|
| 1 | Providing erecting testing and commissioning pumping machinery at Raw water and Pure water works |
| 2 | Providing, installing, commissioning and testing of VERTICAL TURBINE, self water lubricated above floor type pump capable of discharging pure water at the rate of 150 Cum/ Hr. at the duty point head of 15.03 meter and operating within the head range of 20.00 to 10.00 meter including stainless steel basket strainer , bowl assembly , column assembly, discharge head , base plate of suitable size , connecting stool and sole plate of 16 mm thick etc. complete. The column pipes shall be manufactured from ERW pipes of 8 mm thick and each of 1.5 m length provided with anticorrosive paint and all line shafts and impellers shafts of stainless steel AISI 410 and impellers of aluminum bronze, including all consumable materials, accurate digital type Pressure gauge to read entire range of pressure complete with necessary tubing The complete pump assembly from discharge head to strainer shall have to be connected with nuts and bolts of stainless steel AISI 304/316. The pump should be operating at 1460 RPM speed and shall be complete as per the detailed specifications. AND Supplying, erecting, commissioning and testing at site flange mounted vertical Solid shaft (VSS) motor with “F” class insulation and operated on 415 volts, 50 Hz, 3 phase, AC supply,1460 rpm of 15 HP , squirrel cage TEFC induction motor as and per IS:325 complete with non-reversible ratchet arrangement and giving satisfactory trials & training to staff etc complete |
| 3 | Providing, installing, commissioning and testing of VERTICAL TURBINE, self water lubricated above floor type pump capable of discharging raw water at the rate of 150 Cum/ Hr. at the duty point head of 9.80 meter and operating within the head range of 14.00 to 06.00 meter including stainless steel basket strainer, bowl assembly, column assembly, discharge head , base plate of suitable size , connecting stool and sole plate of 16 mm thick etc. complete. The column pipes shall be manufactured from ERW pipes of 8 mm thick and each of 1.5 m length provided with anticorrosive paint and all line shafts and impellers shafts of stainless steel AISI 410 and impellers of aluminum bronze, including all consumable materials, accurate digital type Pressure gauge to read entire range of pressure complete with necessary tubing The complete pump assembly from discharge head to strainer shall have to be connected with nuts and bolts of stainless steel AISI 304/316. The pump should be operating at 1460 RPM speed and shall be complete as per the detailed specifications. AND Supplying, erecting, commissioning and testing at site flange mounted vertical solid shaft (VSS) motor with “F” class insulation and operated on 415 volts, 50 Hz, 3 phase, AC supply, 1460 rpm of 10 HP , squirrel cage TEFC induction motor as and per IS:325 complete with non-reversible ratchet arrangement and giving satisfactory trials & training to staff etc complete |
| 4 | Providing, erecting, commissioning of LT Set switchgear panel, cubical type, MS sheet fabricated from 14 gauge CRCA sheet including all accessories, switchgear, Copper busbar, foundation channel this item includes Designing, providing, erecting, testing & commissioning of FCMA starter without any active electronic component, moving parts & totally harmonics free, Star Delta starter lifted with all accessories including providing & applying painting to frame with international orange colour & two doors & covers Siemens gray etc. The starter shall be suitable for 15 HP induction motor operating at 415 / 440 Volts, 3 phase 50 Hz AC supply. The starter shall be Star Delta Connected The details list of material required for L.T. Starter panel required for L.T. Starter panel are mentioned in itemwise specification consist of material quantity and make including Base Frame and fabrication of appropriate size. The main components of panel are as below. 1) 200 A, 4 pole Microprocessor based MCCB - 1 Nos. for Incomer 2) 200 A, 4 pole Changeover Switch - 1 Nos. 3) Starter Feeders with 100 A MCCB and Star Delta Starter for 15 HP motor. - 2 Nos.+1 No. (Standbye) = 3 Nos. 4) Auxillary Feeder with separate compartment -- 63 A X 2 nos. ; 32 A X 8 Nos.; 5) Capacitor Bank 5 KVAR 2 No., 3 Kvar 2 No., 2 Kvar 5 No. 1 Kvar 5 No. |
| 5 | Providing, erecting, commissioning of LT Set switchgear panel, cubical type, MS sheet fabricated from 14 gauge CRCA sheet including all accessories, switchgear, Copper busbar, foundation channel this item includes Designing, providing, erecting, testing & commissioning of FCMA starter without any active electronic component, moving parts & totally harmonics free, Star Delta starter lifted with all accessories including providing & applying painting to frame with international orange colour & two doors & covers Siemens gray etc. The starter shall be suitable for 10 HP induction motor operating at 415 / 440 Volts, 3 phase 50 Hz AC supply. The starter shall be Star Delta Connected The details list of material required for L.T. Starter panel required for L.T. Starter panel are mentioned in itemwise specification consist of material quantity and make including Base Frame and fabrication of appropriate size.. The main components of panel are as below. 1) 200 A, 4 pole Microprocessor based MCCB - 1 Nos. for Incomer 2) 200 A, 4 pole Changeover Switch - 1 Nos. 3) Starter Feeders with 100 A MCCB and Star Delta Starter for 10 HP motor. - 2 Nos.+1 No. (Standbye) = 3 Nos. 4) Auxillary Feeder with separate compartment -- 63 A X 3 nos. ; 32 A X 8 Nos.; 5) Capacitor Bank 5 KVAR 2 No., 3 Kvar 2 No., 2 Kvar 5 No. 1 Kvar 5 No.. |
| 6 | Providing, erecting and commissioning M.S. Dismantling joint as per requirement and Department's approved drawing and specifications, including machining and rubber rings and suitable for 16 kg/cm2 working pressure with required flanges of suitable size with nut bolts etc complete. The joint should have through long bolts so that during normal working pressure there should be no sliding movement of sliding flanges. L.O.F. ( length over flange ) should not be less than 75% of dia.PW 6-1) 100 mm dia Joint |
| 7 | Supplying erecting testing and commissioning 100 mm dia DI/D/F Slanted seat swing rubber flap check valve (Non Return Valve) similar to RETO STOP Non return Valve having body of ductile cast iron GGG-50 and disc of ductile cast iron GGG-50 with fully encapsulated with EPDM Rubber (Potable water certified). Slanted seat is fixed for easy opening and quick closing. Full bore opening to achieve high discharges & reduced pressure drops. Check valve Electrostatic epoxy power /liquid coating (EP-P) inside and outside color blue RAL 5005 with minimum coating thickness of 250 microns. The EPDM rubber & Epoxy coating should be potable water certified. Face to face dimensions as per EN558-1, series 48 and flange connections as per EN 1092-2/IS 1538 including all labour , material complete. PN rating 1.0 Material of Construction :- Body & Cover :- Ductile iron to EN-JS 1030 (GGG-50) Disc :- Ductile iron to EN-JS 1030 (GGG-40, fully coated with EPDM rubber (portable water certified) Hinge Pin/Shaft :- Stainless Steel [ AISI 431] Cover Screws Nuts :- Stainless Steel [ AISI 304] Plug :- Brass Surface Protection :- Epoxy powder coating, min.-250 microns, color: RAL 5005 signal blue (potable water certified) |
| 8 | Supplying erecting testing and commissioning 100 mm dia DI D/F non-rising spindle soft seated glandless Gate Valves with body and bonnet of Ductile cast iron of grade GGG-50, wedge with fully encapsulated EPDM rubber (approved for drinking water ) and seals of NBR. The valves should be with replaceable stem nut and replaceable sliding shoes. Valve stems shall be of single piece thread rolled type. Valve shall have 3 “O” rings of NBR for stem sealing. Gate valve shall be compatible for buried application without valve chamber. Face-to- face dimensions as per BS 5163-89/IS 14846 – PD/EN 558 F4 and flange connections as per EN1092-2/IS 1538, Maximum valve operating torque should be at least 40% less than the torque as stated in the standard EN 1074. Electrostatic epoxy power / liquid coating (EP-P) inside and outside color blue RSL 5005 with minimum coating thickness of 250 microns. The EPDM rubber & Epoxy coating should be potable water certified. Material of construction :- Body, Bonnet :- Ductile Iron GGG40 (EN-JS-1030) Wedge, (Fully rubber encapsulated):- Ductile Iron GGG 40(EN-JS-1030) encapsulated with EPDM rubber- Portable water certified. Spindle / Stem: - SS: AISI 420 Stem Nut:- Brass Bonnet Gasket: - EPDM rubber potable water certified Internal fasteners: - Stainless Steel SS304 Stem Sealing :- Toroidal NBR sealing rings (Min 03 ‘O’ Rings) Coating: - Inside & Outside epoxy powder coated; DFT minimum 250 micron, shade RAL, 5005 (Signal Blue) potable water certified. excluding GST) PN 1.0 rating a) 100 mm dia |
| 9 | Supplying erecting testing and commissioning DI D/F non-rising spindle soft seated glandless Gate Valves and single chamber, double orifice DI Air valve with Triple function (Venting, admitting and venting during operation), in one piece construction (Both Large and small orifice housed in single housing itself), with capacity to handle air up to sonic velocity (300 m/s), with flange dimension acc. To EN 1092-2 /IS 1538. Body and cover bolts of austenitic GGG40. All internal parts such as float, shell etc & all cover bolts of austenitic alloy, steel and gaskets and seals of EPDM approved for potable water & avoid anti-bacterial growth which is mandatory for drinking water, with Electrostatic epoxy powder coating (EP-P) inside and outside color blue RAL 5005 with minimum coating thickness of 250 micron. Tamper proof design to avoid any external tampering leading to better functioning over longer periods of time and design to avoid any external access to safeguard the system from theft of water through introduction of foreign objects. The Air vlave should be able to seal to as low as 0.3 bar pressure which should be demonstrated during inspection. Material of Construction :- Body:- Ductile iron to EN-JS 1030 (GGG-40) Bonnet & Cover :- Ductile iron to EN-JS 1030 (GGG-40) Float :- Stainless Steel AISI 316 Ti Shell Body :- Stainless Steel AISI 321 Shut off Device & Ring :- Stainless Steel AISI 321 Gasket & Seal :- EPDM Rubber (Potable water certified) Lead Screws :- Stainless Steel AISI 304 Cylindrical Screw :- Stainless Steel AISI 304 Surface Protection :- Electrostatic epoxy powder coating, min.-250 microns, thickness, colour RAL 5005 Blue (portable water certified) a) 80 mm dia |
| 10 | Providing and fabricating structural steel work in rolled sections like joists, channels, angles, tees etc. as per detailed design and drawings or as directed including cutting, fabricating, hoisting, erecting, fixing in position making riveted / bolted /welded connections without connecting plates, braces etc. and including one coat of anticorrosive paint and over it two coats of oil painting of approved quality and shade etc. complete. |
| 11 | Providing, fabricating, erecting, M.S. Flanges sleep on type (all tables) of required size and thickness with both side machined.PW 10-1) Up to 300 NB |
| 12 | Erecting and h oisting in p osition and j ointing, t esting M.S./ C .I. D /F p ipes a nd s pecials in vertical position including cost of all jointing materials (rubber packing, nut bolts, etc.) labour, scaffolding, hydraulic testing etc. complete. Note:Only 85 % rate shall be payable till s atisfactory Hydraulic testing is given.5) 100 mm. |
| 13 | Providing and making flanged joints t o flanged C .I./M.S. p ipes of all classes/specials etc. including cost of all jointing materials (rubber packing, nut bolts, etc.), labour, hydraulic testing etc. complete. Note :Only 85 % rate shall be payable till s atisfactory Hydraulic testing is given.9) 400 mm. |
| 14 | Providing at departmental store or worksite fabricated M. S. Pipe and specials with socket and spigot ends for plain ends with necessary longitudinal and circumferential joints with required number of welding runs including cost of plates, welding rods & all kind of duties except octroi including loading unloading and transportation, etc. complete (Rates excluding GST) |
| 15 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3 core 35 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 16 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 70 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 17 | Supplying, installing and testing earthing with galvanised iron earth plate size 60 x 60 x 0.6 cm complete with all accessories of GI materials & recording the results as per specification No. EA-EP |
| 18 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required as per specification no EA-EP. |
| 19 | Providing and laying in situ /Ready Mix cement concrete M-20 of trap / granite /quartzite/ gneiss metal for R.C.C. work in foundations like raft, strip foundations, grillage and footings of R.C.C. columns and steel stanchions etc. including bailing out water, Steel centering formwork, laying/pumping cover blocks, compaction and curing roughening the surface if special finish is to be provided (Excluding reinforcement and structural steel) etc. complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) |
| 20 | Providing and fixing in position TMT - FE - 500 bar reinforcement of various diameters for R.C.C. pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardis, copings, fins, arches etc. as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete. |
| 21 | Point wiring in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, flush type switch,earthing and required accessories as per specification no. WG-PW/SW |
| 22 | Point wiring for independent plug in PVC trunking (casing-capping) with 1.5 sq.mm FRLSH grade copper wire, flush type switch,earthing and required accessories as per specification no. WG-PW/SW |
| 23 | Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification no. WG-PW/SW |
| 24 | Point wiring for ceiling fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification no. WG-PW/SW |
| 25 | Point wiring for independent plug in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification no. WG-PW/SW |
| 26 | Wiring for plug on board with flush Switch socket, copper wiring and earthing as per specification no. WG-PW/SW |
| 27 | Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25mm with accessories on wall/ceiling as per specification no. WG-MA/CON. |
| 28 | Supplying & erecting mains with 3x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places as per specification no. WG-MA/BW |
| 29 | Supplying & erecting mains with 3x6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places as per specification no. WG-MA/BW |
| 30 | Supplying & erecting mains with 3x10 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places as per specification no. WG-MA/BW |
| 31 | Supplying and erecting flush, shock proof plug socket 6 pin 6A and 16A with switch 16A combined unit erected in recess in 16 gauge M.S sheet box duly painted and connected with earth terminal and leads |
| 32 | Supplying, erecting & marking SPMCB 0.5A to 5A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 33 | Supplying, erecting & marking SP MCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 34 | Supplying, erecting & marking DP MCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 35 | Supplying, erecting & marking FP MCB 6A to 32A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 36 | Supplying, erecting & marking FP MCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 37 | Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 4 ways/phase (12 poles), with door, 1.2mm thickness, surface/flush mounted, IP 43 protection on provided iron/GI frame (horizontal busbar type) as per specification no. SW-MCBDB. |
| 38 | Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 8 ways/phase (24 poles), with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on provided iron/GI frame (horizontal busbar type) as per specification no. SW-MCBDB. |
| 39 | Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on provided iron/GI frame as per specification no. SW-MCBDB |
| 40 | Supplying & erecting CRCA sheet metal enclosures of 1.2mm thickness with 32 A, 3 pin plug & earth socket and 32A, 3 pin plug top with 32A triple pole MCB having rated short - circuit breaking capacity (Icn) 10kA complete erected on provided angle iron/GI frame. |
| 41 | Supplying & erecting triple pole and neutral distribution board (TPNDB), 3 pole MCCB as incomer & outgoing SP MCB (12 poles) or TP MCB of 4 ways (12 poles), with door, 1.2mm thickness, surface/flush mounted, on provided iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1 |
| 42 | Providing and erecting air circulator 600 mm. sweep oscillating type, wall mounting 1440 RPM without speed regulator, overheat protection unit, totally enclosed, flame proof motor suitable for 230/250 volts single phase, 50 cycles A.C. supply, core lead wire and with moisture proof treatment to winding and with ‘E’ class insulation. |
| 43 | Supplying and erecting exhaust fan medium duty 230 V A.C. 50 cycles 225 mm. 1400 RPM with condenser complete erected in position with necessary materials. Fan motor with moisture proof treatment and ‘E’ class insulation. |
| 44 | Supplying and erecting Energy Saving BLDC Ceiling fan 230 V A.C. 50 cycles 1200 mm, Max. Energy Consumption of 28W having service ratio (CMM/W) of Min. 8 , PF>0.9, THD<10% with IR remote control, Temperature Rise of Max. 40 deg.C, having external mounted control PCB completely erected in position as per specification no. FG-FN/CF |
| 45 | Supplying single door refrigerator domestic type of 170 to 195 litres storage capacity, minimum 5 Star inverter type, stabilizer free operation suitable for operation on 100V/300 V, 50 cycles complete with automatic temperature control, shall be marked on unit for sealed unit in refrigeration system and marking sr. no. and date of erection. |
| 46 | Supplying & erecting inverter LED batten 20W tube light fitting with polycarbonate housing, heat sink, integrated HF electronic driver, Min. 2600 mA Lithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 Hrs with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt, CRI>80, CCT of 6500K and THD<=20 % having useful life of minimum 25000 Hrs with over heat protection with minimum 2 years as per specification No. FG-IDF/LED. |
| 47 | Supplying and erecting fan hook of 10 mm. M.S. round bar grouted in RCC slab with making the site as original. |
| 48 | Supplying and erecting ‘B’ grade G.I. pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire. |
| 49 | Supplying and erecting Street light bracket made from 25 mm. dia ‘B’ class G.I. Pipe, 0.6 m in length along with pole cap of 300 mm length and 80 mm dia duly welded with provided leads as per specification no. FG-BKT/BPC. |
| 50 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 10 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 51 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 25 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 52 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 50 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. |
| 53 | Supplying & erecting inline cut point end pole D. P. Structure for 11/0.415 kV, 200 KVA Transformer |
| 54 | Supplying, installing, testing & commissioning 3 phase, 11/0.433 kV, 50 Hz., 200 kVA, Mineral oil im |
| 55 | Supplying and erecting 12.5 m (clear height) motorized high-mast (Top -150mm, Bottom- 360mm) hot dipped galvanized material with average minimum thickness 65 micron, made from high tensile structure grade steel as per BSEN - 10025 S 355/E350 & 3mm thickness, with base plate 25 mm thick x OD 520 mm grade as per IS-2062, pole made in single section & submerge arc welded, with lowering & raising motorized unit, wire rope stainless steel 316 grade 2 nos., 7x19 construction 5mm, SG-DG U clamps, double drum with assembly 250 kg, 5x2.5 Sq.mm. flexible copper cable with lantern carriage assembly suitable for max. 12 nos. luminaries and its control gear box, lightning arrestor, arrangement for fixing aviation light, night glow reflector on pole at suitable height, high-mast with serial number, factory inspection report/test report of high-mast should be provided as per specifications on provided foundation J type stud/bolts with double check nuts & necessary accessories complete. specification no. OH-PL/HM |
| 56 | Providing & erecting 7 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 130 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL |
| 57 | Providing and erecting galvanised 1000mm single arm sword type bracket with FRP dome and ball as per specification no. OH-PL/BKT |
| 58 | Providing and erecting galvanised 1000mm double arm sword type bracket with FRP dome and ball as per specification no. OH-PL/BKT |
| 59 | Supplying and erecting outdoor stand mounted feeder pillar for high-mast of the same manufacturer with 63A TPN MCB incomer, 24hr astronomical time switch with minimum 5 Years battery backup, 45 A TP contactor for automatic switching of luminaries, 2 no 9A contactors and raise/lower push button, and provision for termination of adequate size of incoming and outgoing cables complete erected in min. 14 SWG CRCA sheet box powder coated with supporting angles, self lock, gasket and slanting top erected on CC foundation complete. |
| 60 | Supplying and erecting integrated LED street light fitting 50W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 4400 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K,THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs at L70B50 including driver complete with minimum 2 Years warranty as per specification No. FG-ODF/SL. |
| 61 | Supplying and erecting mini feeder pillar with 415V, 200A FP MCCB as incomer and 2 outgoing circuits with HRC fuse base and cartridge of 100A with aluminium bus bar erected in 14 SWG CRCA sheet box with supporting angles, self locks, gasket and enclosure must be dust proof, rust proof, vermin and water resistant, having slanting top and erected on angle iron/ GI frame in provided C.C. foundation complete as per specification no. SW-MFP. |
| 62 | Supplying and erecting mini feeder pillar with 415V, 315-320A FPMCCB as incomer and 3 outgoing circuits with HRC fuse base and cartridge of 100A aluminium bus bar erected in 14 SWG CRCA sheet box with supporting angles, self locks, gasket and enclosure must be dust proof, rust proof, vermin and water resistant, having slanting top and erected on angle iron/ GI frame in provided C.C. foundation complete as per specification no. SW-MFP. |
| 63 | Supplying & erecting three phase, 415V, street light control panel upto the max load of 6kW, TPN MCB 40A, powder coated CRCA 14 SWG sheet, outdoor type, having IP54, IK10 protection, suitable rating contactor, 24 hrs. astronomical time switch with minimum 5 years battery back up, auto/manual selector switch, ON/OFF push buttons, indicator lamps, control wiring, metering device, etc. for automatic operation with overcurrent, short circuit, earth fault protection on provided iron frame / CC foundation as per specification SW-STCP. |
| 64 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 240 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 65 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 25 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 66 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 67 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 70 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 68 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 69 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 4 core 10 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 70 | Supplying & erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/bus bars or any other places as per specification no. WG-MA/BW |
| 71 | Supplying, erecting & marking SP MCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-MCB |
| 72 | Making Cement concrete foundation including excavation (45 x 45 x 120)cm deep in 1:3:6 cement concrete, 20 to 25 mm stone metal, (45 x 45 x 45)cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for 7 m pole) |
| 73 | Making Cement concrete foundation including excavation (60 x 60 x 150)cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metal with necessary curing and finishing complete.(for stay). |
| 74 | Supplying and spreading stone metal 25mm size for 100mm depth above the ground level complete. |
| 75 | Supplying and erecting fencing of section having size at least 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete with provided earthing as per specification no. SS-AS/FSG |
| 76 | Supplying and erecting 50 x 50 x 6 mm angle iron as corner support 2.45m long fixed at the middle of the fencing frame and the other side inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminium paint complete. |
| 77 | Supplying and erecting single leaf hinged door each 1500 mm in width x 2450 mm in height using B class GI pipe, hinges and angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation and painted complete as per specification no SS-AS/DLD |
| 78 | Supplying, installing and testing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.I. cover complete with all accessories of G.I. materials & recording the results as per specification no. EA-EP |
| 79 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 80 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint in an approved manner with joints required as per specification no EA-EP. |
| 81 | Supplying and erecting GI earth conductor of required sizes used for earthing or any other purposes on wall with necessary GI clamps fixed on wall/cable/ conduit with screws complete. |
| 82 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 75 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. |
| 83 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 90 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. Please Enable Macros to View BoQ information |