 10 KA, 240 Volt, Make : Siemens/ ABB/Schneider/L&T/Havells -04 Nos |
| 14 | (4) Digital Voltmeter of size 96x96mm (0-500V) with built in selector switch. |
| 15 | (5) Digital Ammeter of size 96x96mm (0-400A) with built in selector switch. |
| 16 | (6) Indication lamp 22.5mm dia LED type 240volts AC to show three phase availability-01Set. |
| 17 | (N) Ventilating fans of required size to dissipiate the heat liberated by capacitor units complete with automatic switching ON and OFF of fans depending upon the temperature of the Panel. 230 V AC, 2650 rpm,160 Cu.m/h, Flying leads - 04 Nos |
| 18 | (O) All accessories prewired with suitable size copper conductor cable insulated with fibre glass insulation to with stand high temperature, housed in cubical panel (CPRI approved) made out of 3.15 mm thick MS sheet factory made as per IEC 62208 duly powder coated front and rear door open able with locking arrangement complete with,IK 10 protection against mechanical Shocks as per IEC 62262 foundation as required or recommended by manufacturer. Make of APFC Panel: Note: APFC Panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf and the panels so manufactured will not be accepted. |
| 19 | Supply & fixing capacitor heavy 25 KVAR, cylindrical type, rated voltage 440 Vac, 3 phase, delta connection of Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down of unserviceable Capacitor all as specified and directed . |
| 20 | Supply & fixing capacitor heavy 10 KVAR, cylindrical type, rated voltage 440 Vac, 3 phase, delta connection of Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down of unserviceable Capacitor all as specified and directed . |
| 21 | Supply & fixing capacitor heavy 7.50 KVAR, cylindrical type, rated voltage 440 Vac, 3 phase, delta connection of Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down of unserviceable Capacitor all as specified and directed . |
| 22 | Supply & fixing capacitor heavy 5.00 KVAR, cylindrical type, rated voltage 440 Vac, 3 phase, delta connection of Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down of unserviceable Capacitor all as specified and directed . |
| 23 | Supply & fixing capacitor heavy 4.00 KVAR, cylindrical type, rated voltage 440 Vac, 3 phase, delta connection of Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down of unserviceable Capacitor all as specified and directed . |
| 24 | Supply & fixing capacitor heavy 3.00 KVAR, cylindrical type, rated voltage 440 Vac, 3 phase, delta connection of Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down of unserviceable Capacitor all as specified and directed . |
| 25 | Supply & fixing capacitor heavy 2.00 KVAR, cylindrical type, rated voltage 440 Vac, 3 phase, delta connection of Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down of unserviceable Capacitor all as specified and directed . |
| 26 | Supply & fixing capacitor heavy 1.00 KVAR, cylindrical type, rated voltage 440 Vac, 3 phase, delta connection of Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down of unserviceable Capacitor all as specified and directed . |
| 27 | Supply & fixing of Capacitor Duty Contactor 25 KVAR rating 440 volts 3 phase 50 Hz rating AC-6b,handle high inrush current capacity Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down old unsv contactor all as specified and directed . |
| 28 | Supply & fixing of Capacitor Duty Contactor 15 KVAR rating 440 volts 3 phase 50 Hz rating AC-6b,handle high inrush current capacity Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down old unsv contactor all as specified and directed . |
| 29 | Supply & fixing of Capacitor Duty Contactor 10 KVAR rating 440 volts 3 phase 50 Hz rating AC-6b,handle high inrush current capacity Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down old unsv contactor all as specified and directed . |
| 30 | Supply & fixing of Capacitor Duty Contactor 5 KVAR rating 440 volts 3 phase 50 Hz rating AC-6b,handle high inrush current capacity Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down old unsv contactor all as specified and directed . |
| 31 | Supply & fixing of Capacitor Duty Contactor 3 KVAR rating 440 volts 3 phase 50 Hz rating AC-6b,handle high inrush current capacity Make : L&T / Schneider/Havells/ legrand/GE/L&T including single PVC sheathed copper conductor cable of suitable size, thimble, nuts, bolts, washers etc complete including taking down old unsv contactor all as specified and directed . |
| 32 | Supply, Installation, testing and commissioning of Intelligent Power factor controller relay 8 steps, seven segment LED Display, Augiliary power factor, Algotitham, Dual password protection 4 digit display, Alarm Indication on Display switching time programmable IS to 1809, 90V - 550V 50/60Hz 1A/5A with RS485 Make:- Schneider/ Siemens / ABB/L&T/Havells complete including taking down old unsv contactor all as specified and directed . |
| 33 | Supply, Installation, testing and commissioning of Intelligent Power factor controller relay 12 steps, seven segment LED Display, Augiliary power factor, Algotitham, Dual password protection 4 digit display, Alarm Indication on Display switching time programmable IS to 1809, 90V - 550V 50/60Hz 1A/5A with RS485 Make:- Schneider/ Siemens / ABB/L&T/Havells complete including taking down old unsv contactor all as specified and directed . |
| 34 | Supply and fixing Ventilating fans (exhaust fan of panel ) 230 V AC, 2650 rpm,160 Cu.m/h, with flying leads of required size to dissipiate the heat liberated by capacitor units complete with automatic switching ON and OFF of fans depending upon the temperature of the Panel complete including taking down old unsv ventilating fan complete all as directed by Engr-in-Charge. |
| 35 | Supply, installation, testing in repair MCCB 250 Amp ,415 Volt,36 KA, 4 pole, with thermal & magnetic release rated Ultimate Shortcircuit Breaking Capacity Icu at 415 V (kA rms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = 100% Icu at 415 V (kA rms) 50%, complete all as specified and directed. |
| 36 | Supply, installation, testing in repair MCCB 320 Amp ,415 Volt,36 KA, 4 pole, with thermal & magnetic release rated Ultimate Shortcircuit Breaking Capacity Icu at 415 V (kA rms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = 100% Icu at 415 V (kA rms) 50%, complete all as specified and directed. |
| 37 | Supply, installation, testing in repair MCCB 160 Amp ,415 Volt,25 KA, 4 pole, with thermal & magnetic release rated Ultimate Shortcircuit Breaking Capacity Icu at 415 V (kA rms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = 100% Icu at 415 V (kA rms) 50%, complete all as specified and directed. |
| 38 | Supply, installation, testing in repair MCCB 100 Amp ,415 Volt,25 KA, 4 pole, with thermal & magnetic release rated Ultimate Shortcircuit Breaking Capacity Icu at 415 V (kA rms) Vac (kA rms), Rated Service short circuit Breaking Capacity Ics = 100% Icu at 415 V (kA rms) 50%, complete all as specified and directed |
| 39 | S&F in repair MCB TP 25 to 63 Amp 415 Volt ,'C' curve type and 10KA rupturing capacity all as specified and directed. |
| 40 | M&L in repair Amp meter 0-40 / 50 / 60 /100 Amps, 96mm x 96mm, digital type with inbuilt selectorswitch,auxiliary supply 230 V complete all as specified & directed . Make : AE/ L&T/Rishab/Meco/Enercon. |
| 41 | M&L inrepair Volt meter 0-500 Volts, 96mm x 96mm, digital type with inbuilt selectorswitch,auxiliary supply 230 V complete all as specified & directed . Make : AE/ L&T/Rishab/Meco/Enercon. |
| 42 | M&L in repair toggle switch/ Button Red/Green complete all as specified and directed. |
| 43 | M&L in repair indicating Lamp holder Red/Green complete all as specified and directed. |
| 44 | M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead using GI earth strip in size 32 x6 mm means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth strip protected by galvanized iron 40 mm dia medium grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, providing FRP Earthing pit chamber with cover designed for high loading capacity ,weather proof,rustproof,damper proof ,environment friendly,long use life of size 12 inches in square shape , PGI funnel with wire mesh charcoal/salt, funnel etc complete all as directed. |
| 45 | M&L for painting to steel structure/ fancing (both side wall)/ gate / board etc in any size/ make / thickness etc with MS fittings such as cross arms, clamps, pipe channel, bracing / wire mesh fencing ( both side will be considered as one unit) installation board etc after removing ,scraping cleaning etc to old paint using shyenthic enamel paint applying two coat (one as finishing ) over one coat of red primer oxided by paint spray gun including marking/ written indication sign/ words in diffrent colour etc complete all as site required and directed. Note : Paint colour shall be approved by Deptt. |
| 46 | M&L Electrical insulating rubber mat of size (3 mtr X2 mtr X5mm ) tested for LT Voltage1100 Volts complete all as specified and directed by Engr-in - Charge |
| 47 | Material & labour for continuous brick edging with width equal to the depth of brick sub class 'B' laid dry on end vertically, including necessary excavation and removing surplus spoil to a distance not exceeding 50m complete all as specified and as directed. |
| 48 | M&L for providing loose filling with broken stone aggregate 40 mm to 50 mm size structure from ground level grouted below ground level complete all as specified and directed by Engr-in-Charge. |
| 49 | M & L for digital printing on 5 mm thick Acrylic sheet wih aluminium bidding with provn of eyelids specified font size ,color of letter all as specified & directed by Engr-in-charge. |
| 50 | M& L for writing in Hindi or english on wall or steel surface by prepairng the surface by one coat paint,color and font size of letter and matter will be provided by department all as directed by EIC. |
| 51 | Supply and fixing Rolled Miled steel Framed work as cable trench cover confirming to Fe 410-W (gde-E-250) quality-A with gusset plates, rails braces, etc. complete, drilled for fixing of steel sheeting or other covering and hanging and fixing including taking out rusted frame complete with plaster and brick work as per site requirement all as specified and directed by Engr-in-Charge. |
| 52 | Supply and Fixing of Elegant look Anchor by Panasonic make 40 W AIO LED Solar Street lights having extruded alluminium housing, 100 Wp or more Mono Crystalline Panel/Laminates ((Made in India) fixed on the top of the luminaire housing, maintenance free 12.8 volts 36 Ah or more LiFePO4 battery(BIS certified) , BMS, MPPT charge controller, PIR sensor to provide 2 days (24 hrs ) back up in dimming mode . The luminaire is having IP 65 protection for critical components, IK 07 and having lumen output of > 6400 lm as per LM 79 report of third party NABL lab . The lumen efficacy should be > 160 lm/w and the maximum wattage of the AIO street light luminaire shall not be more than 40 W to deliver 6400 lm . Both the luminaire and Mono Crystalline Panel must be manufactured in India. The Solar lighting company must submit the third party NABL lab reports to justify the Lumen efficacy, luminaire output , IK 07 and IP 65 protection ( In house NABL lab reports will not be acceptable). The complete Solar lighting system must be warrantied for a period of 5 years . The Solar lighting companies must be having toll free base service network to provide immediate after sales service through their service network available in different districts of the state .The Solar lighting companies should submit the lighting design report prepared by their in house lighting design team if required as per the direction of engineer in charge. Lenses should be provided for effective distribution of light on the ground .The AIO solar street lights shall be of Anchor by Panasonic make PA040W11MLF2401or equivalent in Philips/Crompton/Havells |
| 53 | S&F in replacement Substation sign board made out of 3 mm thick aluminium composite panel sheet 1200 mm x 1200 mm including retro reflective sheeting on both side fixed on 50 mm dia stainless steel pipe of grade -304 (non scratchable) of wall thickness not less than 14 gauge including providing letters of not less than 75 mm height fixed on position with 50 mm dia stainless steel pipe (wall thickness of pipe shall be not less than 14 guage and vertical height of board above GL should be 2.4 m & below GL 60 cm deep ) and stainles steel pipe embedded in PPC 1:3:6 type C-1 using 20 mm graded stone aggregate in post holes of size 250 mm x 600 mm including 6 mm thick mild steel base size 200 mm x 200 mm X 600 mm including 6 mm thick mild steel base plate of size 200 mm x 200 mm x 6 mm thick for anchoring of post applying of two coats of anti corrossive paint on anchoring plate and writing letters and numbers on both sides of the board in English and Hindi (as required at site) should be as per IRC 30-1968 using 3M material, numbers of letters exc 50 but n exc 250 on each of the board etc complete all as specified and directed. Note : Square sign board should be cut in one coenerin half of width & depth of it all as specified by Engr-in-Charge. Please Enable Macros to View BoQ information |